16. Detailed Settings in EEPROM of Outdoor Unit

Never use the DN code unlisted in the following table.
DN
04
Operation for using snowfall sensor
05
Outdoor fan silent mode
0C Indoor unit drain pump forced operation
Measures against smell when indoor unit cooling
0D
thermostat OFF
1A Demand 1 current (%)
1B Demand 2 current (%)
1E Demand remote controller display
23
E06 ignore function
2A Dew condensation prevention control of indoor unit
2B DP operation time for slime measures
2C Indoor unit fan stop temperature shift
Condensation temperature adjustment
35
Lower temperature of B area (Tc_B) for heating mode
Condensation temperature adjustment
36
Upper temperature of B area (Tc_B) for heating mode
3E PSccutgt delay-start setting
Item
1 - 23
Setting No.
0=No sensor & control (P)
2=No sensor & no control
0=Invalid (P)
2=Never use
(For detail, refer to 7-5)
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
8-11=delay drive when stopped
12-15=Delay drive when thermostat OFF & stopped
(For detail, refer to 9-4)
0=Invalid (P)
1=Measures against smell
0=0% ,,,,,
45=45% ,,,,,
160=160%
(For detail, refer to 15-1)
0=0% ,,,,,
70=70% (P) ,,,,,
160=160%
(For detail, refer to 15-1)
0=No demand display
1=When demand ON, "ready to start" display (P)
2=When forced thermostat OFF with demand ON,
"ready to start" display
(For detail, refer to 15-2)
-1=Invalid (P)
1=1 ,,,,,
14 - 52=Never use
0=Invalid (P)
2=40 minutes
4=60 minutes
20=20 minutes
40=40 minutes
60=60 minutes
(For detail, refer to 9-4)
-30=-30°C ,,,,,
50=+50°C
(For detail, refer to 9-3-2)
-7=-7°C
0=0°C (P) ,,,,,
(For detail, refer to 2-3-3)
-7=-7°C
0=0°C (P) ,,,,,
(For detail, refer to 2-3-3)
0=8 seconds delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8) second delay-start
3=(system address x3x8) second delay-start
(For detail, refer to 14-2)
Mini VRF SYSTEM
Control Functions
(P) : Factory preset mode
1=Sensor & control
3=Sensor & no control
1=Silent mode
3=Never use
40=40% ,,,,,
100=100% (P) ,,,,,
-1=No control
40=40% ,,,,,
100=100% ,,,,,
-1=No control
0=0
13=13
1=30 minutes
3=50 minutes
30=30 minutes (P)
50=50 minutes
0=+0°C (P) ,,,,,
-6=-6°C ,,,,,
7=7°C
-6=-6°C ,,,,,
7=7°C
1