Siemens Simatic ET 200SP User Manual page 49

Analog input module ai 4xtc hs
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Technical specifications
Error limits for thermocouples
Operational limit for thermocouples (in the entire temperature range)
Operational limit for thermocouples type B, C, E, R, S (in the entire tem-
perature range)
Basic error limit for thermocouples (operational limit at 25 °C)
Basic error limit for thermocouples type B, C, E, R, S (operational limit at
25 °C)
Overall error limits when using internal compensation
The indicated error limits apply as of the following temperatures:
1
For thermocouple type B, C, E, R, S: ±9 K
2
For thermocouple type B, C, E, R, S: ±5.5 K
3
Dimension drawing
See equipment manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/58532597/133300)
48
1
Operational limit (in the entire temperature range at static thermal
state, ambient temperature change < 0.3 K/min)
Basic error limit (operational limit at 25 °C at static thermal state,
ambient temperature change < 0.3 K/min)
Thermocouple type T: -200 °C
Thermocouple type K: -100 °C
Thermocouple type B: +700 °C
Thermocouple type N: -150 °C
Thermocouple type E: -150 °C
Thermocouple type R: +200 °C
Thermocouple type S: +100 °C
(Interference frequency suppression: None)
1
2
3
Analog input module AI 4xTC HS (6ES7134-6JD00-0DA1)
±3.75 K
±7.5 K
± 2.5 K
±5 K
±5.25 K
±3 K