Siemens FDOOT221 Technical Manual page 123

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

Use as
Parameter set
No.
Neural fire
2
detector
4
(FDOOT)
5
6
7
0 (ES ≥13) High Compensation
0 (ES <13) Insensitive
8
9
Wide-
0
spectrum
1
smoke
detector
2
(FDO)
3
Heat detector
0...4
(FDT)
Building Technologies
Fire Safety
Collective maximum current connection factor/alarm verification
(FDOOT241-9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Maximum
current
Designation
connection
factor for
ES < 30
Robust
2
Balanced
Suppression
Fast Response
2
High Compensation
2
1.5
High Suppression
High Sensitive Fast
Universal
2
Universal
Robust
Sensitive
2
All parameter sets
2
For CS1115, the maximum current connection factor values in the column apply for ES <30.
1
Different connection factors due to the different measuring cycles.
2
54BTechnical data FDOOT221, FDOOT241-x / -Ax
Maximum
Alarm verification
current
on control panel
connection
permitted with
factor for
detector ES < 13
ES ≥ 30
(verification time at
1
the control panel
≥50 s)
1.5
No
1.5
Yes
1.5
No
2
1.25
2
No
1.5
1.5
1.5
No
1.5
Yes
1.5
No
7BSpecifications
8
Alarm verification on control
panel permitted with detector
ES ≥ 13 (verification time at the
control panel ≥ 30 s)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
123 | 138
007004_t_en_--
2015-11-04