Pyronix PCX 78 Installation Manual page 19

Table of Contents

Advertisement

Battery charging specification
Float voltage
Battery low voltage cut-off
Recharge time
Control panel type
Standby battery capacity current
Standby battery capacity current
Fuses
230 V mains fuse for mains terminals
The battery connect 'kickstart' button is used to power-up the control panel when there is no mains
supply present. For example: if you wish to program a panel that is being fitted in a new-build
premises before the mains supply has been fully installed. To use it – Hold for 5 seconds and then
release.
For more information, see "The Printed Circuit Board" on page 17
Ensure that the battery jumper is in the correct position for the capacity of battery that you
have connected – otherwise the panel may under-charge a large battery or over-charge and
damage a smaller battery.
PCX Installation Guide
13.8 Vdc
10.5 V
< 24 hours
300 mA (3 Ah to 6 Ah)
700 mA (7 Ah to 17 Ah)
Value
T500 mAH anti-surge slow blow 250 V
102017852 - V01
Type
Ceramic
19