Table of Contents

Advertisement

4BMounting / Installation
5
49BDetector lines

5.19.2.1 Use of unshielded cables

102 | 138
Building Technologies
Fire Safety
The connection is established from base to base using twisted or non-twisted wire
pairs.
-
-
-
+
+
+
+
1
-
A
Connection diagram for collective detector line with and without external alarm indicators (without
shielded cables)
1 Control panel
2 Detector bases FDB201/FDB201-AA, FDB202
Standard circuitry
With standard circuitry, the external alarm indicator is connected to the positive and
negative poles of each detector.
Wire-saving cabling
NOTICE
No approval
Wire-saving cabling in external alarm indicators is prohibited for new sites
The base adapter FDB299 must be used for the FDOOT241-A9.
With wire-saving cabling, the external alarm indicator is connected as follows:
The external alarm indicator must be connected to the positive and negative
poles of at least one detector (A).
The external alarm indicator must be connected to the positive pole of every
other detector (B).
The external alarm indicator need not be connected to the negative pole of
every other detector (C).
2
-
-
+
+
+
LINE
B
3
3 External alarm indicator
4 End-of-line depending on control panel
-
-
+
+
4
007004_t_en_--
2015-11-04
-
-
+
C