INSTRUCTION MANUAL
FOR
DGC-2020HD
DIGITAL GENSET CONTROLLER
Operation
Publication: 9469300996
Revision: C2
Apr-19

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DGC-2020HD and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Basler DGC-2020HD

  • Page 1 INSTRUCTION MANUAL DGC-2020HD DIGITAL GENSET CONTROLLER Operation Publication: 9469300996 Revision: C2 Apr-19...
  • Page 2 Proposición 65, estamos notificándole que uno o más productos químicos allí listados pueden estar presentes en los productos que le vendemos. Para obtener más información sobre los productos químicos específicos que este producto contiene, visite https://es.basler.com/Proposición-65. 警告: 加州第65号提案要求对可能含有加州已知的致癌的、导致先天缺陷或其他生殖伤害的化学物质的产品发出...
  • Page 3: Conventions Used In This Manual

    9469300996 Rev C Preface This instruction manual provides information about the operation of the DGC-2020HD Digital Genset Controller. To accomplish this, the following information is provided: • Controls and indicators • Operating modes • Metering • Alarms • Troubleshooting Conventions Used in this Manual Important safety and procedural information is emphasized and presented in this manual through Warning, Caution, and Note boxes.
  • Page 4 The availability and design of all features and options are subject to modification without notice. Over time, improvements and revisions may be made to this publication. Before performing any of the following procedures, contact Basler Electric for the latest revision of this manual.
  • Page 5 For a complete copy of GNU GENERAL PUBLIC LICENSE Version 2, June 1991 or GNU LESSER GENERAL PUBLIC LICENSE Version 2.1, February 1999 refer to www.gnu.org or contact Basler Electric. You, as a Basler Electric Company customer, agree to abide by the terms and conditions of GNU GENERAL PUBLIC LICENSE Version 2, June 1991 or GNU LESSER GENERAL PUBLIC LICENSE Version 2.1, February 1999, and as such...
  • Page 6 9469300996 Rev C Preface DGC-2020HD...
  • Page 7: Table Of Contents

    Diagnostics .............................. 65 Analysis ..............................67 Reporting and Alarms ..........................71 Event Logging ............................71 Sequence of Events ..........................71 Data Logging ............................73 Trending ..............................74 Differential Reporting ..........................75 Annunciation ............................76 Retrieving and Resetting Alarms ......................77 DGC-2020HD Contents...
  • Page 8 Synchronizer ............................167 Speed Bias ............................168 Load Anticipation ........................... 168 Voltage Bias ............................170 Load Sharing ............................171 Group Start and Group Stop Requests ....................173 DGC-2020HD Front Panel Diagnostics Screens .................. 174 Revision History ............................181 Contents DGC-2020HD...
  • Page 9: Controls And Indicators

    9469300996 Rev C Controls and Indicators DGC-2020HD controls and indicators are located on the front panel and are intended for local control and monitoring of DGC-2020HD operation. Front-panel controls consist of sealed membrane pushbuttons and an optional touch screen. Front-panel indicators consist of LED indicators and a backlit LCD (liquid crystal display).
  • Page 10: Power Indicator

    Off Pushbutton and Mode Indicator. Pressing this button places the DGC-2020HD in Off mode. The red Off mode LED lights when the DGC-2020HD is in Off mode. This button also resets the Breaker Management Pre-Alarms and all MTU ECU Alarms.
  • Page 11: Programmable Indicator Configuration

    Grasp the tab of the label card and pull free. The label card tab is located on the rear of the DGC-2020HD, see Figure 3. When facing the back of the panel, the label card tab is on the left.
  • Page 12: Touch Screen Operation

    However, critical settings must be initiated using the pushbuttons to prevent accidental operation with the touch screen. Touch screen controls are illustrated in Figure 4. Lettered locators in Figure 4 correspond to the control descriptions of Table 2. Controls and Indicators DGC-2020HD...
  • Page 13 Edit pushbutton to accept the change. Up and Down Arrows. Touching the Up arrow scrolls the menu options toward the top of the list and touching the Down arrow scrolls the menu options toward the bottom of the list. DGC-2020HD Controls and Indicators...
  • Page 14: Display Operation And Navigation

    Login and Permissions When attempting to change a protected setting, the DGC-2020HD displays the Login Required screen. To log in, use the arrow keys to navigate the on-screen keyboard. Press the Edit key to select each character.
  • Page 15 On the optional touch screen, a dead bus is indicated by a green colored line segment and an energized (failed or stable) is indicated by a red colored line segment. See Figure 6 for the different breaker and bus states. DGC-2020HD Controls and Indicators...
  • Page 16 System Type setting selection. For details on configuring the system type, see the Device Configuration chapter in the Configuration manual. If no pushbutton activity is detected for 15 minutes, the DGC-2020HD displays the top overview screen. Reset Key Functions Pressing the Reset key while viewing the Overview screen will reset certain active indications.
  • Page 17 Temperature Detectors (RTD): AEM1 RTD2 AEM1 TC2 Analog Expansion Module 1: Resistance Analog Expansion Module 2: Inputs: AEM2 In1 Temperature Detectors (RTD): AEM1 RTD3 Analog Expansion Module 2: Inputs: AEM2 In2 Analog Expansion Module 2: Inputs: AEM2 In3 DGC-2020HD Controls and Indicators...
  • Page 18 Temperature Detectors (RTD): AEM3 RTD8 Bus 1 Failed Analog Expansion Module 3: Thermocouples: Bus 1 Forward Rotation AEM3 TC1 Bus 1 Frequency: Frequency Analog Expansion Module 3: Thermocouples: Bus 1 Frequency: Max ROCOF AEM3 TC2 Bus 1 Frequency: ROCOF Controls and Indicators DGC-2020HD...
  • Page 19 Bus 2 Frequency: Max ROCOF Contact Expansion Module 2: CEM2 Input 3 Bus 2 Frequency: ROCOF Contact Expansion Module 2: CEM2 Input 4 Contact Expansion Module 2: CEM2 Input 5 Bus 2 Power: Max Vector Shift DGC-2020HD Controls and Indicators...
  • Page 20 Gen Dead Contact Outputs: Output 5 Gen Failed Gen Forward Rotation Contact Outputs: Output 6 Contact Outputs: Output 7 Gen Frequency: Frequency Contact Outputs: Output 8 Gen Frequency: Max ROCOF Gen Frequency: ROCOF Contact Outputs: Output 9 Controls and Indicators DGC-2020HD...
  • Page 21 Load Percent System Online kW Capacity kW PID System Total kW Capacity Total Fuel Used kW Ramp Status Load Share Active Total Run Time Logic Control Relays: LCR 1-64 Var Demand Var Mode LS Input DGC-2020HD Controls and Indicators...
  • Page 22 Menu screen options consist of Metering, Settings, and Summary. Metering screens primarily display specific metering information. Settings screens primarily contain settings for configuring the DGC-2020HD. The Summary screen consists of a one-line diagram of the system configuration, mains fail transfer status, bus metering, and breaker command options.
  • Page 23 Logic Control Relays Remote System Manager Inputs Broadcast Logic Modbus Virtual Switches • Outputs Contact Outputs Analog Outputs Configurable Elements Remote Contact Outputs Remote Analog Outputs • Configurable Protection Configurable Protection 1 to Configurable Protection 32 DGC-2020HD Controls and Indicators...
  • Page 24 Unit ID Active Seg ID Sys Manager Sys Man UID Start TD 1 Start TD 2 Stop TD • Load Shedding Sys Total Seq Reserve Sys Online Reserve Priority to Shed Shed Delay Shed Fast Delay Controls and Indicators DGC-2020HD...
  • Page 25 Exercise Timer Relay Control Auto Config Detect Engine Statistics Seven Day Timer • Report Configuration Data Log Trending Sequence of Events Setup Configurable Log Params • Programmable Inputs Contact Inputs Analog Inputs Programmable Functions Remote Contact Inputs DGC-2020HD Controls and Indicators...
  • Page 26 LS (Load Share) Output Demand Start/Stop Sequencing Network Configuration Load Shedding • Logic Logic Timers (1-8) Logic Timers (9-16) Logic Timers (17-14) Logic Timers (25-32) Logic Counters Logic Input Counters Broadcast Logic Summary • System Configuration One-Line Diagram Controls and Indicators DGC-2020HD...
  • Page 27 MB Command (Visible when Mains Breaker control is enabled.) Open, Close, or None • TB Command (Visible when Tie Breaker control is enabled.) Open, Close, or None • TB2 Command (Visible when Tie Breaker 2 control is enabled.) Open, Close, or None DGC-2020HD Controls and Indicators...
  • Page 28 9469300996 Rev C Controls and Indicators DGC-2020HD...
  • Page 29: Operating Modes

