Synchronized Defrost - Emerson XM670K Installing And Operating Instructions

Controllers for multiplexed cabinet
Table of Contents

Advertisement

Action
Enter menu
Waiting for action
Enter section list
Select proper function
Confirm
Exit menu
(*) The devices on the LAN are indexed by using the Adr parameter (in ascending order).
EXAMPLES:
1. To modify the same parameter values in all the devices connected to the LAN: enter the multi-master menu. Select and
confirm ALL. Exit from the multi-master menu. Enter the programming menu and change the required parameter values.
The new values will be changed on all devices connected to the LAN.
CAUTION: At the end of programming, select the LOC section to switch OFF the
9.1.

Synchronized Defrost

The synchronized defrost allows multiple defrosts to be managed from different boards connected through the LAN connection.
In this way, the boards can perform simultaneous defrosts with the possibility to end them in a synchronized manner
CAUTION: In this case, the Adr parameter cannot be duplicated because defrost cannot be managed correctly.
BEGIN
Find Adr
Modify Adr
EXIT
Document Part # 026-4280 Rev 1
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
Button or display
Press the up arrow key for about three (3) seconds; the
SEC
The menu to change the section will be entered. SEC label will be displayed.
Press SET to confirm. The following list will be available to select the proper
network function.
LOC
To gain access only to the local device.
or
GLb
To share global command to all the devices connected to the LAN.
Select and confirm an entry by pressing SET button.
Press SET and the up arrow together or wait aproximately 10 seconds.
Table 9-1 - Multimaster Function Menu Action Buttons
Press for three (3) seconds, the rtC or other will be showed. The measurement unit
blinks.
Press the down arrow key several times to find the Adr parameter, then press SET.
Set the value of Adr parameter, then press SET to confirm the parameter.
or
Press both keys to exit from menu or wait for about 10 seconds.
Table 9-2 - Synchronized Defrost Keys
Notes
icon.
icon will be ON.
.
Page 10 of 33