Proposición 65, estamos notificándole que uno o más productos químicos allí listados pueden estar presentes en los productos que le vendemos. Para obtener más información sobre los productos químicos específicos que este producto contiene, visite https://es.basler.com/Proposición-65. 警告: 加州第65号提案要求对可能含有加州已知的致癌的、导致先天缺陷或其他生殖伤害的化学物质的产品发出...
9469300996 Rev C Preface This instruction manual provides information about the operation of the DGC-2020HD Digital Genset Controller. To accomplish this, the following information is provided: • Controls and indicators • Operating modes • Metering • Alarms • Troubleshooting Conventions Used in this Manual Important safety and procedural information is emphasized and presented in this manual through Warning, Caution, and Note boxes.
Page 4
The availability and design of all features and options are subject to modification without notice. Over time, improvements and revisions may be made to this publication. Before performing any of the following procedures, contact Basler Electric for the latest revision of this manual.
Page 5
For a complete copy of GNU GENERAL PUBLIC LICENSE Version 2, June 1991 or GNU LESSER GENERAL PUBLIC LICENSE Version 2.1, February 1999 refer to www.gnu.org or contact Basler Electric. You, as a Basler Electric Company customer, agree to abide by the terms and conditions of GNU GENERAL PUBLIC LICENSE Version 2, June 1991 or GNU LESSER GENERAL PUBLIC LICENSE Version 2.1, February 1999, and as such...
9469300996 Rev C Controls and Indicators DGC-2020HD controls and indicators are located on the front panel and are intended for local control and monitoring of DGC-2020HD operation. Front-panel controls consist of sealed membrane pushbuttons and an optional touch screen. Front-panel indicators consist of LED indicators and a backlit LCD (liquid crystal display).
Off Pushbutton and Mode Indicator. Pressing this button places the DGC-2020HD in Off mode. The red Off mode LED lights when the DGC-2020HD is in Off mode. This button also resets the Breaker Management Pre-Alarms and all MTU ECU Alarms.
Grasp the tab of the label card and pull free. The label card tab is located on the rear of the DGC-2020HD, see Figure 3. When facing the back of the panel, the label card tab is on the left.
However, critical settings must be initiated using the pushbuttons to prevent accidental operation with the touch screen. Touch screen controls are illustrated in Figure 4. Lettered locators in Figure 4 correspond to the control descriptions of Table 2. Controls and Indicators DGC-2020HD...
Page 13
Edit pushbutton to accept the change. Up and Down Arrows. Touching the Up arrow scrolls the menu options toward the top of the list and touching the Down arrow scrolls the menu options toward the bottom of the list. DGC-2020HD Controls and Indicators...
Login and Permissions When attempting to change a protected setting, the DGC-2020HD displays the Login Required screen. To log in, use the arrow keys to navigate the on-screen keyboard. Press the Edit key to select each character.
Page 15
On the optional touch screen, a dead bus is indicated by a green colored line segment and an energized (failed or stable) is indicated by a red colored line segment. See Figure 6 for the different breaker and bus states. DGC-2020HD Controls and Indicators...
Page 16
System Type setting selection. For details on configuring the system type, see the Device Configuration chapter in the Configuration manual. If no pushbutton activity is detected for 15 minutes, the DGC-2020HD displays the top overview screen. Reset Key Functions Pressing the Reset key while viewing the Overview screen will reset certain active indications.
Page 17
Temperature Detectors (RTD): AEM1 RTD2 AEM1 TC2 Analog Expansion Module 1: Resistance Analog Expansion Module 2: Inputs: AEM2 In1 Temperature Detectors (RTD): AEM1 RTD3 Analog Expansion Module 2: Inputs: AEM2 In2 Analog Expansion Module 2: Inputs: AEM2 In3 DGC-2020HD Controls and Indicators...
