Troubleshooting; Identifying And Diagnosing Issues - Trane IntelliPak Programming Manual

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting

Troubleshooting
This section describes the possible error messages and other issues that you may encounter while
using the Tracer TD7 display.

Identifying and Diagnosing Issues

Diagnostic Name
Affects
and Source
Target
VFD Fault Supply
Unit
Fan - 1
VFD Fault Supply
Fan - 1
VFD Fault Supply
Fan - 1
VFD Fault Supply
Unit
Fan - 2
VFD Fault Supply
Fan - 2
VFD Fault Supply
Fan - 2
52
Severity
Persistence
Warning with
Latching
Special Action
Warning with
Latching
Special Action
Active
Modes
Criteria
[Inactive
Modes]
All
VFD Fault. Numerous drive faults can cause this general
fault. Reference the TR150 Installation and Operating
manual for a list of fault codes and descriptions.
Failure with Supply Fan 2 available:
Generate Supply Fan 1 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 2 NOT available:
Generate Supply Fan 1 Proving Failure
and Shutdown the unit
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this diagnostic
will be cleared in the Symbio 800 controller.
All
VFD Fault. Numerous drive faults can cause this general
fault. Reference the TR150 Installation and Operating
manual for a list of fault codes and descriptions.
Failure with Supply Fan 1 available:
Generate Supply Fan 2 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 1 NOT available:
Generate Supply Fan 2 Proving Failure
And Shutdown the unit
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this diagnostic
will be cleared in the Symbio 800 controller.
Reset
Level
Local
Local
RT-SVP011A-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents