3. Recovering Refrigerant
3-2. Refrigerant Recovery Procedures (Indoor Unit)
The flowchart below shows the refrigerant recovery procedures you must follow when replacing or repairing the
indoor unit due to trouble in the refrigerant circuit.
START
3-2-1. Cooling operation (for all units)
Ball valve is provided in the indoor unit
3-2-2. Refrigerant recovery
procedures (1)
Turn off all equipment in system
When replacing or repairing a faulty
unit, let other normal indoor units run
(excluding indoor unit where refrigerant
is recovered)
Power can independently be turned off
for indoor unit where refrigerant is
recovered
Change controllable number of indoor
units (including changes in group
control and integrated-control settings)
Other indoor units can operate normally
Replace or repair faulty unit
Check for leakage in repaired unit
Evacuate air from repaired unit
Charge refrigerant in repaired unit
(Amount of charge should equal that
recovered by refrigerant recovery unit)
Change controllable number of indoor
units (including changes in group
control and integrated-control settings)
Open ball valve
Ready for normal operation
END
Service work performed on indoor units is done simultaneously using the service ports at the liquid (narrow tube) side and the
gas (wide tube) side ball valves. Refer to each section in the "Installation Instructions" on refrigerant charging, leak checking, and
evacuation procedures.
3-2-1. Cooling operation (for all units)
(1) If the remote controller is used for maintenance of the outdoor unit
1 Connect the outdoor unit maintenance remote controller to the RC connector on the outdoor unit control
PCBs. Then start a test run of all units. (Press and hold the
2 Press the
(MODE) button and change to cooling operation and ensure that the cooling is performed.
A
See the section 4 for the detail of the outdoor maintenance remote controller operation. It may be possible to
determine whether operation is cooling or heating by touching the gas tubing.
Cooling : low temperature (20℃ or lower)
Heating: high temperature (60℃ or higher)
CAUTION
3-2-3. Refrigerant recovery
NO
YES
NO
YES
Modify power to permit turning off
power to refrigerant-recovered
NO
indoor units independently
YES
The gas tubing becomes hot (60°C or higher) in heating mode. Be careful so as
not to be burnt when touching the tubing.
procedures (2)
recovered by refrigerant recovery unit)
recovered by refrigerant recovery unit)
(CHECK) button for 4 seconds or longer.)
3 - 5
Mini VRF SYSTEM
Outdoor Unit Repair Procedures
Turn off all equipment in system
Replace or repair faulty unit
Check for leakage in repaired unit
Evacuate air from repaired unit
Charge refrigerant in repaired unit
(Amount of charge should equal that
Ready for operation
END
Replace or repair faulty unit
Check for leakage in repaired unit
Evacuate air in repaired unit
Charge refrigerant in repaired unit
(Amount of charge should equal that
Open the ball valve
Ready for normal operation
END