Siemens FDOOT221 Technical Manual page 127

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

Detector line
Line separator
External alarm indicators
Building Technologies
Fire Safety
Interactive detector line (FDOOT241-A5)
Operating voltage (modulated)
Operating current (quiescent)
Maximum current connection factor
Address connection factor
Separator connector factor
Protocol
Compatibility
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the line separator opens:
Minimum
Maximum
Permanent current when switches are closed
Switching current (e.g., in the event of a short-
circuit)
Leakage current when switches are open
Serial impedance when switches are closed
Voltage at which the line separator closes
Minimum
Maximum
External alarm indicators which can be
connected
Voltage
Current
Flashing interval times:
Bright
Dark
54BTechnical data FDOOT221, FDOOT241-x / -Ax
DC 21...33 V
Typ. 220 µA
1
1
1
K1151 (interactive)
See 'List of compatibility'
DC 32 V (= V
nom
DC 21.2 V (= V
DC 33 V (= V
max
DC 14.9 V (= V
DC 11.2 V (= V
Max. 0.11 A (= I
Max. 0.20 A (= I
Max. 1 mA (= I
Max. 0.55 Ω (= Z
DC 15.5 V (= V
DC 19.5 V (= V
2
DC 10...17 V
9...15 mA
20 ms
1.5 s (typical)
7BSpecifications
)
)
min
)
)
SO min
)
SO max
)
C max
)
S max
)
L max
)
C max
)
SC min
)
SC max
127 | 138