Siemens Simatic ET 200SP User Manual page 25

Analog input module ai 4xtc hs
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.4 Scalable measuring range
Rules
● The measuring range center must be within the nominal range of the underlying
measuring range. It is specified in integers.
● The scalable measuring range is spanned symmetrically over the measuring range
center. Depending on the resolution, various value ranges result (
● The scalable measuring range is limited by underflow and overflow of the underlying
measuring range:
– It is clipped at the underflow when it falls below the limit.
– It is clipped at the overflow when it exceeds the limit (
Example
The following example illustrates the effect of scalable measuring ranges:
Scalable measuring range with 2 decimal places in hexadecimal S7 format
Scalable measuring range with 3 decimal places in hexadecimal S7 format
Scalable measuring range which is cut off at the overflow of the underlying measuring range (clipping)
Figure 4-2
Examples of scalable measuring ranges
24
).
Analog input module AI 4xTC HS (6ES7134-6JD00-0DA1)
Manual, 03/2019, A5E42405270-AB
,
).