49BDetector lines
5.19.2.1 Use of unshielded cables
102 | 138
Building Technologies
Fire Safety
The connection is established from base to base using twisted or non-twisted wire
pairs.
-
-
-
+
+
+
+
1
-
A
Connection diagram for collective detector line with and without external alarm indicators (without
shielded cables)
1 Control panel
2 Detector bases FDB201/FDB201-AA, FDB202
Standard circuitry
With standard circuitry, the external alarm indicator is connected to the positive and
negative poles of each detector.
Wire-saving cabling
NOTICE
No approval
Wire-saving cabling in external alarm indicators is prohibited for new sites
●
The base adapter FDB299 must be used for the FDOOT241-A9.
With wire-saving cabling, the external alarm indicator is connected as follows:
●
The external alarm indicator must be connected to the positive and negative
poles of at least one detector (A).
●
The external alarm indicator must be connected to the positive pole of every
other detector (B).
●
The external alarm indicator need not be connected to the negative pole of
every other detector (C).
2
-
-
+
+
+
LINE
B
3
3 External alarm indicator
4 End-of-line depending on control panel
-
-
+
+
4
007004_t_en_--
2015-11-04
-
-
+