    In Off mode, the DGC-2020HD will not start under any circumstance. It cannot be started automatically. Programmable logic functions normally in this mode. In Run (manual) mode, the DGC-2020HD runs and cannot be shut off automatically. The breaker can be opened or closed through programmable logic inputs. Programmable logic functions normally in this mode.
  • Page 30 Peak Shave Local Start Request Once the power imported from mains reaches a predetermined level, and the start mode is Single Generator, the local generator is automatically started to pick up the load. The local generator is the Operating Modes DGC-2020HD...
  • Page 31: Operating States

    Ready The engine is not running. The DGC-2020HD is ready to run. This is the normal state of the DGC-2020HD in OFF mode, and in AUTO mode when the engine is not running, or in the process of starting or stopping.
  • Page 32: Operating Mode Control

    Refer to the Controls and Indicators chapter for more information. Tie Breaker Configuration When the DGC-2020HD is configured as a tie breaker controller it does not control a genset. Thus, the standard operating modes described above do not apply. Special operating modes for tie breaker controllers are described below.
  • Page 33: Metering

    The DGC-2020HD provides comprehensive metering of internal and system conditions. These capabilities include extensive parameter metering, status indication, and reporting. Metering Explorer DGC-2020HD metering is accessed through the metering explorer menu on the front panel display or the BESTCOMSPlus ®...
  • Page 34: Engine

    The Engine metering screen (Figure 8) provides information and metering of engine components. Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter in the Configuration manual for their descriptions. Metering DGC-2020HD...
  • Page 35: Battery Charger 1 And 2

    Figure 8. Metering Explorer, Engine Screen Battery Charger 1 and 2 BESTCOMSPlus Navigation Path: Metering Explorer, Battery Charger Front Panel Navigation Path: Metering > Battery Charger Metering, status, and active pre-alarms of the battery charger(s) are displayed on this screen. See Figure DGC-2020HD Metering...
  • Page 36: Generator

    Figure 9. Metering Explorer, Battery Charger Screen Generator BESTCOMSPlus Navigation Path: Metering Explorer, Generator Front Panel Navigation Path: Metering > Gen Metering of the voltage, current, angle, frequency, and vector shift of the generator is displayed on this screen. See Figure 10. Metering DGC-2020HD...
  • Page 37: Bus 1 And Optional Bus 2

    Front Panel Navigation Path: Metering > Bus 1 or Bus 2 Metering of the voltage, current, angle, frequency, and vector shift of Bus 1 and optional Bus 2 is displayed on these screens. See Figure 11. Figure 11. Metering Explorer, Bus 1 and Bus 2 (Optional) Screens DGC-2020HD Metering...
  • Page 38: Power

    This screen (Figure 13) provides metering of total positive and negative watthours, total positive and negative var hours, and total VA hours for the generator, bus 1, and optional bus 2. The Edit button provides options to upload total watthour and total var hour values to the DGC-2020HD. Metering...
  • Page 39: Synchronization

    Synchronization screen (Figure 14) in BESTCOMSPlus. Figure 14. Metering Explorer, Synchronization Screen The Synchronization screen is automatically displayed on the front panel while the synchronizer is active. See Figure 15. Figure 15. Front Panel Synchronization Screen DGC-2020HD Metering...
  • Page 40: Differential

    Figure 16. Metering Explorer, Differential Screen Active Setpoints BESTCOMSPlus Navigation Path: Metering Explorer, Active Setpoints Front Panel Navigation Path: Metering > Active Setpoints Active setpoints, active control mode, and active baseload levels are displayed on this screen. See Figure 17. Metering DGC-2020HD...
  • Page 41: Run Statistics

    Loaded Run Time, and Unloaded Run time can be changed by clicking the Edit Cumulative Run Statistics button. This is helpful when installing the DGC-2020HD into a pre-existing system. This allows the current statistics of the genset to be transferred into the DGC-2020HD for uninterrupted tracking.
  • Page 42: Status Indication

    This screen indicates status of breakers, modes, switches, and I/O connection status. The status is TRUE when the corresponding indicator is lit. See Figure 19 and Figure 20. Status indications differ depending on system configuration. Figure 19. Metering Explorer, Status Screen (Generator and Group Breaker Control) Metering DGC-2020HD...
  • Page 43: Inputs

    9469300996 Rev C Figure 20. Metering Explorer, Status Screen (Generator and Tie Breaker Control) Inputs Contact Inputs BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Contact Inputs Front Panel Navigation Path: Metering > Status > Inputs > Contact Inputs DGC-2020HD Metering...
  • Page 44: Analog Inputs

    Front Panel Navigation Path: Metering > Status > Inputs > Remote Contact Inputs > CEM-2020 # There are four remote contact input screens, one for each possible CEM-2020 (Contact Expansion Module). When CEM-2020s are connected, the status of the remote contact inputs, configurable remote Metering DGC-2020HD...
  • Page 45 BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Remote Analog Inputs, AEM # Inputs, AEM # RTD Inputs Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > AEM-2020 # > RTD Input Temperatures / Raw RTD Inputs Figure 25 illustrates the BESTCOMSPlus RTD Inputs screen. DGC-2020HD Metering...
  • Page 46 BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Remote Analog Inputs, AEM # Inputs, AEM # Input Values Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > AEM-2020 # Figure 27 illustrates the BESTCOMSPlus Input Values screen. Metering DGC-2020HD...
  • Page 47 BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Voltage Regulation Module, VRM RTD Inputs Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > VRM > RTD Input Temperatures / Raw RTD Inputs Figure 28 illustrates the BESTCOMSPlus VRM RTD Inputs screen. DGC-2020HD Metering...
  • Page 48 Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > VRM > RTD Input Temperatures / Raw RTD Inputs Figure 29 illustrates the BESTCOMSPlus VRM RTD Input Values screen and Figure 30 illustrates the VRM-2020 RTD calibration screen. Figure 29. Metering Explorer, Inputs, Voltage Regulation Module, VRM RTD Input Values Metering DGC-2020HD...
  • Page 49 Front Panel Navigation Path: Metering > Status > Logic Control Relays This screen displays the status of the 64 logic control relays. A logic control relay input is true when the corresponding indicator is lit. See Figure 31. Figure 31. Metering Explorer, Inputs, Logic Control Relays Screen DGC-2020HD Metering...
  • Page 50: Remote System Manager Inputs

    Figure 33. Metering Explorer, Inputs, Broadcast Logic Screen Modbus Switches BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Modbus Switches Front Panel Navigation Path: Metering > Inputs > Modbus Switches The status of each Modbus switch is displayed on this screen (Figure 34). Metering DGC-2020HD...
  • Page 51: Outputs

    Front Panel Navigation Path: Metering > Status > Outputs > Contact Outputs This screen indicates the status of the twelve contact outputs and the Start, Run, and Pre-start outputs. The status is TRUE when the corresponding indicator is lit. See Figure 35. DGC-2020HD Metering...
  • Page 52: Analog Outputs

    BESTCOMSPlus Navigation Path: Metering Explorer, Outputs, Configurable Elements Front Panel Navigation Path: Metering > Status > Configurable Elements This screen indicates the status of the eight configurable elements. The status is true when the corresponding indicator is lit. See Figure 37. Metering DGC-2020HD...
  • Page 53 Front Panel Navigation Path: Metering > Status > Outputs > Remote Analog Outputs > AEM -2020 # There are four remote analog output screens, one for each possible AEM-2020 (Analog Expansion Module). Each of these screens displays the scaled and raw values of the four remote analog outputs of DGC-2020HD Metering...
  • Page 54: Configurable Protection

