H Comfort Protection Mode; I Fault Codes - Vaillant VWL 57/5 IS Operating, Installation And Maintenance Instructions

Hydraulic station
Table of Contents

Advertisement

H
Comfort protection mode
Code
Meaning
200
Sensor fault: Temp. air inlet
I
Fault codes
In the event of faults which are caused by components in the refrigerant circuit, inform customer service.
Code
Meaning
F.022
Water pressure too low
F.042
Fault: Coding resistor
F.073
Sensor fault: Build. circ. pressure
F.514
Sensor fault: Compr. inlet temp.
F.517
Sensor fault: Compr. outlet temp.
F.519
Sensor fault: Building circuit re-
turn temp.
F.520
Sensor fault: Building circuit flow
temp.
F.526
Sensor fault: EEV outlet temp.
F.546
Sensor fault: High pressure
F.582
Fault: EEV
F.585
Sensor fault: Capac. outlet temp.
F.718
Fan unit 1: Fan blocked
F.729
Compressor outlet temperature
too low
0020257319_02 Hydraulic station Installation and maintenance instructions
Description
Still possible to operate with existing,
functional outdoor temperature sensor
Cause
Pressure loss in the building circuit
due to leakages or air pockets
Building circuit pressure sensor
defective
Coding resistor damaged or not set
The sensor is not connected or the
sensor input has short-circuited
The sensor is not connected or the
sensor input has short-circuited
The sensor is not connected or the
sensor input has short-circuited
The sensor is not connected or the
sensor input has short-circuited
The sensor is not connected or the
sensor input has short-circuited
The sensor is not connected or the
sensor input has short-circuited
Sensor not connected or sensor
input has short-circuited
EEV is not connected correctly or
there is a cable break to the coil
The sensor is not connected or the
sensor input has short-circuited
There is no confirmation signal stat-
ing that the fan is rotating
The compressor outlet temperature
is lower than 0 °C for more than 10
minutes or the compressor outlet
temperature is lower than -10 °C
even though the heat pump is in the
operating characteristics.
Appendix
Remedy
Replace the air inlet sensor
Remedy
Check the building circuit for leaks
Top up with water, purge
Check the quality of the plug contact
on the PCB and on the cable har-
ness
Check that the pressure sensor is
working correctly
Replace the pressure sensor
Check that the coding resistor is
positioned correctly and, if required,
replace it.
Check and, if required, replace the
sensor
Replace the cable harness
Check and, if required, replace the
sensor
Replace the cable harness
Check and, if required, replace the
sensor
Replace the cable harness
Check and, if required, replace the
sensor
Replace the cable harness
Check and, if required, replace the
sensor
Replace the cable harness
Check and, if required, replace the
sensor
Replace the cable harness
Check the sensor (e.g. using an in-
stallation aid), and replace if neces-
sary
Replace the cable harness
Check the plug connections and, if
required, replace the coil from the
EEV
Check and, if required, replace the
sensor
Replace the cable harness
Check the air route and, if required,
remove any blockages
Checking the high-pressure sensor
Checking that the EEV is working
correctly
Checking for condensate leaking
from the temperature sensor (under-
cooling)
Check whether the 4-port diverter
valve is in the intermediate position
Checking the refrigerant volume for
overfilling
53