Communication Networks
4. Press the board close to XC140 and on the bottom right corner until the complete insertion of the connector
and the plastic spacer.
5. Secure the board to the metallic spacers with the provided bolt.
6. Connect one end of the Fieldbus cable to the MVW3000 control rack, according to the
9-2.
7. Connect the other end of the Fieldbus cable to the Fieldbus board, according to the

9.1.2 Profibus DP

The inverter that is fitted with the Profibus DP Kit operates in slave mode, allowing the reading/writing of its
parameters through a master. The inverter does not start the communication with other nodes, it only answers
to the master controls. The physical medium uses a two-conductor twisted-pair cable (RS-485) allowing data
transmission at baud rates between 9.6 kbits/s and 12 Mbits/s. The
of a Profibus DP network.
9
9-2 | MVW3000
9-2 | MVW3000
DEVICENET
Figure 9.2: Connection to the Fieldbus board
Figure 9.3: Connection to the Fieldbus board
Figure 9.3 on page
PROFIBUS DP
Figure 9.4 on page 9-3
Figure 9.3 on page
9-2.
shows an overview