Page 18
Temperature Detectors (RTD): AEM3 RTD8 Bus 1 Failed Analog Expansion Module 3: Thermocouples: Bus 1 Forward Rotation AEM3 TC1 Bus 1 Frequency: Frequency Analog Expansion Module 3: Thermocouples: Bus 1 Frequency: Max ROCOF AEM3 TC2 Bus 1 Frequency: ROCOF Controls and Indicators DGC-2020HD...
Page 19
Bus 2 Frequency: Max ROCOF Contact Expansion Module 2: CEM2 Input 3 Bus 2 Frequency: ROCOF Contact Expansion Module 2: CEM2 Input 4 Contact Expansion Module 2: CEM2 Input 5 Bus 2 Power: Max Vector Shift DGC-2020HD Controls and Indicators...
Page 20
Gen Dead Contact Outputs: Output 5 Gen Failed Gen Forward Rotation Contact Outputs: Output 6 Contact Outputs: Output 7 Gen Frequency: Frequency Contact Outputs: Output 8 Gen Frequency: Max ROCOF Gen Frequency: ROCOF Contact Outputs: Output 9 Controls and Indicators DGC-2020HD...
Page 21
Load Percent System Online kW Capacity kW PID System Total kW Capacity Total Fuel Used kW Ramp Status Load Share Active Total Run Time Logic Control Relays: LCR 1-64 Var Demand Var Mode LS Input DGC-2020HD Controls and Indicators...
Page 22
Menu screen options consist of Metering, Settings, and Summary. Metering screens primarily display specific metering information. Settings screens primarily contain settings for configuring the DGC-2020HD. The Summary screen consists of a one-line diagram of the system configuration, mains fail transfer status, bus metering, and breaker command options.
Page 23
Logic Control Relays Remote System Manager Inputs Broadcast Logic Modbus Virtual Switches • Outputs Contact Outputs Analog Outputs Configurable Elements Remote Contact Outputs Remote Analog Outputs • Configurable Protection Configurable Protection 1 to Configurable Protection 32 DGC-2020HD Controls and Indicators...
Page 24
Unit ID Active Seg ID Sys Manager Sys Man UID Start TD 1 Start TD 2 Stop TD • Load Shedding Sys Total Seq Reserve Sys Online Reserve Priority to Shed Shed Delay Shed Fast Delay Controls and Indicators DGC-2020HD...
Page 25
Exercise Timer Relay Control Auto Config Detect Engine Statistics Seven Day Timer • Report Configuration Data Log Trending Sequence of Events Setup Configurable Log Params • Programmable Inputs Contact Inputs Analog Inputs Programmable Functions Remote Contact Inputs DGC-2020HD Controls and Indicators...
Page 27
MB Command (Visible when Mains Breaker control is enabled.) Open, Close, or None • TB Command (Visible when Tie Breaker control is enabled.) Open, Close, or None • TB2 Command (Visible when Tie Breaker 2 control is enabled.) Open, Close, or None DGC-2020HD Controls and Indicators...
Page 28
9469300996 Rev C Controls and Indicators DGC-2020HD...
In Off mode, the DGC-2020HD will not start under any circumstance. It cannot be started automatically. Programmable logic functions normally in this mode. In Run (manual) mode, the DGC-2020HD runs and cannot be shut off automatically. The breaker can be opened or closed through programmable logic inputs. Programmable logic functions normally in this mode.
Page 30
Peak Shave Local Start Request Once the power imported from mains reaches a predetermined level, and the start mode is Single Generator, the local generator is automatically started to pick up the load. The local generator is the Operating Modes DGC-2020HD...
Ready The engine is not running. The DGC-2020HD is ready to run. This is the normal state of the DGC-2020HD in OFF mode, and in AUTO mode when the engine is not running, or in the process of starting or stopping.
Refer to the Controls and Indicators chapter for more information. Tie Breaker Configuration When the DGC-2020HD is configured as a tie breaker controller it does not control a genset. Thus, the standard operating modes described above do not apply. Special operating modes for tie breaker controllers are described below.
