5.19.5.3 Connecting external alarm indicators

5.19.6 Connection diagram for interactive detector line

110 | 138
Building Technologies
Fire Safety
The points below apply to connecting external alarm indicators:
If the external alarm indicator is connected to only one individual detector, there
is no limitation.
If only original SIGMALOOP detectors and FDOOT241-A4 with base adapter
FDB241 are used, there is no limitation.
If several FDOOT241-A4 are merged with Sinteso detector base FDB22x on an
external alarm indicator, the external alarm indicator FDAI9x must be used.
-
-
-
+
+
+
+
1
-
+
3
Connecting external alarm indicators
1 Control panel
2 Sinteso detector base FDB22x
The existing cabling can be transferred for interactive detectors.
The multiple protocol detector must be installed in the detector base DB1151A
using a base adapter FDB251.
Connecting an external alarm indicator to the base adapter FDB251 is not
permitted according to EN 54.
2
-
-
+
+
LINE
-
+
FDAI9x
3 External alarm indicator
-
-
+
+
-
007004_t_en_--
-
-
+
+
2015-11-04