Panasonic S-15MY2E5A CZ-KPY3A Installation Instructions Manual
Panasonic S-15MY2E5A CZ-KPY3A Installation Instructions Manual

Panasonic S-15MY2E5A CZ-KPY3A Installation Instructions Manual

Hide thumbs Also See for S-15MY2E5A CZ-KPY3A:
Table of Contents

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS

– VRF System Air Conditioner –
for Refrigerant R410A
■ R410A Models
Model No.
Indoor Units
Indoor Units
Type
Type
4-Way Cassette
Y2
60×60
ENGLISH
Read through the Installation Instructions before you proceed with the installation.
In particular, you will need to read under the "IMPORTANT!" section at the top of the page.
FRANÇAIS
Lisez les instructions d'installation avant de commencer l'installation.
En particulier, vous devez lire la section "IMPORTANT!" en haut de la plage.
ESPAÑOL
Lea las Instrucciones de instalación antes de proceder con la instalación del equipo.
En concreto, deberá leer detenidamente la sección "¡IMPORTANTE!" situada al principio de la página.
DEUTSCH
Lesen Sie die Einbauanleitung, bevor Sie mit der Installation beginnen.
Insbesondere die Hinweise im Abschnitt "WICHTIG!" oben auf der Seite müssen unbedingt gelesen werden.
ITALIANO
Leggere le Istruzioni di installazione prima di procedere con l'installazione.
Prestare particolare attenzione alla sezione "IMPORTANTE!" all'inizio della pagina.
NEDERLANDS
Lees de installatie-instructies zorgvuldig door voor u begint met de installatie.
U moet vooral het gedeelte waar "BELANGRIJK!" boven staat heel goed lezen.
PORTUGUÊS
Leia cuidadosamente as instruções de instalação antes de prosseguir com a instalação.
Em particular, é necessário ler as informações na secção "IMPORTANTE!" na parte superior da página.
ΕΛΛΗΝΙΚΆ
Διαβάστε τις Οδηγίες εγκατάστασης πριν συνεχίσετε με την εγκατάσταση.
Συγκεκριμένα, θα χρειαστεί να διαβάσετε την ενότητα «ΣΗΜΑΝΤΙΚΟ!» στο πάνω μέρος της σελίδας.
БЪЛГАРСКИ
Прочетете инструкциите за инсталиране преди да продължите с инсталирането.
В частност, ще трябва да прочетете раздела „ВАЖНО!" в горната част на страницата.
РУССКИЙ
Перед выполнением установки прочтите инструкцию по установке.
В частности, вам следует прочесть раздел «ВАЖНО!» вверху страницы.
УКРАЇНСЬКА
Перш ніж продовжити встановлення, прочитайте вказівки зі встановлення.
Зокрема, обов'язково прочитайте розділ «ВАЖЛИВО!» вгорі сторінки.
B.INDONESIA
Bacalah seluruh Petunjuk Pemasangan sebelum Anda melakukan pemasangan.
Secara khusus, Anda perlu membaca bagian "PENTING!" di bagian atas halaman.
AMP Air Conditioning
15
22
S-15MY2E5A
S-22MY2E5A
(CZ-KPY3A)*
(CZ-KPY3A)*
(CZ-KPY3B)*
(CZ-KPY3B)*
Rated Capacity
28
36
S-28MY2E5A
S-36MY2E5A
(CZ-KPY3A)*
(CZ-KPY3A)*
(CZ-KPY3B)*
(CZ-KPY3B)*
www.ampair.co.uk | sales@ampair.co.uk
45
56
S-45MY2E5A
S-56MY2E5A
(CZ-KPY3A)*
(CZ-KPY3A)*
(CZ-KPY3B)*
(CZ-KPY3B)*
*Panel (optional parts)
F616379

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic S-15MY2E5A CZ-KPY3A

  • Page 1: Installation Instructions

    INSTALLATION INSTRUCTIONS – VRF System Air Conditioner – for Refrigerant R410A ■ R410A Models Model No. Indoor Units Indoor Units Rated Capacity Type Type S-15MY2E5A S-22MY2E5A S-28MY2E5A S-36MY2E5A S-45MY2E5A S-56MY2E5A 4-Way Cassette (CZ-KPY3A)* (CZ-KPY3A)* (CZ-KPY3A)* (CZ-KPY3A)* (CZ-KPY3A)* (CZ-KPY3A)* 60×60 (CZ-KPY3B)* (CZ-KPY3B)* (CZ-KPY3B)* (CZ-KPY3B)*...
  • Page 2: Important

