3BPlanning
4
27BParameter sets: Heat detector
4.5.1.2 Specifications
No.
Name
1
A1R
60 °C rate of rise
2
BR
80 °C rate of rise
3
A1S
60 °C maximum
4
BS
80 ℃ Maximum
14
Application-specific parameter sets
15
4.5.2 Heat detector FDT221
4.5.2.1 Description
68 | 138
Building Technologies
Fire Safety
Operating
Static activation
temperature
temperature
typ. / max.
[°C]
[°C]
25 / 50
60
40 / 65
80
25 / 50
60
40 / 65
80
Applicable with slow temperature increases <1 K/min.
1
Applicable with fast temperature increases of >10 K/min. When there is a slow temperature
2
increase of <10 K/min, this value rises by a few degrees.
All parameter sets apart from 14 and 15 comply with standard EN 54-5.
Heat detector FDT221 has the following parameter sets:
●
A1R (1)
●
BR (2)
See also
Description [➙ 67]
Differential activation
temperature
1
2
∆T [K]
25
29
–
–
Differential activation possible
from ambient temperature:
[°C]
3
30
–
–
007004_t_en_--