    This screen (Figure 41) displays active alarms, pre-alarms, and global soft alarms. Alarms, pre-alarms, and global soft alarms are reset when the DGC-2020HD is set to Off mode. Certain pre-alarms pertaining to system breakers can be reset by pressing the Reset key on the front panel. See the Reporting and Alarms chapter for details.
  • Page 55: J1939 Ecu

    The ECU Data metering screen (Figure 43) provides information and metering of engine components. Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter for their descriptions. DGC-2020HD Metering...
  • Page 56 The Isuzu Status metering screen (Figure 44) provides Isuzu engine parameters that may be useful for exhaust system troubleshooting. Figure 44. Metering Explorer, J1939 ECU, Isuzu Status Engine Configuration BESTCOMSPlus Navigation Path: Metering Explorer, J1939 ECU, Engine Configuration Front Panel Navigation Path: Metering > J1939 ECU > J1939 Engine Config Metering DGC-2020HD...
  • Page 57: Mtu

    Front Panel Navigation Path: Metering > MTU > MTU Alarms On the MTU Alarms screen (Figure 46), MTU fault codes are displayed in a scrolling window. MTU alarms and MTU pre-alarms are also reported on this screen. The status is true when the corresponding LED is red. DGC-2020HD Metering...
  • Page 58 Information and metering of engine components is provided by the MTU Status metering screen. Refer to Figure 48. Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter in the Configuration manual for their descriptions. Metering DGC-2020HD...
  • Page 59 Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter in the Configuration manual for their descriptions. Figure 49. Metering Explorer, MTU, MTU Engine Status Screen DGC-2020HD Metering...
  • Page 60: Summary

    BESTCOMSPlus Navigation Path: Metering Explorer, Summary Front Panel Navigation Path: Summary Pertinent bus and engine metering is displayed on the Summary screen (Figure 50) in BESTCOMSPlus. Figure 50. Metering Explorer, Summary Screen The front panel Summary screen is shown in Figure 51. Metering DGC-2020HD...
  • Page 61: Detailed Summary

    Figure 51. Front Panel Summary Screen Detailed Summary BESTCOMSPlus Navigation Path: Metering Explorer, Detailed Summary Front Panel Navigation Path: Not available through the front panel Comprehensive bus and engine metering is displayed on the Detailed Summary screen (Figure 52). DGC-2020HD Metering...
  • Page 62: System Status

    The bus view displays the different bus segments in the system. This dynamically changes as breakers are opened and closed. Each of these views is only available if the view is valid for the current system configuration. Metering DGC-2020HD...
  • Page 63 Every generator in the system has a separate line entry in the table, including units which are not on the local generator’s active segment. Units of measure are stated in the table header, rather than after the actual value. See Figure 55. Figure 55. Metering Explorer, System Status, Generator Screen DGC-2020HD Metering...
  • Page 64 System Mains Bus BESTCOMSPlus Navigation Path: Metering Explorer, System Status, System Mains Bus Front Panel Navigation Path: Metering > System Status > System Mains Bus The System Mains Bus screen (Figure 58) provides an overall mains bus summary. Metering DGC-2020HD...
  • Page 65 BESTCOMSPlus Navigation Path: Metering Explorer, System Status, System Load Bus Front Panel Navigation Path: Metering > System Status > System Load Bus The System Load Bus screen (Figure 60) provides an overall load bus summary. Figure 60. Metering Explorer, System Status, System Load Bus Screen DGC-2020HD Metering...
  • Page 66: Control Panel

    DGC-2020HD. The PC or laptop running BESTCOMSPlus must be connected to the DGC-2020HD via the USB, Ethernet, or Modem (see the Communication chapter for details). Using the Metering Explorer in BESTCOMSPlus, open the Control Panel screen.
  • Page 67 Front Panel Navigation Path: Not available through front panel The Control Panel VRM (Figure 63) provides options for changing operating modes, selecting setpoint pre-positions, and fine tuning setpoints. The setpoints for AVR and FCR are displayed, as well as function status. DGC-2020HD Metering...
  • Page 68 Soft Start: The Soft Start indicator changes from gray to green during startup when the soft start function is active. • Null Balance: The Null Balance indicator changes from gray to green when the setpoint of the inactive operating mode (AVR or FCR) matches the setpoint of the active mode. Metering DGC-2020HD...
  • Page 69: Generator Network Status

    Front Panel Navigation Path: Metering > Gen Network Status The Generator Network Status metering screen is illustrated in Figure 64. The status of the generator network is available from each DGC-2020HD when the generator is part of a multi-machine network. The System Type setting (found under the BESTCOMSPlus ®...
  • Page 70: Generator Sequencing

    • System Total kW Capacity indicates the sum of rated power of all generators in the network. The Number of Units parameter displays zero when the DGC-2020HD is not communicating with other DGC-2020HDs on the network. All of these parameters except for Active Segment ID are available to the Configurable Protection function and may be useful for implementing load sharing schemes.
  • Page 71: Mains Fail Transfer Status

    Transferring to Mains: Load is being transferred to the mains bus. • Disabled: DGC-2020HD is in the Off or Run operating mode or in the alarm state. Transfer Delay, Return Delay, Max Parallel Time, Max Transfer Time, Open Transition Delay, and Return Timer indicate the amount of time remaining in the delay or timer.
  • Page 72: Load Shedding

    Figure 66. Metering Explorer, Mains Fail Transfer Status Load Shedding BESTCOMSPlus Navigation Path: Metering Explorer, Load Shedding Front Panel Navigation Path: Metering > Load Shedding The Load Shedding screen (Figure 67) displays reserve power, priority to shed/add, delay timers, and enabled priority loads. Metering DGC-2020HD...
  • Page 73: Diagnostics

    Diagnostics screens provide metering for kW and var control, load share, and mains power parameters. Control BESTCOMSPlus Navigation Path: Metering Explorer, Diagnostics, Control Front Panel Navigation Path: Metering > Diagnostics > Control Figure 68 illustrates the BESTCOMSPlus Control screen. DGC-2020HD Metering...
  • Page 74: Mains Power

    Figure 69. Metering Explorer, Diagnostics, Load Share Screen Mains Power BESTCOMSPlus Navigation Path: Metering Explorer, Diagnostics, Mains Power Front Panel Navigation Path: Metering > Diagnostics > Mains Power Figure 70 illustrates the BESTCOMSPlus Mains Power screen. Figure 70. Metering Explorer, Diagnostics, Mains Power Metering DGC-2020HD...
  • Page 75: Analysis

    Figure 71. Metering Explorer, Diagnostics, VRM Control Analysis BESTCOMSPlus Navigation Path: Metering Explorer, Analysis Front Panel Navigation Path: Not available through the front panel Oscillography of nearly all genset parameters can be monitored in real time using the Analysis screen (Figure 72). DGC-2020HD Metering...
  • Page 76 (up to six). For example, to monitor Analog Input 1 in the top graph, enable the radio button where the Analog Input 1 row intersects the Parameter 1 column. Metering DGC-2020HD...
  • Page 77 9469300996 Rev C Figure 73. Metering Explorer, Analysis, Analysis Configuration Screen DGC-2020HD Metering...
  • Page 78 9469300996 Rev C Metering DGC-2020HD...
  • Page 79: Reporting And Alarms

    Windows clipboard, or to print the event log. Clicking the Refresh button performs a fresh download of the list from the DGC-2020HD. The Clear button provides the option of clearing selected or all event logs. Refer to Figure 74.
  • Page 80 Clicking the Refresh button performs a fresh download of the list from the DGC-2020HD. The Clear button provides the option of clearing selected or all event logs. Refer to Figure Figure 75. Metering Explorer, Reports, Sequence of Events Setup ®...
  • Page 81: Data Logging

    Navigation Path: Settings Explorer, Report Configuration, Data Log Setup Front Panel Navigation Path: Settings > Report Configuration > Datalog The data logging function of the DGC-2020HD can record up to 6 oscillography records. DGC-2020HD oscillography records use the IEEE Standard Common Format for Transient Data Exchange (COMTRADE).
  • Page 82: Trending

