Siemens FDOOT221 Technical Manual page 63

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

No.
Name
0
Universal
1
2
Robust
1
Universal
3
Sensitive
2
4
Universal Fast
3
5
Super Sensitive
6
Ultra Sensitive
Building Technologies
Fire Safety
Only select this parameter set if high sensitivity is required and no deceptive
phenomena (visible aerosols) can be expected.
Response time [s]
50
80
50
30
8
12
12
Delivery status; can only be selected in collective mode and MS8 mode.
1
Default status in AnalogPLUS mode as DO1131A
2
Can only be selected in AnalogPLUS mode
3
Parameter sets 0...5 meet the criteria of standard EN 54-7.
Parameter set 5 meets the criteria of standard EN 54-27. You will find more
information in documents A6V10446712 and A6V10427924. See 'Applicable
documents [➙ 9]' chapter.
25BParameter sets: Neural fire detector
Sensitivity
To open fire/smoldering fire
[%/m]
2.3 / 8.0
2.3 / 8.0
2.3 / 8.0
1.6 / 5.6
2.3 / 8.0
1.0 / 1.5
0.35 / 0.5