Basler VR63-4A/UL Instruction Manual

Basler VR63-4A/UL Instruction Manual

Voltage regulator

Advertisement

Quick Links

BASLER ELECTRIC,
INTRODUCTION
The VR63-4A/UL Voltage Regulators are
designed for use on 50/60 Hz brushless
generators. The regulator includes frequency
compensation, overexcitation shutdown, a
solid-state build-up circuit, and EMI filtering.
WARNING
To prevent personal injury or equipment
damage, only qualified
technicians or
operators should install, operate, or
service this device.
ELECTRICAL SPECIFICATIONS
Dc Output Power:
4
Adc
at
63
Vdc
(252W)
continuous,
7 Adc at 100 Vdc (700W) forcing one minute
(at 240 Vac input).
Exciter Field Dc Resistance:
15 ohms minimum; 100 ohms maximum.
Ac Power Input:
Operating range: 190 Vac to 240 Vac ±10%
Single phase, 50/60 Hz, Burden 500 VA.
Sensing Input:
100-120 Vac, Single phase, 50/60 Hz ±10%,
1 VA burden.
Voltage Adjust Range:
90-132 Vac.
Regulation Accuracy:
Better than ±1.0% no load to full load.
Response Time:
Less than 1.5 cycles for ±5% change in
sensing voltage.
EMI Suppression:
Internal electromagnetic interference filter
(EMI filter).
Overexcitation Shutdown:
Output power is removed under the following
conditions: Exciter field voltage exceeds 100
±5 Vdc for a time inversely proportional to
voltage magnitude, or within 0.2 seconds if the
exciter field voltage exceeds 135 ±5 Vdc.
Voltage Build-up:
Internal provisions for automatic voltage build-
up from generator residual voltages as low as
10 Vac.
Power Dissipation:
8 Watts maximum.
PHYSICAL SPECIFICATIONS
Operating Temperature:
-40° C (-40° F) to +60° C (+140° F).
Storage Temperature:
-65° C (-85° F) to +85° C (+185° F).
Vibration:
Withstands 1.3 Gs at 2 to 26 Hz; 0.036"
double amplitude at 26 to 50 Hz; and 5 Gs at
50 to 500 Hz.
INSTRUCTION MANUAL
VOLTAGE REGULATOR
Model: VR63-4A/UL
BOX 269,
Shock:
Withstands up to 15 Gs in each of three
mutually perpendicular axes.
Weight:
14 oz. (0.40 kg) Net.
CSA Approved/UL Recognized
FUSES
It is recommended that fuses with high
interruption capability be installed per the
interconnection diagram to protect wiring from
faults before the regulator. Install 5 A, 250 V
fuses with a high interruption capability in the
lines 3 and 4. Refer to the Interconnection
Diagrams.
maximum
Fuse
interconnection diagrams to avoid inter-
rupting the field current.
MOUNTING
The regulator may be mounted in any
position. Refer to the Drilling Diagram.
EXCITER FIELD POWER CIRCUIT (wires F+
and F-).
Connect the regulator wire F+ to the brushless
exciter field terminal F+, and wire F- to
terminal F-.
The dc resistance of the exciter field
must be equal to or greater than 15 ohms
and less than 100 ohms.
FOR
HIGHLAND, IL 62249
NOTE
must
be
installed
per
Drilling Diagram
CAUTION
PHONE 618/654-2341
POWER/SENSING INPUT CIRCUIT (wires 3
and 4)
Connect as shown by the Interconnection
Diagrams.
the
FAX 618/654-2351

Advertisement

loading

Summary of Contents for Basler VR63-4A/UL

  • Page 1 Shock: INTRODUCTION POWER/SENSING INPUT CIRCUIT (wires 3 Withstands up to 15 Gs in each of three and 4) The VR63-4A/UL Voltage Regulators are mutually perpendicular axes. designed for use on 50/60 Hz brushless Connect as shown by the Interconnection Weight: generators.
  • Page 2 9 1668 00 995 IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE © 1998, Basler Electric Co., Highland, IL 62249 MUTUAL UNDERSTANDING THAT IT WILL NOT BE First Printing November 1986 USED IN ANY MANNER DETRIMENTAL TO THE...
  • Page 3 Interconnection Diagram, 208/240 V Nominal Operational Test Interconnection Diagram, 120V Generator with Auxiliary Winding...