    Front Panel Navigation Path: Settings > Report Configuration > Trending The trend log records the activity of DGC-2020HD parameters over an extended period of time. When enabled, up to six selectable parameters can be monitored over a user-defined duration ranging from 1 to 720 hours.
  • Page 83: Differential Reporting

    (87G) status and creates a differential report. Only one report is stored in nonvolatile memory. When a new report is generated, the DGC-2020HD discards the old report and replaces it with the new one.
  • Page 84: Annunciation

    An alarm configuration setting determines the type of annunciation that is used. The annunciation types are described in the following paragraphs. Alarm When an alarm condition exists, the following actions are taken by the DGC-2020HD: • Stop the engine by opening the fuel contact output.
  • Page 85: Retrieving And Resetting Alarms

    Status of each active alarm and pre-alarm is displayed on the Alarms screen (Figure 80). This screen is found in the Metering Explorer. Active pre-alarms are listed in the upper panel, alarms are listed in the lower panel. DGC-2020HD Reporting and Alarms...
  • Page 86 10 seconds while the Overview screen is displayed. To reset the maintenance interval pre-alarm by using BESTCOMSPlus, use the Metering Explorer to open the Run Statistics screen and click on the Reset Maintenance Interval button. Reporting and Alarms DGC-2020HD...
  • Page 87: Mtu Fault Codes

    Metering > MTU > MTU Fault Codes. Each fault code is displayed with a fault description and the fault number. If the DGC-2020HD does not have descriptive information about a fault number that was received, the fault description will display as “NO TEXT AVAILABLE”.
  • Page 88 ERR REC2 INVALID Checksum fault. LO ECU SUPPLY VOLTS Power supply voltage too low (limit 1). LOLO ECU SUPPLY VOLTS Power supply voltage too low (limit 2). HI ECU SUPPLY VOLTS Power supply voltage too high (limit 1). MTU Fault Codes DGC-2020HD...
  • Page 89 SD T EXHAUST A Exhaust gas temperature-sensor on A-side defect. SD T EXHAUST B Exhaust gas temperature-sensor on B-side defect. SD P CHARGE AIR Charge air pressure-sensor defect. SD P LUBE OIL Lube oil pressure-sensor defect. DGC-2020HD MTU Fault Codes...
  • Page 90 SD SPD DEMAND AN Analog speed demand defect. SD SPDMTEST BNCH Short circuit, cable breakage. SD SPINUT Analog spinning value defect. SD LOAD ANLG FLT Filtered analog load pulse signal not available. SD FREQUENCY INPUT Frequency input defect. MTU Fault Codes DGC-2020HD...
  • Page 91 Short circuit in injector cable of cylinder A6. WIRING CYLNDR A7 Short circuit in injector cable of cylinder A7. WIRING CYLNDR A8 Short circuit in injector cable of cylinder A8. WIRING CYLNDR A9 Short circuit in injector cable of cylinder A9. DGC-2020HD MTU Fault Codes...
  • Page 92 Short circuit or open load on transistor output plant 5 (TOP 5). AL WIRING TOP 6 Short circuit or open load on transistor output plant 6 (TOP 6). AL MCR EXCEEDED DBR/MCR Function: MCR (Maximum Continuous Rating) in exceeded. MTU Fault Codes DGC-2020HD...
  • Page 93 High Pre-Engine Coolant Temperature (Limit 2). AL L1 P AUX 2 Auxiliary Pressure 2 Level 1 Alarm. AL L2 P AUX 2 Auxiliary Pressure 2 Level 2 Alarm. LO P FUEL RAIL 2 STR Low pressure on fuel rail 2. DGC-2020HD MTU Fault Codes...
  • Page 94 Sensor Defect In Exhaust System C Temperature Sensor. SD T EXHAUST D Sensor Defect In Exhaust System D Temperature Sensor. HI T EXHAUST C High Exhaust C Temperature (Limit 1). SS T EXHAUST C High Exhaust C Temperature (Limit 2). MTU Fault Codes DGC-2020HD...
  • Page 95 Sensor Defect In Oil Coolant Temperature (R2) Sensor. TD ENG SPD SNS DEV Engine Speed Sensor Deviation. SD ENG SPD SENSR 3 Sensor Defect in Engine Speed Third Sensor. SS T COOL RED 2 Coolant Temperature Red 2 Alarm (Limit 2). DGC-2020HD MTU Fault Codes...
  • Page 96 Intake B Air Pressure After Filter (Limit 2). AL SAM MSG DATA FLT SAM Module Missing Data Fault. L1 CAN MAX TIMG RETRD Maximum Timing Retard from CAN (Limit 1). L2 CAN MAX TIMG RETRD Maximum Timing Retard from CAN (Limit 2). MTU Fault Codes DGC-2020HD...
  • Page 97 Open load or short circuit on PWM pressure regulating valve channel 2. VLV 2 STR L1 P FUEL SEC FLTDIFF Secondary Filter Fuel Pressure Limit 1 Alarm. AL EIL PROTECTION STR Alarm for Protection Module in response to faulty or manipulated EIL. DGC-2020HD MTU Fault Codes...
  • Page 98 PROACT B Communications Lost. AL NOXA COMM LOST NOX A Communications Lost. AL NOXB COMM LOST NOX B Communications Lost. AL PHYTRNA COM LST PHYTRON A Communications Lost. AL PHYTRNB COM LST PHYTRON B Communications Lost. MTU Fault Codes DGC-2020HD...
  • Page 99 AL SD EXT SPEED DMD SW Channel signals open load. AL SD SPEED DMD Channel signals open load or internal error. INCREASE STR AL SD BINARY SPD DMD Channel signals open load or internal error. LMT STR DGC-2020HD MTU Fault Codes...
  • Page 100 DPF Periodic Rigorous TM Alarm. DPF RIG TM SUPPR DPF Rigorous TM Suppressed Alarm. DPF FLASH READ ERR DPF Flash Memory Read Error Alarm. AL EMISSN FLT Emission Fault Alarm. AL EMISSN FLT2 Emission Fault 2 Alarm. MTU Fault Codes DGC-2020HD...
  • Page 101 Temperature Sensor E2 Wrong Position Alarm. WRONG POS TMP SNS E3 Temperature Sensor E3 Wrong Position Alarm. L1 P CHARGE AIR B Charge Air B Pressure (Limit 1) Alarm. L2 P CHARGE AIR B Charge Air B Pressure (Limit 2) Alarm. DGC-2020HD MTU Fault Codes...
  • Page 102 Bypass Valve Defect Alarm. AL ASH VOLUME Ash Volume Alarm. ECU NT CLS ECO FLAP A ASO Flap A not closed by ECU Alarm. ECU NT CLS ECO FLAP B ASO Flap B not closed by ECU Alarm. MTU Fault Codes DGC-2020HD...
  • Page 103 SCR F1 SU ADBLUE QNTY SCR F1 SU ADBLUE Quantity. SCR F2 SU ADBLUE QNTY SCR F2 SU ADBLUE Quantity. SCR ADBLUE PRESSR SCR ADBLUE Pressure Alarm. SCR SU PRIME REQUEST SCR SU Priming Request Alarm. DGC-2020HD MTU Fault Codes...
  • Page 104 Exhaust Temperature After SCR F3 (Limit 1) Alarm. L2 TEXH AFT SCRF3 Exhaust Temperature After SCR F3 (Limit 2) Alarm. AL MIC5 YELLOW MIC 5 Yellow Alarm. AL MIC5 RED MIC 5 Red Alarm. AL MIC5 COMM LOST MIC 5 Comms Lost Alarm. MTU Fault Codes DGC-2020HD...
  • Page 105 Turbo Charger 5 Overspeed (Limit 1). SS ETC5 OVERSPEED Turbo Charger 5 Overspeed (Limit 2). ADBLUE TEMP HI F1 ADBLUE (DEF) Temperature Too High F1 Alarm. ADBLUE TEMP HI F2 ADBLUE (DEF) Temperature Too High F2 Alarm. DGC-2020HD MTU Fault Codes...
  • Page 106 INJ DRIFT LMT1 CYL A9 Cylinder A9 Injector Drift Limit 1 Alarm. 1041 INJ DRFT LMT1 CYL A10 Cylinder A10 Injector Drift Limit 1 Alarm. 1042 INJ DRIFT LMT1 CYL B1 Cylinder B1 Injector Drift Limit 1 Alarm. MTU Fault Codes DGC-2020HD...
  • Page 107 F2 T DEF TOO HI F2 DEF Temperature Too High Alarm. 1087 LO F2 TEXH BFR SCR F2 Exhaust Temperature before SCR Too Low Alarm. 1088 LO F2 TEXH AFT SCR F2 Exhaust Temperature after SCR Too Low Alarm. DGC-2020HD MTU Fault Codes...
  • Page 108 9469300996 Rev C MTU Fault Codes DGC-2020HD...
  • Page 109: Diagnostic Trouble Codes

