Trane IntelliPak Programming Manual page 79

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Diagnostic Name
Affects
and Source
Target
Comm Loss: EXV
Circuit
1 Cktx
Comm Loss: EXV
1 Cktx
Comm Loss: EXV
1
Comm Loss: EXV
Circuit
2 Cktx
Comm Loss: EXV
2 Cktx
Comm Loss: EXV
2
Comm Loss:
Chiller
Local BAS
Interface
Comm Loss:
Local BAS
Interface
Comm: Local BAS
Interface
Comm Loss:
Circuit
Condenser
Cooling Valve
CktX
Comm Loss:
Condenser
Cooling Valve
CktX
Comm: Cond
Cooling Valve
Comm Loss:
Circuit
Condenser
Reheat Valve
Cktx
Comm Loss:
Condenser
Reheat Valve
Cktx
Comm: Cond
Reheat Valve
Comm Loss: Hot
Circuit
Gas Bypass Valve
Ckt1
Comm Loss: Hot
Gas Bypass Valve
Ckt1
Comm Loss: Hot
Gas Bypass Valve
Comm Loss:
Unit
Supply Air
Isolation Damper
Comm Loss:
Supply Air
Isolation Damper
Comm: SA Iso
Damper
RT-SVP011A-EN
Severity
Persistence
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Warning
Non-Latching All
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Active
Modes
Criteria
[Inactive
Modes]
All
Continual loss of communication between the MP and the
EXV Step Status has occurred for a 30 second period, OR
EXV Steps Maximum Position has not been received. If
EXV Steps Maximum Position has not been received, MP
will periodically request EXV Steps Maximum Position,
since it is only transmitted upon request.
All
Continual loss of communication between the MP and the
EXV Step Status has occurred for a 30 second period, OR
EXV Steps Maximum Position has not been received. If
EXV Steps Maximum Position has not been received, MP
will periodically request EXV Steps Maximum Position,
since it is only transmitted upon request.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful communication is
established with the LonTalk LLID (LCIC) or BacNet LLID
(BCIC).
All
Continual loss of communication between the MP and the
Condenser Reheat Cooling Status has occurred for a 30
second period.
All
Continual loss of communication between the MP and the
Condenser Reheat Heating Status has occurred for a 30
second period.
All
Continual loss of communication between the MP and the
Hot Gas Bypass Valve Step Status has occurred for a 30
second period, OR Hot Gas Bypass Valve Steps Maximum
Position has not been received. If Hot Gas Bypass Valve
Steps Maximum Position has not been received, MP will
periodically request Hot Gas Bypass Valve Steps
Maximum Position, since it is only transmitted upon
request.
All
Continual loss of communication between the MP and the
Supply Air Isolation Damper has occurred for a 30 second
period.
Troubleshooting
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
79