Panasonic U-4LE2E5 Service Manual & Test Run Service Manual page 135

Mini vrf system, r410a
Hide thumbs Also See for U-4LE2E5:
Table of Contents

Advertisement

3. Mini VRF Alarm Codes
E16 Alarm
Alarm code
E16
Alarm meaning
More indoor units are found in Auto Addressing than the setting on outdoor PCB.
Alarm conditions
The number of indoor units was too many when auto address setting was performed.
After initial communications were completed, an unrecognized unit was detected.
Probable cause
(1) The number of indoor units set at the indoor unit quantity setting SW (SW3, SW4) on the
Outdoor Unit Control PCB is less than the number set.
(2) The inter-unit control wiring is wired incorrectly.
Check
(1) See the section "7. TEST RUN" and check the number of indoor units that is set.
(2) Check the inter-unit control wiring at the indoor and outdoor units.
Correction
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform auto
address setting again.
Example
Notes
E20 Alarm
Alarm code
E20
Alarm meaning
No indoor unit responded in Auto Addressing.
Alarm conditions
When auto address setting was performed, no indoor units were recognized.
Probable cause
(1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.
(2) Serial wire is disconnected at the outdoor unit.
(3) The power is OFF at all indoor units in the system.
Check
(1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.
(2) Check whether serial wire is disconnected at the terminal base.
(3) Check the power at the indoor units.
Correction
(1) Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.
Example
Notes
Position of serial terminal base
U-4LE2E5, U-5LE2E5, U-6LE2E5
U-4LE2E8, U-5LE2E8, U-6LE2E8
terminal base
6 - 7
Mini VRF SYSTEM
Trouble Diagnosis
terminal base
6