    There are 16 configurable DGC detection elements that can be utilized for handling of proprietary DTCs that may not be stored in the DGC-2020HD. For more information, refer to the Configurable J1939 Diagnostics Trouble Code (DTC) Detection chapter in the Configuration manual.
  • Page 110 INTAKE AIR PRESSR Intake Air Pressure Air Filt Restricted Air Filter Restriction (High) AIR FLTR DIF PRS Air Filter Differential Pressure Barometrc Prs INVLD Barometric Pressure (Invalid) Barometrc Prs ERR Barometric Pressure (Error) BAROMETRIC PRESS Barometric Pressure Diagnostic Trouble Codes DGC-2020HD...
  • Page 111 Caption used on front panel for Display of J1939 Parameter TR OUTPUT SHAFT SPD Transmission Output Shaft Speed Vehicle Identification Number Data Mismatch with other VIN Data MisMatch controllers ENGINE HOURS Engine Run Time in Hours TOTAL FUEL USED Total Fuel Usage DGC-2020HD Diagnostic Trouble Codes...
  • Page 112 Fuel pressure is low Fuel Shutoff Malfunctn Fuel shutoff is shorted or open ENG POSITION SENSOR Engine Position Sensor Pump Pos Sns Noisy Pump Position Sensor Input Noise Pump Pos Sns Curr LO Pump Position Sensor Current (Low) Diagnostic Trouble Codes DGC-2020HD...
  • Page 113 Cylinder #6 EUI Circuit (Open) Cyl 6 EUI Ckt SHORT Cylinder #6 EUI Circuit (Shorted) Cyl 6 EUI Ckt MECH FL Cylinder #6 EUI Circuit (Mechanical Failure) Cyl 6 EUI QR INVLD Cylinder #6 EUI Circuit QR Code (Invalid) DGC-2020HD Diagnostic Trouble Codes...
  • Page 114 Knock Sensor 1 Heater Circuit 2 UEGO Heater Circuit #02 HEATER REGEN SYSTM Heater Regeneration System REQ SPD DATA ERRATIC Speed Demand Data is erratic Spd/Trq Msg INVLD Vehicle Speed/Torque Message Invalid ENGINE REQSTED SPEED Engine Requested Speed Diagnostic Trouble Codes DGC-2020HD...
  • Page 115 Turbo Charger 2 Oil Pressure 1169 TURBO CH2 SPEED Turbo 2 Speed 1170 TURBO CH3 SPEED Turbo 3 Speed 1171 TURBO CH4 SPEED Turbo 4 Speed 1172 Trbo Cmp Tmp Volt HI Turbo Compressor Inlet Temp Input Voltage (High) DGC-2020HD Diagnostic Trouble Codes...
  • Page 116 Engine Starter Solenoid Lockout Relay Driver Circuit 1322 MULTI CYL MISFIRE Misfire detected on multiple engine cylinders 1323 MISFIRE CYLINDER 1 Misfire detected on a single engine cylinder 1324 MISFIRE CYLINDER 2 Misfire detected on a single engine cylinder Diagnostic Trouble Codes DGC-2020HD...
  • Page 117 ECU MAIN RELAY ECM Main Relay 1557 Fan 2 Drive State Fan 2 Drive State 1569 Engine Torque Derate Engine Torque Derate 1569 Fuel Derate Fuel Derate 1623 TACOGRPH OUT SHFT SPD Tachograph Output Shaft Speed DGC-2020HD Diagnostic Trouble Codes...
  • Page 118 INJECTOR GROUP 1 Engine Injector Group 1 2798 INJECTOR GROUP 2 Engine Injector Group 2 2899 START ENABL DEV 1 CFG Engine Start Enable Device 1 Configuration 2980 Fuel Pressure Fuel Pressure 3031 DEF TEMP DEF Temperature Diagnostic Trouble Codes DGC-2020HD...
  • Page 119 FUEL VLV LK TEST CTL Engine Fuel Shutoff Valve Leak Test Control 3605 COOLANT PUMP CTL Coolant Pump Control 3607 Engine Shutdown Engine Emergency (Immediate) Shutdown Indication 3609 DPF INTAKE PRESSR 1 DPF Intake Pressure 1 DGC-2020HD Diagnostic Trouble Codes...
  • Page 120 Purge did not complete within the maximum allowed time 516098 Knock Sensr 2 Knock Sensor 2 516131 Propane/Gas Lockoff Propane/Natural Gas Lockoff 520555 UEGO INRC Manufacturer Assignable SPN – Contact Engine Manufacturer for details. 520556 EXH Gas Sensr 2 Exhaust Gas Sensor 2 Diagnostic Trouble Codes DGC-2020HD...
  • Page 121 Manufacturer for details 523420 ECU ERROR ECU Error - Manufacturer Assignable SPN – Contact Engine Manufacturer for details Multi State Switch 1 - Manufacturer Assignable SPN – Contact 523450 MULTI STATE SWITCH 1 Engine Manufacturer for details DGC-2020HD Diagnostic Trouble Codes...
  • Page 122 Manufacturer for details 523613 RAIL PRESSURE Fuel Injection Rail Press - Manufacturer Assignable SPN – Contact Engine Manufacturer for details ure 523615 METERING UNIT VALVE Metering Unit Valve - Manufacturer Assignable SPN – Contact Engine Manufacturer for details Diagnostic Trouble Codes DGC-2020HD...
  • Page 123 523617 ECU ERROR ECU Error - Manufacturer Assignable SPN – Contact Engine Manufacturer for details Table 9. DTCs Displayed by the DGC-2020HD (FMI Strings) String Displayed Description DATA HI MOST SEVERE Data is higher than expected at the most severe level...
  • Page 124 9469300996 Rev C Diagnostic Trouble Codes DGC-2020HD...
  • Page 125: Event List

