Section 5: Maintenance

Operate Transfer Switch

Operate the transfer switch at least once a month. This
can be done by performing a normal test of the system.
The system test switch only simulates failure of the utility
power source, therefore, service will be interrupted only
during the actual transfer of the load.
Clean and Inspect Transfer
Switch
Protect the transfer switch against construction grit, metal
chips, excessive moisture, and other harmful dirt at all
times. At least once a year, turn off all power supplies to
the switch, then brush and vacuum away dust and dirt
that has accumulated inside the enclosure. After
cleaning, inspect the transfer switch carefully. Look for
evidence of arcing, burning, hot spots, charring, and
other damage. If any of these are found, have the switch
assembly checked by an authorized service technician.

Main Current Carrying Contacts

At least once annually, have an Independent Authorized
Service Dealer (IASD) check the main current carrying
contacts in the transfer mechanism. They will repair or
replace major components that have been found
defective.
Contactor Part
Main Contacts
Between movable
contact and bus bars
Operating
Actuator and other
Mechanism
parts of the
contactors. Does not
include movable
contacts
Integrated Load Center Owner's Manual
TABLE 1. Recommended Lubricants
Description
Rheolube 363
Mobilgrease 28
Mobiltemp SHC 32
Polo Moly Complex Grease #NLG12
Dow Corning (Molykote) BR2 Plus

Twelve-Volt Batteries (Two)

The batteries in this transfer switch are of the
rechargeable lead acid type. Replace with Generac part
#0D2568, Panasonic catalog no. LC-R12R3PU, or
equivalent every three (3) years.
After replacing batteries, be sure to tape thermistor back
in place for proper battery charger operation.

Lubrication

Operating parts inside the transfer mechanism have
been properly lubricated at the time of assembly. Under
normal conditions, no additional lubrication should be
required. The service technician should lubricate all
recommended
mechanism components are replaced.
NOTE: Use only specified greases to lubricate contactor
parts. DO NOT USE ANY SUBSTITUTES.
A table of recommended lubricants is provided below.
Recommended Lubricants
Maintenance
points
whenever
major
Manufacturer
Nye Lubricants, Inc., USA
Mobil Oil Co., USA
Mobil Oil Co., USA
Polo Lubricants, USA
Dow Corning Co., USA
transfer
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

004892004877

Table of Contents