    IMPORTANT! • Provide a power outlet exclusively for each unit, and full disconnection means Please Read Before Starting having a contact separation in all poles This air conditioner must be installed by the sales dealer must be incorporated in the fixed wiring or installer.
  • Page 3 When Connecting Refrigerant Tubing • This product must not be modified or disassembled • When performing piping WARNING WARNING under any circumstances. work do not mix air except Modified or disassembled for specified refrigerant unit may cause fire, (R410A) in refrigeration electric shock or injury.
  • Page 4: Important Information Regarding The Refrigerant Used

    IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type: R410A value: 1975 GWP = global warming potential Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.
  • Page 5: Table Of Contents

    CONTENTS Page Page IMPORTANT! ........2 8.
  • Page 6: General

    1. GENERAL 1-3. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local This booklet briefly outlines where and how to install the source, you will need: air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all Deoxidized annealed copper tube for refrigerant tubing.
  • Page 7: Selecting The Installation Site

    2. SELECTING THE INSTALLATION SITE 3. HOW TO INSTALL THE INDOOR UNIT 2-1. Indoor Unit 3-1. Preparation for Ceiling Suspension This unit uses a drain pump. Use a carpenter’s level to check AVOID: that the unit is level. ● areas where leakage of flammable gas may be expected. ●...
  • Page 8: Installing The Drain Pipe

    Keep the length of the bolt Down-slope Upward-slope from the bracket to 40 mm Air conditioner Ceiling body Air Trap No Air Trap Paper model for Set screw for paper installation Adjust to the same model (4 pieces) Fig. 3-6 height Open the ceiling board along the outer edge of the paper model.
  • Page 9: Electrical Wiring

    4. ELECTRICAL WIRING 4-2. Recommended Wire Length and Wire Diameter for Power Supply System 4-1. General Precautions on Wiring (B) Power supply cable (1) Before wiring, confirm the rated voltage of the unit as Minimum power Model shown on its nameplate, then carry out the wiring closely Power supply supply cables Length...
  • Page 10: Wiring System Diagrams

    4-3. Wiring System Diagrams Indoor unit (No. 1) Power supply Outdoor unit 220/230/240V ~50/60Hz INV unit Ground Power supply Remote 380/400/415V, 3 N~, 50Hz controller Ground Ground Ground Indoor unit Ground (No. 2) Inter-outdoor-unit control wiring Power supply Ground 220/230/240V ~50/60Hz Outdoor unit Ground INV unit...
  • Page 11 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
  • Page 12: For Stranded Wiring

    How to connect wiring to the terminal ■ For stranded wiring (1) Cut the wire end with cutting pliers, Stranded wire Special Screw then strip the insulation to expose washer the stranded wiring about 10 mm and Ring tightly twist the wire ends. (Fig. 4-7) pressure Ring pressure terminal...
  • Page 13: How To Process Tubing

    5. HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or The liquid tubing side is connected by a flare nut, and the gas water from entering the tubes before they are used. tubing side is connected by brazing.
  • Page 14: Insulating The Refrigerant Tubing

    Heat Insulation For the flare nuts at tubing connections, be sure to use the ● flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refrigerant tubing that is used must be of the correct wall thickness as shown in the table below. CAUTION Tightening torque Be sure to perform heat insulation on the drain, liquid and...
  • Page 15: Taping The Tubes

    5-4. Taping the Tubes 6. HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH-SPEC WIRED (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with REMOTE CONTROLLER armoring tape in 1 bundle. To prevent condensation from (OPTIONAL PART) overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 16: When Using Wireless Remote Controller Instead Of Wired Remote Controller

    • Place decorative panel on the screws (3 pcs.) before (6) After completing the aforementioned, install the removed fitting, move decorative panel as illustrated and tighten part by reversing the steps for removal. all the screws (4 pcs.). LM (CN033) WL (CN130) Ground screw Securing the tentative...
  • Page 17: How To Install Wireless Remote Controller Receiver

    8. HOW TO INSTALL WIRELESS REMOTE CONTROLLER RECEIVER Air Filter Installation NOT E Refer to the Operating Instructions attached to the optional Wire- Insert the air filter less Remote Controller Receiver. to the tabs of the intake grille. 9. APPENDIX ■...
  • Page 18 ■ Troubleshooting If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Indoor unit ● Symptom Cause Noise Sound like streaming water during Sound of refrigerant liquid flowing inside unit ●...
  • Page 19 Check Before Requiring Services ● Symptom Cause Remedy Air conditioner does not run Power failure or after power failure Press ON/OFF operation button on remote control at all although power is turned unit again. Operation button is turned off. Switch on power if breaker is turned off. ●...
  • Page 20 – NOTE – AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...

Table of Contents