A.3
Parameter assignment and structure of channel parameter (REAL
representation)
The data record of the module has an identical structure, regardless of whether you
configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can
reconfigure the module in your user program regardless of your programming. This means
that you can use all the functions of the module even if you configured it via PROFIBUS-
GSD.
Parameter assignment in the user program
You can reassign the parameters of the module in RUN. For example, the measuring range
of selected channels can be changed in RUN without having an effect on the other channels.
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data record
128. The parameters set with STEP 7 will not be changed on the CPU, which means that the
parameters set in STEP 7 will be valid again after a restart.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output
parameter contains a corresponding error code.
You will find a description of the "WRREC" instruction and the error codes in the STEP 7
online help.
Analog input module AI 4xTC HS (6ES7134-6JD00-0DA1)
Manual, 03/2019, A5E42405270-AB
A.3 Parameter assignment and structure of channel parameter (REAL representation)
Meaning
11
Code for the measuring range invalid
H
12
Value for fixed reference temperature
H
invalid
21
Code for temperature unit invalid
H
22
Code for measuring range resolution inva-
H
lid or scalable measuring range not per-
missible
Parameter data records
Solution
Use valid code for measuring range, see
Table A-5 Codes for measuring range
(Page 56).
Use valid reference temperature, see Fig-
ure A-3 Structure of byte x to x+21 for
channel 0 to 3 - S7 representation
(Page 55), byte x+8.
Use valid code for temperature unit Figure
A-3 Structure of byte x to x+21 for channel
0 to 3 - S7 representation (Page 55), byte
x+4.
Use valid code for measuring range
resolution.
Disable scalable measuring range.