Appendix
Setting level
Contact details Telephone num-
ber
End the installation assistant?
1)
See the overview of fault codes: Fault lists are only available, and can only be deleted, if faults have occurred.
F
Status codes
Statuscode
S.34 Heating mode: Frost pro-
tection
S.100 Standby
S.101 Heating: Compressor
shutdown
S.102 Heating: Compressor
blocked
S.103 Heating: Prerun
S.104 Heating: Compressor
active
S.107 Heating: Overrun
S.111 Cooling: Compressor
shutdown
S.112 Cooling: Compressor
blocked
S.113 Cooling: Compressor
mode prerun
S.114 Cooling: Compressor
active
S.117 Cooling: Compressor
mode overrun
S.125 Heating: Immersion
heater active
S.132 Domestic hot water:
Compressor blocked
S.133 Domestic hot water:
Prerun
S.134 Domestic hot water:
Compressor active
S.135 Domestic hot water:
Immersion heater active
S.137 Domestic hot water:
Overrun
S.141 Heating: Immersion
heater shutdown
S.142 Heating: Immersion
heater blocked
S.151 Domestic hot water:
Immersion heater shutdown
S.152 Domestic hot water:
Immersion heater blocked
S.173 Anti-cycling time for
the energy supply company
S.202 Check programme: Pur-
ging of building circuit active
S.203 Actuator test active
S.212 Connection fault: Con-
trol not recognised
50
Values
Unit
Min.
Max.
Phone number
Meaning
If the measured outdoor temperature falls below XX °C, the temperature of the heating circuit's flow
and return is monitored. If the temperature difference exceeds the set value, the pump and com-
pressor are started without a heat demand.
There is no heat demand or cooling demand. Standby 0: Outdoor unit. Standby 1: Indoor unit
The heat demand is met, the demand is ended by the system control and the heat deficit is offset.
The compressor is switched off.
The compressor is blocked for heating mode because the heat pump is outside of its operating limits.
The start conditions for the compressor in heating mode are checked. Start the other actuators for
heating mode.
The compressor works in order to meet the heat demand.
The heat demand is met, the compressor is switched off. The pump and fan overrun.
The cooling demand is met, the demand is ended by the system control. The compressor is switched
off.
The compressor is blocked for cooling mode because the heat pump is outside of its operating limits.
The start conditions for the compressor in cooling mode are checked. Start the other actuators for
cooling mode.
The compressor works in order to meet the cooling demand.
The cooling demand is met, the compressor is switched off. The pump and fan overrun.
The immersion heater is used in heating mode.
The compressor is blocked for domestic hot water mode because the heat pump is outside of the
operating limits.
The start conditions for the compressor in domestic hot water mode are checked. Start the other actu-
ators for domestic hot water mode.
The compressor works in order to meet the domestic hot water demand.
The immersion heater is used in domestic hot water mode.
The domestic hot water demand is met, the compressor is switched off. The pump and fan overrun.
The heat demand is met, the immersion heater is switched off.
The immersion heater is blocked for heating mode.
The domestic hot water demand is met, the immersion heater is switched off.
The immersion heater is blocked for domestic hot water mode.
The mains voltage supply is interrupted by the energy supply company. The maximum anti-cycling
time is set in the configuration.
The building circuit pump is actuated in cyclical intervals, alternately in heating mode and domestic
hot water mode.
The sensor and actuator test is currently operating.
System control was previously detected but the connection is broken. Check the eBUS connection to
the system control. It can only be operated with the heat pump's additional functions.
Installation and maintenance instructions Hydraulic station 0020257319_02
Increment, select, ex-
Factory setting
planation
0–9
Empty
Yes, back
Setting