The DGC-2020HD provides comprehensive metering of internal and system conditions. These capabilities include extensive parameter metering, status indication, and reporting. Metering Explorer DGC-2020HD metering is accessed through the metering explorer menu on the front panel display or the BESTCOMSPlus ®...
The Engine metering screen (Figure 8) provides information and metering of engine components. Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter in the Configuration manual for their descriptions. Metering DGC-2020HD...
Figure 8. Metering Explorer, Engine Screen Battery Charger 1 and 2 BESTCOMSPlus Navigation Path: Metering Explorer, Battery Charger Front Panel Navigation Path: Metering > Battery Charger Metering, status, and active pre-alarms of the battery charger(s) are displayed on this screen. See Figure DGC-2020HD Metering...
Figure 9. Metering Explorer, Battery Charger Screen Generator BESTCOMSPlus Navigation Path: Metering Explorer, Generator Front Panel Navigation Path: Metering > Gen Metering of the voltage, current, angle, frequency, and vector shift of the generator is displayed on this screen. See Figure 10. Metering DGC-2020HD...
Front Panel Navigation Path: Metering > Bus 1 or Bus 2 Metering of the voltage, current, angle, frequency, and vector shift of Bus 1 and optional Bus 2 is displayed on these screens. See Figure 11. Figure 11. Metering Explorer, Bus 1 and Bus 2 (Optional) Screens DGC-2020HD Metering...
This screen (Figure 13) provides metering of total positive and negative watthours, total positive and negative var hours, and total VA hours for the generator, bus 1, and optional bus 2. The Edit button provides options to upload total watthour and total var hour values to the DGC-2020HD. Metering...
Synchronization screen (Figure 14) in BESTCOMSPlus. Figure 14. Metering Explorer, Synchronization Screen The Synchronization screen is automatically displayed on the front panel while the synchronizer is active. See Figure 15. Figure 15. Front Panel Synchronization Screen DGC-2020HD Metering...
Figure 16. Metering Explorer, Differential Screen Active Setpoints BESTCOMSPlus Navigation Path: Metering Explorer, Active Setpoints Front Panel Navigation Path: Metering > Active Setpoints Active setpoints, active control mode, and active baseload levels are displayed on this screen. See Figure 17. Metering DGC-2020HD...
Loaded Run Time, and Unloaded Run time can be changed by clicking the Edit Cumulative Run Statistics button. This is helpful when installing the DGC-2020HD into a pre-existing system. This allows the current statistics of the genset to be transferred into the DGC-2020HD for uninterrupted tracking.
This screen indicates status of breakers, modes, switches, and I/O connection status. The status is TRUE when the corresponding indicator is lit. See Figure 19 and Figure 20. Status indications differ depending on system configuration. Figure 19. Metering Explorer, Status Screen (Generator and Group Breaker Control) Metering DGC-2020HD...
Front Panel Navigation Path: Metering > Status > Inputs > Remote Contact Inputs > CEM-2020 # There are four remote contact input screens, one for each possible CEM-2020 (Contact Expansion Module). When CEM-2020s are connected, the status of the remote contact inputs, configurable remote Metering DGC-2020HD...
Page 45
BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Remote Analog Inputs, AEM # Inputs, AEM # RTD Inputs Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > AEM-2020 # > RTD Input Temperatures / Raw RTD Inputs Figure 25 illustrates the BESTCOMSPlus RTD Inputs screen. DGC-2020HD Metering...
Page 46
BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Remote Analog Inputs, AEM # Inputs, AEM # Input Values Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > AEM-2020 # Figure 27 illustrates the BESTCOMSPlus Input Values screen. Metering DGC-2020HD...
Page 47
BESTCOMSPlus Navigation Path: Metering Explorer, Inputs, Voltage Regulation Module, VRM RTD Inputs Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > VRM > RTD Input Temperatures / Raw RTD Inputs Figure 28 illustrates the BESTCOMSPlus VRM RTD Inputs screen. DGC-2020HD Metering...
Page 48
Front Panel Navigation Path: Metering > Status > Inputs > Remote Analog Input Values > VRM > RTD Input Temperatures / Raw RTD Inputs Figure 29 illustrates the BESTCOMSPlus VRM RTD Input Values screen and Figure 30 illustrates the VRM-2020 RTD calibration screen. Figure 29. Metering Explorer, Inputs, Voltage Regulation Module, VRM RTD Input Values Metering DGC-2020HD...
Page 49
Front Panel Navigation Path: Metering > Status > Logic Control Relays This screen displays the status of the 64 logic control relays. A logic control relay input is true when the corresponding indicator is lit. See Figure 31. Figure 31. Metering Explorer, Inputs, Logic Control Relays Screen DGC-2020HD Metering...
Front Panel Navigation Path: Metering > Status > Outputs > Contact Outputs This screen indicates the status of the twelve contact outputs and the Start, Run, and Pre-start outputs. The status is TRUE when the corresponding indicator is lit. See Figure 35. DGC-2020HD Metering...
BESTCOMSPlus Navigation Path: Metering Explorer, Outputs, Configurable Elements Front Panel Navigation Path: Metering > Status > Configurable Elements This screen indicates the status of the eight configurable elements. The status is true when the corresponding indicator is lit. See Figure 37. Metering DGC-2020HD...
Page 53
Front Panel Navigation Path: Metering > Status > Outputs > Remote Analog Outputs > AEM -2020 # There are four remote analog output screens, one for each possible AEM-2020 (Analog Expansion Module). Each of these screens displays the scaled and raw values of the four remote analog outputs of DGC-2020HD Metering...
This screen (Figure 41) displays active alarms, pre-alarms, and global soft alarms. Alarms, pre-alarms, and global soft alarms are reset when the DGC-2020HD is set to Off mode. Certain pre-alarms pertaining to system breakers can be reset by pressing the Reset key on the front panel. See the Reporting and Alarms chapter for details.
The ECU Data metering screen (Figure 43) provides information and metering of engine components. Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter for their descriptions. DGC-2020HD Metering...
Page 56
The Isuzu Status metering screen (Figure 44) provides Isuzu engine parameters that may be useful for exhaust system troubleshooting. Figure 44. Metering Explorer, J1939 ECU, Isuzu Status Engine Configuration BESTCOMSPlus Navigation Path: Metering Explorer, J1939 ECU, Engine Configuration Front Panel Navigation Path: Metering > J1939 ECU > J1939 Engine Config Metering DGC-2020HD...
Front Panel Navigation Path: Metering > MTU > MTU Alarms On the MTU Alarms screen (Figure 46), MTU fault codes are displayed in a scrolling window. MTU alarms and MTU pre-alarms are also reported on this screen. The status is true when the corresponding LED is red. DGC-2020HD Metering...
Page 58
Information and metering of engine components is provided by the MTU Status metering screen. Refer to Figure 48. Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter in the Configuration manual for their descriptions. Metering DGC-2020HD...
Page 59
Under certain circumstances, parameters may indicate one of the following codes: NA (not applicable), NC (not connected), NS (not sent), or SF (sender fail). See the Communication chapter in the Configuration manual for their descriptions. Figure 49. Metering Explorer, MTU, MTU Engine Status Screen DGC-2020HD Metering...
BESTCOMSPlus Navigation Path: Metering Explorer, Summary Front Panel Navigation Path: Summary Pertinent bus and engine metering is displayed on the Summary screen (Figure 50) in BESTCOMSPlus. Figure 50. Metering Explorer, Summary Screen The front panel Summary screen is shown in Figure 51. Metering DGC-2020HD...
Figure 51. Front Panel Summary Screen Detailed Summary BESTCOMSPlus Navigation Path: Metering Explorer, Detailed Summary Front Panel Navigation Path: Not available through the front panel Comprehensive bus and engine metering is displayed on the Detailed Summary screen (Figure 52). DGC-2020HD Metering...
The bus view displays the different bus segments in the system. This dynamically changes as breakers are opened and closed. Each of these views is only available if the view is valid for the current system configuration. Metering DGC-2020HD...
Page 63
Every generator in the system has a separate line entry in the table, including units which are not on the local generator’s active segment. Units of measure are stated in the table header, rather than after the actual value. See Figure 55. Figure 55. Metering Explorer, System Status, Generator Screen DGC-2020HD Metering...
Page 64
System Mains Bus BESTCOMSPlus Navigation Path: Metering Explorer, System Status, System Mains Bus Front Panel Navigation Path: Metering > System Status > System Mains Bus The System Mains Bus screen (Figure 58) provides an overall mains bus summary. Metering DGC-2020HD...
Page 65
BESTCOMSPlus Navigation Path: Metering Explorer, System Status, System Load Bus Front Panel Navigation Path: Metering > System Status > System Load Bus The System Load Bus screen (Figure 60) provides an overall load bus summary. Figure 60. Metering Explorer, System Status, System Load Bus Screen DGC-2020HD Metering...
DGC-2020HD. The PC or laptop running BESTCOMSPlus must be connected to the DGC-2020HD via the USB, Ethernet, or Modem (see the Communication chapter for details). Using the Metering Explorer in BESTCOMSPlus, open the Control Panel screen.
Page 67
Front Panel Navigation Path: Not available through front panel The Control Panel VRM (Figure 63) provides options for changing operating modes, selecting setpoint pre-positions, and fine tuning setpoints. The setpoints for AVR and FCR are displayed, as well as function status. DGC-2020HD Metering...
Page 68
Soft Start: The Soft Start indicator changes from gray to green during startup when the soft start function is active. • Null Balance: The Null Balance indicator changes from gray to green when the setpoint of the inactive operating mode (AVR or FCR) matches the setpoint of the active mode. Metering DGC-2020HD...
Front Panel Navigation Path: Metering > Gen Network Status The Generator Network Status metering screen is illustrated in Figure 64. The status of the generator network is available from each DGC-2020HD when the generator is part of a multi-machine network. The System Type setting (found under the BESTCOMSPlus ®...
• System Total kW Capacity indicates the sum of rated power of all generators in the network. The Number of Units parameter displays zero when the DGC-2020HD is not communicating with other DGC-2020HDs on the network. All of these parameters except for Active Segment ID are available to the Configurable Protection function and may be useful for implementing load sharing schemes.
Transferring to Mains: Load is being transferred to the mains bus. • Disabled: DGC-2020HD is in the Off or Run operating mode or in the alarm state. Transfer Delay, Return Delay, Max Parallel Time, Max Transfer Time, Open Transition Delay, and Return Timer indicate the amount of time remaining in the delay or timer.
Diagnostics screens provide metering for kW and var control, load share, and mains power parameters. Control BESTCOMSPlus Navigation Path: Metering Explorer, Diagnostics, Control Front Panel Navigation Path: Metering > Diagnostics > Control Figure 68 illustrates the BESTCOMSPlus Control screen. DGC-2020HD Metering...
Figure 71. Metering Explorer, Diagnostics, VRM Control Analysis BESTCOMSPlus Navigation Path: Metering Explorer, Analysis Front Panel Navigation Path: Not available through the front panel Oscillography of nearly all genset parameters can be monitored in real time using the Analysis screen (Figure 72). DGC-2020HD Metering...
Page 76
(up to six). For example, to monitor Analog Input 1 in the top graph, enable the radio button where the Analog Input 1 row intersects the Parameter 1 column. Metering DGC-2020HD...
Windows clipboard, or to print the event log. Clicking the Refresh button performs a fresh download of the list from the DGC-2020HD. The Clear button provides the option of clearing selected or all event logs. Refer to Figure 74.
Page 80
Clicking the Refresh button performs a fresh download of the list from the DGC-2020HD. The Clear button provides the option of clearing selected or all event logs. Refer to Figure Figure 75. Metering Explorer, Reports, Sequence of Events Setup ®...
Navigation Path: Settings Explorer, Report Configuration, Data Log Setup Front Panel Navigation Path: Settings > Report Configuration > Datalog The data logging function of the DGC-2020HD can record up to 6 oscillography records. DGC-2020HD oscillography records use the IEEE Standard Common Format for Transient Data Exchange (COMTRADE).
Front Panel Navigation Path: Settings > Report Configuration > Trending The trend log records the activity of DGC-2020HD parameters over an extended period of time. When enabled, up to six selectable parameters can be monitored over a user-defined duration ranging from 1 to 720 hours.
(87G) status and creates a differential report. Only one report is stored in nonvolatile memory. When a new report is generated, the DGC-2020HD discards the old report and replaces it with the new one.
An alarm configuration setting determines the type of annunciation that is used. The annunciation types are described in the following paragraphs. Alarm When an alarm condition exists, the following actions are taken by the DGC-2020HD: • Stop the engine by opening the fuel contact output.
Status of each active alarm and pre-alarm is displayed on the Alarms screen (Figure 80). This screen is found in the Metering Explorer. Active pre-alarms are listed in the upper panel, alarms are listed in the lower panel. DGC-2020HD Reporting and Alarms...
Page 86
10 seconds while the Overview screen is displayed. To reset the maintenance interval pre-alarm by using BESTCOMSPlus, use the Metering Explorer to open the Run Statistics screen and click on the Reset Maintenance Interval button. Reporting and Alarms DGC-2020HD...
Metering > MTU > MTU Fault Codes. Each fault code is displayed with a fault description and the fault number. If the DGC-2020HD does not have descriptive information about a fault number that was received, the fault description will display as “NO TEXT AVAILABLE”.
Page 88
ERR REC2 INVALID Checksum fault. LO ECU SUPPLY VOLTS Power supply voltage too low (limit 1). LOLO ECU SUPPLY VOLTS Power supply voltage too low (limit 2). HI ECU SUPPLY VOLTS Power supply voltage too high (limit 1). MTU Fault Codes DGC-2020HD...
Page 89
SD T EXHAUST A Exhaust gas temperature-sensor on A-side defect. SD T EXHAUST B Exhaust gas temperature-sensor on B-side defect. SD P CHARGE AIR Charge air pressure-sensor defect. SD P LUBE OIL Lube oil pressure-sensor defect. DGC-2020HD MTU Fault Codes...
Page 90
SD SPD DEMAND AN Analog speed demand defect. SD SPDMTEST BNCH Short circuit, cable breakage. SD SPINUT Analog spinning value defect. SD LOAD ANLG FLT Filtered analog load pulse signal not available. SD FREQUENCY INPUT Frequency input defect. MTU Fault Codes DGC-2020HD...
Page 91
Short circuit in injector cable of cylinder A6. WIRING CYLNDR A7 Short circuit in injector cable of cylinder A7. WIRING CYLNDR A8 Short circuit in injector cable of cylinder A8. WIRING CYLNDR A9 Short circuit in injector cable of cylinder A9. DGC-2020HD MTU Fault Codes...
Page 92
Short circuit or open load on transistor output plant 5 (TOP 5). AL WIRING TOP 6 Short circuit or open load on transistor output plant 6 (TOP 6). AL MCR EXCEEDED DBR/MCR Function: MCR (Maximum Continuous Rating) in exceeded. MTU Fault Codes DGC-2020HD...
Page 93
High Pre-Engine Coolant Temperature (Limit 2). AL L1 P AUX 2 Auxiliary Pressure 2 Level 1 Alarm. AL L2 P AUX 2 Auxiliary Pressure 2 Level 2 Alarm. LO P FUEL RAIL 2 STR Low pressure on fuel rail 2. DGC-2020HD MTU Fault Codes...
Page 94
Sensor Defect In Exhaust System C Temperature Sensor. SD T EXHAUST D Sensor Defect In Exhaust System D Temperature Sensor. HI T EXHAUST C High Exhaust C Temperature (Limit 1). SS T EXHAUST C High Exhaust C Temperature (Limit 2). MTU Fault Codes DGC-2020HD...
Page 95
Sensor Defect In Oil Coolant Temperature (R2) Sensor. TD ENG SPD SNS DEV Engine Speed Sensor Deviation. SD ENG SPD SENSR 3 Sensor Defect in Engine Speed Third Sensor. SS T COOL RED 2 Coolant Temperature Red 2 Alarm (Limit 2). DGC-2020HD MTU Fault Codes...
Page 96
Intake B Air Pressure After Filter (Limit 2). AL SAM MSG DATA FLT SAM Module Missing Data Fault. L1 CAN MAX TIMG RETRD Maximum Timing Retard from CAN (Limit 1). L2 CAN MAX TIMG RETRD Maximum Timing Retard from CAN (Limit 2). MTU Fault Codes DGC-2020HD...
Page 97
Open load or short circuit on PWM pressure regulating valve channel 2. VLV 2 STR L1 P FUEL SEC FLTDIFF Secondary Filter Fuel Pressure Limit 1 Alarm. AL EIL PROTECTION STR Alarm for Protection Module in response to faulty or manipulated EIL. DGC-2020HD MTU Fault Codes...
Page 98
PROACT B Communications Lost. AL NOXA COMM LOST NOX A Communications Lost. AL NOXB COMM LOST NOX B Communications Lost. AL PHYTRNA COM LST PHYTRON A Communications Lost. AL PHYTRNB COM LST PHYTRON B Communications Lost. MTU Fault Codes DGC-2020HD...
Page 99
AL SD EXT SPEED DMD SW Channel signals open load. AL SD SPEED DMD Channel signals open load or internal error. INCREASE STR AL SD BINARY SPD DMD Channel signals open load or internal error. LMT STR DGC-2020HD MTU Fault Codes...
Page 101
Temperature Sensor E2 Wrong Position Alarm. WRONG POS TMP SNS E3 Temperature Sensor E3 Wrong Position Alarm. L1 P CHARGE AIR B Charge Air B Pressure (Limit 1) Alarm. L2 P CHARGE AIR B Charge Air B Pressure (Limit 2) Alarm. DGC-2020HD MTU Fault Codes...
Page 102
Bypass Valve Defect Alarm. AL ASH VOLUME Ash Volume Alarm. ECU NT CLS ECO FLAP A ASO Flap A not closed by ECU Alarm. ECU NT CLS ECO FLAP B ASO Flap B not closed by ECU Alarm. MTU Fault Codes DGC-2020HD...
Page 103
SCR F1 SU ADBLUE QNTY SCR F1 SU ADBLUE Quantity. SCR F2 SU ADBLUE QNTY SCR F2 SU ADBLUE Quantity. SCR ADBLUE PRESSR SCR ADBLUE Pressure Alarm. SCR SU PRIME REQUEST SCR SU Priming Request Alarm. DGC-2020HD MTU Fault Codes...
Page 104
Exhaust Temperature After SCR F3 (Limit 1) Alarm. L2 TEXH AFT SCRF3 Exhaust Temperature After SCR F3 (Limit 2) Alarm. AL MIC5 YELLOW MIC 5 Yellow Alarm. AL MIC5 RED MIC 5 Red Alarm. AL MIC5 COMM LOST MIC 5 Comms Lost Alarm. MTU Fault Codes DGC-2020HD...
Page 105
Turbo Charger 5 Overspeed (Limit 1). SS ETC5 OVERSPEED Turbo Charger 5 Overspeed (Limit 2). ADBLUE TEMP HI F1 ADBLUE (DEF) Temperature Too High F1 Alarm. ADBLUE TEMP HI F2 ADBLUE (DEF) Temperature Too High F2 Alarm. DGC-2020HD MTU Fault Codes...