    32-5 Rvs Pwr Alarm Reverse power trip Alarm 32-5 Rvs Pwr Prealarm Reverse power trip Pre-Alarm 32-6 kW Ovrld Alarm kW overload trip Alarm 32-6 kW Ovrld Prealarm kW overload trip Pre-Alarm 32-6 Rvs Pwr Alarm reverse power trip Alarm DGC-2020HD Event List...
  • Page 126 Alarm 47-5 Volt Phs Imbal Prealarm Phase voltage imbalance trip Pre-Alarm 47-6 Volt Phs Imbal Alarm Phase voltage imbalance trip Alarm 47-6 Volt Phs Imbal Prealarm Phase voltage imbalance trip Pre-Alarm 51-1 OvrCurr Alarm Overcurrent trip Alarm Event List DGC-2020HD...
  • Page 127 81-2 UndFreq Alarm Under frequency trip Alarm 81-2 UndFreq Prealarm Under frequency trip Pre-Alarm 81-3 OvrFreq Alarm Over frequency trip Alarm 81-3 OvrFreq Prealarm Over frequency trip Pre-Alarm 81-3 ROCOF Alarm Rate of change of frequency trip Alarm DGC-2020HD Event List...
  • Page 128 AEM-2020 1 duplicate AEM Status Only AEM1 Global Warning AEM-2020 1 global warning Status Only AEM1 In1 Out Range AEM-2020 1 Input 1 Out of Range Alarm AEM1 In1 Out Range AEM-2020 1 Input 1 Out of Range Pre-Alarm Event List DGC-2020HD...
  • Page 129 AEM-2020 1 Input 5 Out of Range Alarm AEM1 In5 Out Range AEM-2020 1 Input 5 Out of Range Pre-Alarm AEM1 In5 T1 Alarm AEM-2020 1 Input 5 Threshold 1 Alarm AEM1 In5 T1 Prealarm AEM-2020 1 Input 5 Threshold 1 Pre-Alarm DGC-2020HD Event List...
  • Page 130 AEM1 Out2 Out Range A AEM-2020 1 Output 2 Out of Range Alarm AEM1 Out2 Out Range PA AEM-2020 1 Output 2 Out of Range Pre-Alarm AEM1 Out3 Out Range A AEM-2020 1 Output 3 Out of Range Alarm Event List DGC-2020HD...
  • Page 131 AEM-2020 1 RTD 4 Threshold 2 Pre-Alarm AEM1 RTD4 T3 Alarm AEM-2020 1 RTD 4 Threshold 3 Alarm AEM1 RTD4 T3 Prealarm AEM-2020 1 RTD 4 Threshold 3 Pre-Alarm AEM1 RTD4 T4 Alarm AEM-2020 1 RTD 4 Threshold 4 Alarm DGC-2020HD Event List...
  • Page 132 AEM-2020 1 RTD 8 Threshold 3 Pre-Alarm AEM1 RTD8 T4 Alarm AEM-2020 1 RTD 8 Threshold 4 Alarm AEM1 RTD8 T4 Prealarm AEM-2020 1 RTD 8 Threshold 4 Pre-Alarm AEM1 TC1 T1 Alarm AEM-2020 1 Thermocouple 1 Threshold 1 Alarm Event List DGC-2020HD...
  • Page 133 AEM-2020 2 Input 3 Out of Range Alarm AEM2 In3 Out Range AEM-2020 2 Input 3 Out of Range Pre-Alarm AEM2 In3 T1 Alarm AEM-2020 2 Input 3 Threshold 1 Alarm AEM2 In3 T1 Prealarm AEM-2020 2 Input 3 Threshold 1 Pre-Alarm DGC-2020HD Event List...
  • Page 134 AEM-2020 2 Input 7 Threshold 1 Alarm AEM2 In7 T1 Prealarm AEM-2020 2 Input 7 Threshold 1 Pre-Alarm AEM2 In7 T2 Alarm AEM-2020 2 Input 7 Threshold 2 Alarm AEM2 In7 T2 Prealarm AEM-2020 2 Input 7 Threshold 2 Pre-Alarm Event List DGC-2020HD...
  • Page 135 AEM-2020 2 RTD 2 Threshold 2 Pre-Alarm AEM2 RTD2 T3 Alarm AEM-2020 2 RTD 2 Threshold 3 Alarm AEM2 RTD2 T3 Prealarm AEM-2020 2 RTD 2 Threshold 3 Pre-Alarm AEM2 RTD2 T4 Alarm AEM-2020 2 RTD 2 Threshold 4 Alarm DGC-2020HD Event List...
  • Page 136 AEM-2020 2 RTD 6 Threshold 3 Pre-Alarm AEM2 RTD6 T4 Alarm AEM-2020 2 RTD 6 Threshold 4 Alarm AEM2 RTD6 T4 Prealarm AEM-2020 2 RTD 6 Threshold 4 Pre-Alarm AEM2 RTD7 Out Range AEM-2020 2 RTD 7 Out of Range Alarm Event List DGC-2020HD...
  • Page 137 AEM-2020 3 Input 1 Out of Range Alarm AEM3 In1 Out Range AEM-2020 3 Input 1 Out of Range Pre-Alarm AEM3 In1 T1 Alarm AEM-2020 3 Input 1 Threshold 1 Alarm AEM3 In1 T1 Prealarm AEM-2020 3 Input 1 Threshold 1 Pre-Alarm DGC-2020HD Event List...
  • Page 138 AEM-2020 3 Input 5 Threshold 1 Alarm AEM3 In5 T1 Prealarm AEM-2020 3 Input 5 Threshold 1 Pre-Alarm AEM3 In5 T2 Alarm AEM-2020 3 Input 5 Threshold 2 Alarm AEM3 In5 T2 Prealarm AEM-2020 3 Input 5 Threshold 2 Pre-Alarm Event List DGC-2020HD...
  • Page 139 AEM3 Out3 Out Range A AEM-2020 3 Output 3 Out of Range Alarm AEM3 Out3 Out Range PA AEM-2020 3 Output 3 Out of Range Pre-Alarm AEM3 Out4 Out Range A AEM-2020 3 Output 4 Out of Range Alarm DGC-2020HD Event List...
  • Page 140 AEM-2020 3 RTD 4 Threshold 3 Pre-Alarm AEM3 RTD4 T4 Alarm AEM-2020 3 RTD 4 Threshold 4 Alarm AEM3 RTD4 T4 Prealarm AEM-2020 3 RTD 4 Threshold 4 Pre-Alarm AEM3 RTD5 Out Range AEM-2020 3 RTD 5 Out of Range Alarm Event List DGC-2020HD...
  • Page 141 AEM-2020 3 RTD 8 Threshold 4 Pre-Alarm AEM3 TC1 T1 Alarm AEM-2020 3 Thermocouple 1 Threshold 1 Alarm AEM3 TC1 T1 Prealarm AEM-2020 3 Thermocouple 1 Threshold 1 Pre-Alarm AEM3 TC1 T2 Alarm AEM-2020 3 Thermocouple 1 Threshold 2 Alarm DGC-2020HD Event List...
  • Page 142 AEM-2020 4 Input 3 Threshold 1 Alarm AEM4 In3 T1 Prealarm AEM-2020 4 Input 3 Threshold 1 Pre-Alarm AEM4 In3 T2 Alarm AEM-2020 4 Input 3 Threshold 2 Alarm AEM4 In3 T2 Prealarm AEM-2020 4 Input 3 Threshold 2 Pre-Alarm Event List DGC-2020HD...
  • Page 143 AEM-2020 4 Input 7 Threshold 2 Alarm AEM4 In7 T2 Prealarm AEM-2020 4 Input 7 Threshold 2 Pre-Alarm AEM4 In7 T3 Alarm AEM-2020 4 Input 7 Threshold 3 Alarm AEM4 In7 T3 Prealarm AEM-2020 4 Input 7 Threshold 3 Pre-Alarm DGC-2020HD Event List...
  • Page 144 AEM-2020 4 RTD 2 Threshold 3 Pre-Alarm AEM4 RTD2 T4 Alarm AEM-2020 4 RTD 2 Threshold 4 Alarm AEM4 RTD2 T4 Prealarm AEM-2020 4 RTD 2 Threshold 4 Pre-Alarm AEM4 RTD3 Out Range AEM-2020 4 RTD 3 Out of Range Alarm Event List DGC-2020HD...
  • Page 145 AEM-2020 4 RTD 6 Threshold 4 Pre-Alarm AEM4 RTD7 Out Range AEM-2020 4 RTD 7 Out of Range Alarm AEM4 RTD7 Out Range AEM-2020 4 RTD 7 Out of Range Pre-Alarm AEM4 RTD7 T1 Alarm AEM-2020 4 RTD 7 Threshold 1 Alarm DGC-2020HD Event List...
  • Page 146 Analog Input 1 Threshold 2 Alarm Analog In 1 T2 Prealarm Analog Input 1 Threshold 2 Pre-Alarm Analog In 1 T3 Alarm Analog Input 1 Threshold 3 Alarm Analog In 1 T3 Prealarm Analog Input 1 Threshold 3 Pre-Alarm Event List DGC-2020HD...
