Panasonic U-4LE2E5 Service Manual & Test Run Service Manual page 14

Mini vrf system, r410a
Hide thumbs Also See for U-4LE2E5:
Table of Contents

Advertisement

2. Compressor Control
3. Compressor Control
(3) Forced Stopping of Compressor
Once a compressor stops, it will not start for a period of 3 minutes (3-minute forced OFF).
However, this is not applied when the compressor was forced to stop as the result of a special control
operation. (Start control, Defrost control, Refrigerant oil recovery control, etc.)
(4) Capacity Control of Compressor (Roadmap Control)
1
1
Capacity control of compressor (start & stop of compressor and increase & decrease of inverter frequency)
are controlled according to the numerical value of the pressure sensor installed at the outdoor unit and the
temperature sensor installed at the indoor unit heat exchanger.
* The pressure detected by the pressure sensor is converted to the saturated temperature.
High pressure saturated temperature is converted from values detected by the high pressure sensor.
Low pressure saturated temperature is converted from values detected by the low pressure sensor.
2
This control is performed every 30 seconds.
3
When cooling operation, evaporation temperature (= antifreeze control) and condensation temperature
(= high pressure prevention control) are applied.
When heating operation, condensation temperature (= high pressure prevention control) is applied.
Definition of evaporation temperature (Te)
Lowest temperature of all indoor units' evaporation temperature (E1, E3) in the system including the
stopped indoor units
Definition of condensation temperature (Tc)
Outdoor units' high pressure saturated temperature
Load level varies from a minimum of 0 to a maximum of 30 on 1 to 1 basis up to 31 levels.
When the indoor unit stops (including thermostat OFF), the level shows "0".
In the case of test run mode, the actual level implies "30" even if a PC monitor indicates "31".
* In the case that the compressor is stopped from such as special controls, load level does not turn to "0"
even if the indoor unit is most likely to be in stopped state.
The indoor unit demand level varies according to the following 2 conditions.
Intake temperature difference:
Difference between indoor unit remote control set temperature and intake temperature (TA)
Discharge temperature difference:
Difference between preset discharge setting temperature according to the type of indoor unit and
actual discharge temperature (TF)
Load level increases when the differential temperature noted above indicates plus (+) value and
decreases when it indicates minus (-) value.
However, the types of units which are set to control the discharge temperature vary according to the
lowest value from the intake temperature difference and discharge temperature difference.
Te target and Tc target are controlled by the maximum value of all indoor units load level.
Control Functions - Outdoor unit
1 - 4
2WAY VRF SYSTEM
Mini VRF SYSTEM
Control Functions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents