Siemens FDOOT221 Technical Manual page 130

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

7BSpecifications
8
55BTechnical data FDO221, FDO241
Device characteristics
Ambient conditions
Mechanical data
Standards
130 | 138
Building Technologies
Fire Safety
Response sensitivity:
FDO221
FDO241
Compensation, zone 'normal'
Compensation, zone 'Information/Impairment'
Compensation speed
Detector diagnosis
Permissible operating temperature
FDO221
FDO241
Storage temperature
Air humidity
Protection categories according to EN 60529 /
IEC 60529:
Base FDB221/FDB221-AA/FDB222, base
attachment FDB291
Base FDB221 and sealing element
FDBZ295
Sounder base FDSB291
Base attachment wet FDB295
Electromagnetic compatibility:
1 MHz...2 GHz
Permissible wind speed
Color
European standards
Typ. 2...3.5 %/m (depending on the
parameter set)
Typ. 1.4...3.5 %/m (depending on the
parameter set)
≤1 voltage increase for detection
≤1.5 voltage increases for detection
≤1/45 voltage increase for detection/h
With detector exchanger and tester
FDUD292 or intelligent detector tester
FDUD293
-10...+60 °C
-25...+70 °C
-30...+75 °C
≤95 % rel.
IP43
IP44
IP43
IP44
50 V/m
Max. 5 m/s
∼RAL 9010 pure white
EN 54-7
EN 54-17
007004_t_en_--
2015-11-04

Hide quick links:

Advertisement

Table of Contents
loading