  • Page 147 Auto Restart In Prgrss Auto restart in progress Status Only AVR Output-Out Of Range AVR Output: out of range Alarm Alarm AVR Output-Out of Range AVR Output: out of range Pre-Alarm Prealarm Batt Chargr Fail-Alarm Battery charger failure Alarm DGC-2020HD Event List...
  • Page 148 Alarm CEM1 Input 2 Prealarm CEM-2020 1 Input 2 Pre-Alarm CEM1 Input 3 Alarm CEM-2020 1 Input 3 Alarm CEM1 Input 3 Prealarm CEM-2020 1 Input 3 Pre-Alarm CEM1 Input 4 Alarm CEM-2020 1 Input 4 Alarm Event List DGC-2020HD...
  • Page 149 CEM-2020 3 communication failure Pre-Alarm CEM3 Dup CEM-2020 CEM-2020 3 duplication CEM Status Only CEM3 Global Warning CEM-2020 3 global warning Status Only CEM3 HwMismatch PA CEM-2020 3 hardware mismatch Pre-Alarm CEM3 Input 1 Alarm CEM-2020 3 Input 1 Alarm DGC-2020HD Event List...
  • Page 150 Pre-Alarm CEM4 Input 7 Alarm CEM-2020 4 Input 7 Alarm CEM4 Input 7 Prealarm CEM-2020 4 Input 7 Pre-Alarm CEM4 Input 8 Alarm CEM-2020 4 Input 8 Alarm CEM4 Input 8 Prealarm CEM-2020 4 Input 8 Pre-Alarm Event List DGC-2020HD...
  • Page 151 CnfPrt 05 T2 Prealarm Configurable Protection 5 Threshold 2 Pre-Alarm CnfPrt 05 T3 Alarm configurable protection 5 threshold 3 Alarm CnfPrt 05 T3 Prealarm Configurable Protection 5 Threshold 3 Pre-Alarm CnfPrt 05 T4 Alarm Configurable Protection 5 Threshold 4 Alarm DGC-2020HD Event List...
  • Page 152 CnfPrt 10 T3 Prealarm Configurable Protection 10 Threshold 3 Pre-Alarm CnfPrt 10 T4 Alarm Configurable Protection 10 Threshold 4 Alarm CnfPrt 10 T4 Prealarm Configurable Protection 10 Threshold 4 Pre-Alarm CnfPrt 11 T1 Alarm Configurable Protection 11 Threshold 1 Alarm Event List DGC-2020HD...
  • Page 153 CnfPrt 15 T4 Prealarm Configurable Protection 15 Threshold 4 Pre-Alarm CnfPrt 16 T1 Alarm Configurable Protection 16 Threshold 1 Alarm CnfPrt 16 T1 Prealarm Configurable Protection 16 Threshold 1 Pre-Alarm CnfPrt 16 T2 Alarm Configurable Protection 16 Threshold 2 Alarm DGC-2020HD Event List...
  • Page 154 CnfPrt 21 T1 Prealarm Configurable Protection 21 Threshold 1 Pre-Alarm CnfPrt 21 T2 Alarm Configurable Protection 21 Threshold 2 Alarm CnfPrt 21 T2 Prealarm Configurable Protection 21 Threshold 2 Pre-Alarm CnfPrt 21 T3 Alarm Configurable Protection 21 Threshold 3 Alarm Event List DGC-2020HD...
  • Page 155 CnfPrt 26 T2 Prealarm Configurable Protection 26 Threshold 2 Pre-Alarm CnfPrt 26 T3 Alarm Configurable Protection 26 Threshold 3 Alarm CnfPrt 26 T3 Prealarm Configurable Protection 26 Threshold 3 Pre-Alarm CnfPrt 26 T4 Alarm Configurable Protection 26 Threshold 4 Alarm DGC-2020HD Event List...
  • Page 156 CnfPrt 31 T3 Prealarm Configurable Protection 31 Threshold 3 Pre-Alarm CnfPrt 31 T4 Alarm Configurable Protection 31 Threshold 4 Alarm CnfPrt 31 T4 Prealarm Configurable Protection 31 Threshold 4 Pre-Alarm CnfPrt 32 T1 Alarm Configurable Protection 32 Threshold 1 Alarm Event List DGC-2020HD...
  • Page 157 Config DTC 15 Alarm Configurable DTC 15 Alarm Config DTC 154 Pre-Alarm Configurable DTC 15 Pre-Alarm Config DTC 16 Alarm Configurable DTC 16 Alarm Config DTC 164 Pre-Alarm Configurable DTC 16 Pre-Alarm Config Element 1 Alarm Configurable Element 1 Alarm DGC-2020HD Event List...
  • Page 158 DEF Warning Level 2 Diesel exhaust fluid warning level 2 Pre-Alarm Demand Start Stop Demand start/stop request: start Status Only RequestStart Demand Start Stop Demand start/stop request: stop Status Only RequestStop Diag Trbl Code A Diagnostic trouble code Alarm Event List DGC-2020HD...
  • Page 159 Gen Reverse Rotation Generator reverse rotation Pre-Alarm Gentest Generator test run session is in progress Status Only Gentest Loaded Generator test run session with load is in progress. Status Only Global Sender Fail Alrm Global sender fail Alarm DGC-2020HD Event List...
  • Page 160 Alarm Input 1 Prealarm Input 1 Pre-Alarm Input 10 Alarm Input 10 Alarm Input 10 Prealarm Input 10 Pre-Alarm Input 11 Alarm Input 11 Alarm Input 11 Prealarm Input 11 Pre-Alarm Input 12 Alarm Input 12 Alarm Event List DGC-2020HD...
  • Page 161 Pre-Alarm Loss of ECU Comm A Loss of ECU communications Alarm Loss of ECU Comm PA Loss of ECU communications Pre-Alarm Loss Of Sensing Alarm Loss of sensing Alarm Loss Of Sensing Pre-Alarm Loss of sensing Pre-Alarm DGC-2020HD Event List...
  • Page 162 OEL Alarm Overexcitation limiter Alarm OEL Pre-Alarm Overexcitation limiter Pre-Alarm Off Mode Status Off mode Status Only Oil Pressure SF-Alarm Oil pressure sender failure Alarm Oil Pressure SF-Prealarm Oil pressure sender failure Pre-Alarm Overcrank Alarm Overcrank Status Only Event List DGC-2020HD...
  • Page 163 Status Only Regen Inhbtd PA Regeneration inhibited Pre-Alarm Regen Reqd PA Regeneration required Pre-Alarm Run Mode Status Run mode Status Only Runup Spd Lo PA Run-up speed low Pre-Alarm SCR Forced Purge Isuzu SCR forced purge Pre-Alarm DGC-2020HD Event List...
  • Page 164 VRM RTD Input 3 Out Of Range Trip Pre-Alarm OutOfRange Pre-Alarm VRM RTD Input4 VRM RTD Input 4 Out Of Range Trip Alarm OutOfRange Alarm VRM RTD Input4 VRM RTD Input 4 Out Of Range Trip Pre-Alarm OutOfRange Pre-Alarm Event List DGC-2020HD...
  • Page 165 Alarm VRM RTD4 T2 Pre-Alarm VRM RTD Input 4 Threshold 2 Trip Pre-Alarm VRM RTD4 T3 Alarm VRM RTD Input 4 Threshold 3 Trip Alarm VRM RTD4 T3 Pre-Alarm VRM RTD Input 4 Threshold 3 Trip Pre-Alarm DGC-2020HD Event List...
  • Page 166 VRM RTD8 T4 Pre-Alarm VRM RTD Input 8 Threshold 4 Trip Pre-Alarm VRM uP Reset Alarm VRM-2020 microprocessor reset Alarm Weak Battery PreAlm Weak battery Pre-Alarm Zero Power Req Zero power transfer request to open circuit breaker Status Only Event List DGC-2020HD...
  • Page 167: Troubleshooting

