Maintenance

11.3 Replacing the coding element at the power connector of the system power supply and load current supply

11.3
Replacing the coding element at the power connector of the system
power supply and load current supply
Introduction
The coding consists of a 2-part coding element.
Ex factory a part of the coding element is inserted into the back side of the power connector.
The other part is firmly inserted in the system power supply or load power supply.
This prevents the insertion of a power connector of a system power supply or load power
supply into a module of a different type.
Do not manipulate the coding element, or leave it off
• Changing or replacing the coding element can result in dangerous system states.
• To avoid damage, do not change or replace the coding element.
• You must not remove the coding element.
Replacement parts scenario
Insertion of the coding element into a new power connector in the case of a replacement
part.
Dangerous voltage
When installing the coding element, you must take into account the supply voltage of the
system power supply and load power supply: 24 V DC, 24/48/60 V DC or 120/230 V AC/DC
Only install the coding element with switched-off voltage.
You must insert the coding element in such a way that the power connector matches the
power supply module in terms of voltage.
270
DANGER
DANGER
S7-1500R/H redundant system
System Manual, 10/2018, A5E41814787-AA