18. DEFAULT PARAMETER MAP

The numbers of the first column are simple indexes that are unrelated to the position on the device menu. The total amount of parameters can be different depending on the
applications. SUBMENUS: the parameters O1...O24 of the clock belongs to rtC label; V1...V30 ELECTRONIC VALVE belongs to EEV.
LABEL
VALUE
CLOCK AND DEFROST By pressing SET
rtC
it's possible to enter on RTC submenu
CbP
- - -
RTC presence
Hur
- - -
Hours.
Min
- - -
Minutes.
dAY
- - -
Day of the week.
Hd1
nU
First weekly day.
Hd2
nU
Second weekly day.
Hd3
nU
Third weekly day.
Energy saving cycle start during
iLE
0.0
workdays.
Energy saving cycle length during
dLE
0.0
workdays.
iSE
0.0
Energy saving cycle start during holidays.
Energy saving cycle length during
dSE
0.0
holidays.
Temperature increasing during Energy
HES
0.0
Saving cycle (Day/Night).
Ld1
6.0
Workdays First defrost start.
Ld2
13.0
Workdays Second defrost start.
Ld3
21.0
Workdays Third defrost start.
Ld4
nU
Workdays Fourth defrost start.
Ld5
nU
Workdays Fifth defrost start.
Ld6
nU
Workdays Sixth defrost start.
Sd1
6.0
Holidays First defrost start.
Sd2
13.0
Holidays Second defrost start.
Sd3
21.0
Holidays Third defrost start.
Sd4
nU
Holidays Fourth defrost start.
Sd5
nU
Holidays Fifth defrost start.
Sd6
nU
Holidays Sixth defrost start.
nU
Lo1
Workdays First light switch.
nU
Lo2
Workdays Second light switch.
nU
Lo3
Workdays Third light switch.
nU
Lo4
Workdays Fourth light switch.
nU
Lo5
Workdays Fifth light switch.
nU
Lo6
Workdays Sixth light switch.
dLo
0.0
Light on time during workdays.
nU
So1
Holidays First light switch.
nU
So2
Holidays Second light switch.
nU
So3
Holidays Third light switch.
nU
So4
Holidays Fourth light switch.
nU
So5
Holidays Fifth light switch.
nU
So6
Holidays Sixth light switch.
dSo
0.0
Holidays Sixth defrost start.
EEU
ELECTRONIC VALVE
1592023140 XM678D GB r2.8 01.09.2017.docx
DESCRIPTION
RANGE
Access to CLOCK submenu (if present)
Y = the optional RTC board is used.
- - -
N = the optional RTC board is not used even if mounted
- - -
-
- - -
-
Sun(0); SAt(6)
-
Sun(0); SAt(6); nu(7)
Set the first day of the week which follows the holiday times.
Sun(0); SAt(6); nu(7)
Set the second day of the week which follows the holiday times.
Sun(0); SAt(6); nu(7)
Set the third day of the week which follows the holiday times.
During the Energy Saving cycle the set point is increased by the
value in HES so that the operation set point is [SET + HES].
0.0 to 23h50min (143)
Format: hours.10min, resolution: 10min.
Set the duration of the Energy Saving cycle on workdays.
0.0 to 24h00min (144)
Format: hours.10min, resolution: 10min.
Format: hours.10min, resolution: 10min.
0.0 to 23h50min (143)
0.0 to 24h00min (144)
Format: hours.10min, resolution: 10min.
[-30.0°C to 30.0°C]
Set the increasing value of the set-point during the Energy Saving
[-54°F to 54°F]
cycle.
0.0 to 23h50min (143)
nU(144)
Ld1 to 23h50min (143)
nU(144)
Workdays defrost start: [Ldn to 23h50min] these parameters set
Ld2 to 23h50min (143)
the beginning of the eight programmable defrost cycles during
nU(144)
workdays. Ex: when [Ld2 = 12.4] the second defrost starts at 12.40
during workdays.
Ld3 to 23h50min (143)
nU = not used.
nU(144)
Format: hours.10min, resolution: 10min.
Ld4 to 23h50min (143)
nU(144)
Ld5 to 23h50min (143)
nU(144)
0.0 to 23h50min (143)
nU(144)
Sd1 to 23h50min (143)
nU(144)
Holidays defrost start: [Sdn to 23h50min] these parameters set
Sd2 to 23h50min (143)
the beginning of the eight programmable defrost cycles on
nU(144)
holidays. Ex: when [Sd2 = 3.4] the second defrost starts at 3.40 on
Sd3 to 23h50min (143)
holidays.
nU = not used.
nU(144)
Format: hours.10min, resolution: 10min.
Sd4 to 23h50min (143)
nU(144)
Sd5 to 23h50min (143)
nU(144)
0.0 to 23h50min (143)
nU(144)
Lo1 to 23h50min (143)
nU(144)
Lo2 to 23h50min (143)
nU(144)
Format: hours.10min, resolution: 10min.
Lo3 to 23h50min (143)
nU(144)
Lo4 to 23h50min (143)
nU(144)
Lo5 to 23h50min (143)
nU(144)
Set the duration of the light on time on workdays.
0.0 to 24h00min (144)
Format: hours.10min, resolution: 10min.
0.0 to 23h50min (143)
nU(144)
So1 to 23h50min (143)
nU(144)
So2 to 23h50min (143)
nU(144)
Format: hours.10min, resolution: 10min.
So3 to 23h50min (143)
nU(144)
So4 to 23h50min (143)
nU(144)
So5 to 23h50min (143)
nU(144)
Set the duration of the light on time on holidays.
0.0 to 24h00min (144)
Format: hours.10min, resolution: 10min.
By pressing SET you can enter electronic expansion valve
submenu.
XM678D
NOTES
9/