Siemens Simatic ET 200SP User Manual page 64

Analog input module ai 4xtc hs
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Codes for measuring range
The following table contains the codes for the measuring ranges of the analog input module.
You need to enter these codes in the relevant x+1.
Table A- 13
Measuring range
Voltage
50 mV
80 mV
250 mV
1 V
Thermocouple
Type B
Type N
Type E
Type R
Type S
Type J
Type L
Type T
Type K
Type U
Type C
Type TXK
Limits for hardware interrupts
The following tables contain the permitted limits for hardware interrupts (in each case, the
usable value is given). The limits depend on the selected measurement type and the
selected measuring range. The value for the high limit must be greater than the value for the
low limit.
Table A- 14
Voltage
±50 mV
58.7927 mV
-58.7945 mV
Table A- 15
Thermocouple
°C
2069.9
-119.9
Analog input module AI 4xTC HS (6ES7134-6JD00-0DA1)
Manual, 03/2019, A5E42405270-AB
A.3 Parameter assignment and structure of channel parameter (REAL representation)
Codes for measuring range
Voltage limits
±80 mV
94.0683 mV
-94.0712 mV
Limits for thermocouple types B, C, and E
Type B
°F
K
°C
3276.5
2343.1
2499.9
-183.9
153.3
-119.9
Code
0000 0001
0000 0010
0000 0011
0000 0101
0000 0000
0000 0001
0000 0010
0000 0011
0000 0100
0000 0101
0000 0110
0000 0111
0000 1000
0000 1001
0000 1010
0000 1011
±250 mV
± 1 V
293.963 mV
1.17585 V
-293.972 mV
-1.17589 V
Type C
°F
K
°C
3276.5
2773.1
1199.9
-183.9
153.3
-269.9
Parameter data records
High limit
Low limit
Type E
°F
K
2191.9
1473.1
High limit
-453.9
3.3
Low limit
63

Advertisement

Table of Contents
loading

Table of Contents