Detailed Settings In Eeprom Of Outdoor Unit - Panasonic U-4LE2E5 Service Manual & Test Run Service Manual

Mini vrf system, r410a
Hide thumbs Also See for U-4LE2E5:
Table of Contents

Advertisement

11. Detailed Settings in EEPROM of Outdoor
Unit
Never use the DN code unlisted in the following table.
DN
05
Outdoor fan silent mode
0C
Indoor unit drain pump forced operation
Measures against smell when indoor unit cooling
0D
thermostat OFF
1A
Demand 1 current (%)
1B
Demand 2 current (%)
1E
Demand remote controller display
23
E06 ignore function
27
Auto change over function for mini VRF system
2B
DP operation time for slime measures
2C
Indoor unit fan stop temperature shift
Condensation temperature adjustment
35
Lower temperature of B area (Tc_B) for heating mode
Condensation temperature adjustment
36
Upper temperature of B area (Tc_B) for heating mode
3E
PSccutgt delay-start setting
3F
Evaporating temperature control lower limit shift
40
Evaporating temperature control upper limit shift
Indoor unit fan's intermittent operation and operating
51
time when in cooling thermostat OFF
Indoor unit fan's intermittent operation and stopped
52
time when in cooling thermostat OFF
5F
High efficiency mode setting
Item
1 - 33
Control Functions - Outdoor unit
Setting No.
0=Invalid (P)
2=Silent mode 2,,,,,
(For details, see "4. Outdoor Unit Fan Control (6)")
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
(For details, see "5. Outdoor Unit CCU Control (4)")
0=Invalid (P)
1=Measures against smell
0=0%
45=45%,,,,,
160=160%
(For details, see "9. Demand Control")
0=0%
70=70% (P),,,,,
160=160%
(For details, see "9. Demand Control")
0=No demand display
1=When demand ON, "ready to start" display (P)
2=When forced thermostat OFF with demand ON,
"ready to start" display
(For details, see "9. Demand Control")
-1=Invalid (P)
1=1 ,,,,,
14 - 52=Never use
(For details, see "10. Other Functions")
0=Invalid (P)
40=40 minutes
60=60 minutes
120=120 minutes
240=240 minutes
(For details, see "10. Other Functions (1)")
20=20 minutes
40=40 minutes
60=60 minutes
(For details, see "5. Outdoor Unit CCU Control (4)")
-30=-30°C,,,,, 0=+0°C (P) ,,,,,50=+50°C
-7=-7°C -6=-6°C,,,,, 0=0°C (P) ,,,,, 7=7°C
-7=-7°C -6=-6°C,,,,, 0=0°C (P) ,,,,, 7=7°C
0=8 second delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8) second delay-start
3=(system address x3x8) second delay-start
-9=-9°C,,,,,0=0°C (P), 1=1°C,,,,,20=20°C
-9=-9°C,,,,,0=0°C (P), 1=1°C,,,,,20=20°C
30=30 seconds , 60=60 seconds (P) ,,,, 240=240 seconds
5=5 minutes (P), 10=10 minutes, 15=15 minutes, 20=20 minutes,
25=25 minutes, 30=30 minutes
0=Invalid (P), 1=Valid
(For details, see "4. Outdoor Unit Fan Control (8)")
Mini VRF SYSTEM
(P) : Factory preset mode
1=Silent mode 1
16=Silent mode 16
40=40%
100=100% (P) ,,,,,
-1=No control
40=40%
100=100% ,,,,,
-1=No control
0=0
13=13
30=30 minutes
50=50 minutes
90=90 minutes
180=180 minutes
30=30 minutes (P)
50=50 minutes
1