Trane IntelliPak Programming Manual page 69

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Diagnostic Name
Affects
and Source
Target
Hydronic Heat
Unit
Actuator Failed
Open
Hydronic Heat
Actuator Failed
Open
HH Actuator Fail
Closed
Chilled Water
Unit
Actuator Failed
Closed
Chilled Water
Actuator Failed
Closed
CW Actuator Fail
Closed
Chilled Water
Unit
Actuator Failed
Open
Chilled Water
Actuator Failed
Open
CW Actuator Fail
Closed
Outdoor Air
Unit
Damper Input
Outdoor Air
Damper Input
OA Damper Input
Relief Air Damper
Unit
Input
Relief Air Damper
Input
Rel Air Damper
Input
Return Air
Unit
Humidity Sensor
Return Air
Humidity Sensor
RA Humidity
Sensor
Return Air
Unit
Temperature
Sensor
Return Air
Temperature
Sensor
RA Temperature
Sensor
Outdoor Air
Unit
Humidity Sensor
Outdoor Air
Humidity Sensor
OA Humidity
Sensor
RT-SVP011A-EN
Severity
Persistence
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non-Latching All
with
Special
Action
Warning
Non-Latching All
with
Special
Action
Warning
Non-Latching All
Active
Modes
Criteria
[Inactive
Modes]
The hydronic heat actuator position has been greater
than the actuator command by 10% for 5 continuous
minutes.
The chilled water actuator position has been lower than
the actuator command by 10% for 5 continuous minutes.
The chilled water actuator position has been greater than
the actuator command by 10% for 5 continuous minutes.
The Outdoor Air Damper Input has failed out of range.
This voltage is an indication of actual damper position.
The Relief Air Damper Input has failed out of range. This
voltage is an indication of actual damper position.
The Return Air Humidity sensor has failed out of range.
This drives a 'fall back' response to Enthalpy Economizer
and Energy Wheel decisions.
The Return Air Temperature sensor has failed out of
range.
This drives a 'fall back' response to Enthalpy Economizer,
Energy Wheel, and possibly Rapid Restart decisions.
The Outdoor Air Humidity sensor has failed out of range.
No action is taken for this sensor failure only the Outdoor
Air Humidity Sensor Active has special action.
Troubleshooting
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
69