    9469300996 Rev C Troubleshooting If you do not get the results that you expect from the DGC-2020HD, first check the programmable settings for the appropriate function. Use the following troubleshooting procedures when difficulties are encountered in the operation of your genset control system.
  • Page 168 Figure 82. Device Manager Step 3. In the Properties windows, select the Driver tab and click Update Driver. See Figure 83. Figure 83. DGC-2020HD Properties Step 4. Select Browse My Computer for Driver Software as shown in Figure 84. Troubleshooting...
  • Page 169 9469300996 Rev C Figure 84. Update Driver Software - DGC-2020HD Step 5. Click Browse and navigate to C:\Program Files\Basler Electric\USB Device Drivers\USBIO. Click Next. See Figure 85. Figure 85. Update Driver Software - DGC-2020HD Step 6. If a Windows Security window (Figure 86) appears, click Install.
  • Page 170 Check to determine if there are multiple ECUs on the engine. If so, consult the engine manufacturer’s documentation to determine the CAN Bus 2 address of the ECU that will respond to rpm requests. Set the Engine ECU Address setting under the CAN Bus 2 (ECU) Troubleshooting DGC-2020HD...
  • Page 171: Inputs And Outputs

    Use a voltmeter connected between the BATT– terminal (P4-49) and the sender negative terminals on the DGC-2020HD to verify that there is no voltage difference at any time. Any voltage differences may manifest themselves as erratic sender readings. Wiring should be corrected so that no differences exist.
  • Page 172: Ground Faults Detected In Ungrounded System Applications

    Verify that all wiring is properly connected. Refer to the Typical Applications chapter in the Installation manual. Step 2. Ensure that the proper current is present at the DGC-2020HD current sensing inputs 1, 2, 3, 4, 5, and 6. Step 3.
  • Page 173: Generator Breaker Does Not Open When It Should

    • The DGC-2020HD itself when the automatic mains fail transfer (ATS) feature is enabled. • The DGC-2020HD itself when the Run with Load logic element receives a Start pulse in the programmable logic. • The DGC-2020HD itself when started from the Exercise Timer and the Run with Load box is checked in the Generator Exerciser settings.
  • Page 174: Mains Breaker Does Not Open When Mains Fails

    Metering Explorer in BESTCOMSPlus and verify that the Mains Failed status LED is lit when the power on the DGC-2020HD bus voltage input is either out of voltage or frequency range. If necessary, modify the settings on the Settings, Breaker Management, Bus Condition screen to achieve correct detection.
  • Page 175: Synchronizer

    Initiate a breaker close request by one of the methods listed in the Breaker Management chapter in the Configuration manual. Step 3: Check for raise and/or lower pulses coming from the DGC-2020HD if the governor or AVR bias control output type is contact. Step 4: Check the governor and/or AVR bias analog outputs on the DGC-2020HD with a volt meter if the governor or AVR bias control output type is analog.
  • Page 176: Speed Bias

    Load Anticipation Large Frequency Overshoot on Recovery Kla Gain may be too high and GOV output may be saturated. See Figure 88. Navigate to Settings, Bias Control Settings, Governor Bias Control Settings and decrease Load Anticipation, Kla Gain. Troubleshooting DGC-2020HD...
  • Page 177 Settings, Governor Bias Control Settings and decrease Load Anticipation, Tla Washout Filter Constant. Figure 89. Tla Too High Causing Recovery Overshoot Poor Recovery Kla Gain may be too low. See Figure 90. Navigate to Settings, Bias Control Settings, Governor Bias Control Settings and increase Load Anticipation, Kla Gain. DGC-2020HD Troubleshooting...
  • Page 178: Voltage Bias

    Generator Voltage Does Not Change When Voltage Bias Changes As a test, you can force a fixed voltage on the AVR bias output by setting the Min Output Voltage and Max Output Voltage to the same value by navigating to Settings, Programmable Outputs, Analog Output Troubleshooting DGC-2020HD...
  • Page 179: Load Sharing

    If the input status is correct, but the Gen Breaker status under Metering, Status, Bus Condition, Gen is not, check the PLC logic, and verify that the Gen Breaker fed into the DGC-2020HD is tied in logic to the Status input on the Gen Breaker logic element.
  • Page 180 Step 2: Verify generator breaker status is being correctly received as described in Generator Breaker Status is not being received by the DGC-2020HD. If the status is correct, proceed to Step 3. Step 3: Check the Load Share Line operating voltage range by examining the Min. and Max. Voltage parameters found in BESTCOMSPlus®...
  • Page 181: Group Start And Group Stop Requests

    Step 10: If it appears that something is driving the load share line but it is not the DGC-2020HD on one of the non-running units, search for an external device that is driving or loading down the load share lines.
  • Page 182: Dgc-2020Hd Front Panel Diagnostics Screens

    DGC-2020HD Front Panel Diagnostics Screens There are several diagnostic screens in the DGC-2020HD that can be useful for debugging load sharing issues and I/O module related issues. The following debug screens are available: Load Share Line, Control, AEM-2020, CEM-2020, VRM, Mains Power and VRM Control.
  • Page 183 To Mains logic element is true, the Watt Demand will be equal to the base load set point. When the generator breaker is open or the kW controller is disabled, the Watt Demand will always be equal to the value calculated from the voltage that the DGC-2020HD sees on its load share line. •...
  • Page 184 Ramp Status: This indicates the current kvar ramp direction as None, Up, or Down. • var Ramp Demand: This is the normalized var demand that is ramped from the initial var loading upon generator breaker closure to the desired var output. The rate at which the ramp occurs is Troubleshooting DGC-2020HD...
  • Page 185 Volt Error: This is the normalized difference between the measured generator voltage and the voltage to which the DGC-2020HD is trying to synchronize. It will be 0.00 at all times except when the DGC-2020HD is trying to synchronize its generator inputs to its bus input. When synchronizing, this will typically be 0.000 or some relatively small number and move a small...
  • Page 186 9469300996 Rev C • DGC To AEM BP: DGC-2020HD to AEM-2020 Binary Points. This is a 32-bit, bit packed number representing the binary points transmitted from the DGC-2020HD to the AEM-2020. Debug at this level is not necessary. • AEM To DGC BP: AEM-2020 to DGC-2020HD Binary Points. This is a 32-bit, bit packed number representing the binary points transmitted from the AEM-2020 to the DGC-2020HD.
  • Page 187 This screen is useful for debugging VRM-2020 control related issues. It gives visibility into the states of the VRM-2020 regulation modes and limiters in the DGC-2020HD. The VRM Control diagnostics screen is located on the front panel at Metering > Diagnostics > VRM Control.
  • Page 188 9469300996 Rev C Troubleshooting DGC-2020HD...
  • Page 189: Revision History

    9469300996 Rev C Revision History Table 11 provides a historical summary of the changes made to the DGC-2020HD hardware. Application firmware changes are listed in Table 12 and BESTCOMSPlus® changes are listed in Table 13. The corresponding revisions made to this instruction manual are summarized in Table 14. Revisions are listed in chronological order.
  • Page 190 Added Engine ECU Address setting to specify which ECU to correspond with when multiple ECUs are detected on the network • Added support for Volvo EMS2.3 Tier 4 SCR Exhaust System parameter annunciation via proprietary J1939 PGN • Added configurable math functions Revision History DGC-2020HD...
  • Page 191 Display, and Pre-Alarm annunciation Display on the Overview Screen • Added a setting to allow user to modify the domain name used in emails from Basler products • Added more setpoint adjustment capability to volt trim, speed trim, kW, var, and PF controllers •...
  • Page 192 • 3.08.02, Mar-15 Minor regional settings improvement • 3.09.00, Apr-15 Added support for firmware version 1.01.00 (see firmware revision history above) • Analysis view updated with support for 6 plots • 3.10.00, Oct-15 Maintenance release (DECS-150 launch) Revision History DGC-2020HD...
  • Page 193 • C, Jul-18 Added description of rear power LED. • Added statement about DIN Rail and Rear Panel mount options not having an HMI. • Removed “LCD is Blank and all LEDs are Flashing…” from Troubleshooting chapter. DGC-2020HD Revision History...
  • Page 194 9469300996 Rev C Revision History DGC-2020HD...
  • Page 196 Highland IL 62249-1074 USA Suzhou Industrial Park 15-06 Peninsula Plaza Tel: +1 618.654.2341 215122 Suzhou Singapore 179098 Fax: +1 618.654.2351 P.R. CHINA Tel: +65 68.44.6445 email: info@basler.com Tel: +86 512.8227.2888 Fax: +65 68.44.8902 Fax: +86 512.8227.2887 email: singaporeinfo@basler.com email: chinainfo@basler.com...