Troubleshooting
Diagnostic Name
Affects
and Source
Target
Supply Air High
Unit
Static Pressure
Lockout
Supply Air High
Static Pressure
Lockout
SA High Static
Press Lock
Discharge Air
Unit
High
Temperature
Detected
Discharge Air
High
Temperature
Detected
Discharge Air
High Temp
Return Air High
Unit
Temperature
Detected
Return Air High
Temperature
Detected
Return Air High
Temp
Ventilation
Unit
Override Mode A
Ventilation
Override Mode A
Ventilation
Override Mode A
Ventilation
Unit
Override Mode B
Ventilation
Override Mode B
Ventilation
Override Mode B
Ventilation
Unit
Override Mode C
Ventilation
Override Mode C
Ventilation
Override Mode C
Ventilation
Unit
Override Mode D
Ventilation
Override Mode D
Ventilation
Override Mode D
Ventilation
Unit
Override Mode E
Ventilation
Override Mode E
Ventilation
Override Mode E
62
Severity
Persistence
Immediate
Latching
Shutdown
with Special
Action
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Active
Modes
Criteria
[Inactive
Modes]
All
The supply air pressure has exceeded the Supply Air
Pressure High Limit Setpoint the 3
while the unit is operating in any mode.
VOM Behavior: During VOM this diagnostic is not
generated. See Supply Fan Control specification for more
information.
All
If the Discharge air temperature exceeds 200F then an
Immediate Stop will be generated. This is intended to
shut the unit down the unit if high duct temperatures
exist.
This must be from a Local Discharge Air Temperature
sensor (not an arbitrated value)
All
If the Return air temperature exceeds 135F then an
Immediate Stop will be generated. This is intended to
shut the unit down the unit if high duct temperatures
exist.
This Diagnostic is only available if Comparative Enthalpy
is Installed in configuration and the Return Air
Temperature is operating normally.
The unit is following VOM mode A.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
The unit is following VOM mode B.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
The unit is following VOM mode C.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
The unit is following VOM mode D.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
The unit is following VOM mode E.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
Reset
Level
Remote
rd
consecutive time
Local
Local
Local
Local
Local
Local
Local
RT-SVP011A-EN