Relay output
Alarm Class
Alarm Item
One Stage Dosing
Two Stage Dosing
Note
Load
Signal output: < 500 Ω at 14 to 24 VDC (active), 14 to 30 VDC (passive)
Relay output: 30 VAC/VDC, 100 mA
Passive signal input: 15 to 30 VDC, 2 to 15 mA
Connection check-up
1. Check individual wire installation by tugging firmly.
2. Firmly tighten cable glands and insert blanking plugs in unused cable entries.
3. Remove o-ring from lid.
4. Reinstate lid and screw in until mechanical stop. Wind back lid by one turn.
5. Mount o-ring by pulling it over the lid and tighten lid cover until you feel friction from the o-ring on both sides. Wind lid
further by one quarter of a turn to seal on the o-ring.
6. Reinstate and tighten lid lock screw.
7. Ensure that moisture does not penetrate to inside of electronics housing by creating a drip loop (bend cables downward)
immediately before cable glands.
12
X
Normally closed
SITRANS FCT030 transmitter
A5E03922778-006, 12/2013