3.3 Features of the 'Technical Ambient Supervision
Environment:
Temperature
°C
Sensory
Building Technologies
Fire Safety
18BFeatures of the 'Technical Ambient Supervision Message'
Message'
The 'Technical Ambient Supervision Message' cannot be configured on all fire
control panels. Observe the information in the 'List of compatibility'.
'Technical Ambient Supervision Message' mode detects an increase in
temperature caused by hysteresis above a specified threshold.
Temperature monitoring compares the current measured temperature with a preset
threshold value.
You can configure the following parameters for the point detector:
Threshold value for temperature
Alarming when the temperature threshold value is exceeded or undershot
Hysteresis range
Parameter configuration is carried out using the 'SintesoWorks' software.
T [°C]
t
Signal analysis
Figure 3: Signal processing by the 'Technical Ambient Supervision Message'
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
According to EN 54-2, signals for temperature detection must not be used to
control fire detection equipment.
See also
 Point detectors with 'Technical Ambient Supervision
Message' function [➙ 28]
2BStructure and function
Algorithms
3
Warning level for
Technical Ambient
Supervision Alarm
Result