Page 107
F2 T DEF TOO HI F2 DEF Temperature Too High Alarm. 1087 LO F2 TEXH BFR SCR F2 Exhaust Temperature before SCR Too Low Alarm. 1088 LO F2 TEXH AFT SCR F2 Exhaust Temperature after SCR Too Low Alarm. DGC-2020HD MTU Fault Codes...
Page 108
9469300996 Rev C MTU Fault Codes DGC-2020HD...
There are 16 configurable DGC detection elements that can be utilized for handling of proprietary DTCs that may not be stored in the DGC-2020HD. For more information, refer to the Configurable J1939 Diagnostics Trouble Code (DTC) Detection chapter in the Configuration manual.
Page 110
INTAKE AIR PRESSR Intake Air Pressure Air Filt Restricted Air Filter Restriction (High) AIR FLTR DIF PRS Air Filter Differential Pressure Barometrc Prs INVLD Barometric Pressure (Invalid) Barometrc Prs ERR Barometric Pressure (Error) BAROMETRIC PRESS Barometric Pressure Diagnostic Trouble Codes DGC-2020HD...
Page 111
Caption used on front panel for Display of J1939 Parameter TR OUTPUT SHAFT SPD Transmission Output Shaft Speed Vehicle Identification Number Data Mismatch with other VIN Data MisMatch controllers ENGINE HOURS Engine Run Time in Hours TOTAL FUEL USED Total Fuel Usage DGC-2020HD Diagnostic Trouble Codes...
Page 112
Fuel pressure is low Fuel Shutoff Malfunctn Fuel shutoff is shorted or open ENG POSITION SENSOR Engine Position Sensor Pump Pos Sns Noisy Pump Position Sensor Input Noise Pump Pos Sns Curr LO Pump Position Sensor Current (Low) Diagnostic Trouble Codes DGC-2020HD...
Page 120
Purge did not complete within the maximum allowed time 516098 Knock Sensr 2 Knock Sensor 2 516131 Propane/Gas Lockoff Propane/Natural Gas Lockoff 520555 UEGO INRC Manufacturer Assignable SPN – Contact Engine Manufacturer for details. 520556 EXH Gas Sensr 2 Exhaust Gas Sensor 2 Diagnostic Trouble Codes DGC-2020HD...
Page 121
Manufacturer for details 523420 ECU ERROR ECU Error - Manufacturer Assignable SPN – Contact Engine Manufacturer for details Multi State Switch 1 - Manufacturer Assignable SPN – Contact 523450 MULTI STATE SWITCH 1 Engine Manufacturer for details DGC-2020HD Diagnostic Trouble Codes...
Page 122
Manufacturer for details 523613 RAIL PRESSURE Fuel Injection Rail Press - Manufacturer Assignable SPN – Contact Engine Manufacturer for details ure 523615 METERING UNIT VALVE Metering Unit Valve - Manufacturer Assignable SPN – Contact Engine Manufacturer for details Diagnostic Trouble Codes DGC-2020HD...
Page 123
523617 ECU ERROR ECU Error - Manufacturer Assignable SPN – Contact Engine Manufacturer for details Table 9. DTCs Displayed by the DGC-2020HD (FMI Strings) String Displayed Description DATA HI MOST SEVERE Data is higher than expected at the most severe level...
Page 124
9469300996 Rev C Diagnostic Trouble Codes DGC-2020HD...
Page 126
Alarm 47-5 Volt Phs Imbal Prealarm Phase voltage imbalance trip Pre-Alarm 47-6 Volt Phs Imbal Alarm Phase voltage imbalance trip Alarm 47-6 Volt Phs Imbal Prealarm Phase voltage imbalance trip Pre-Alarm 51-1 OvrCurr Alarm Overcurrent trip Alarm Event List DGC-2020HD...
Page 127
81-2 UndFreq Alarm Under frequency trip Alarm 81-2 UndFreq Prealarm Under frequency trip Pre-Alarm 81-3 OvrFreq Alarm Over frequency trip Alarm 81-3 OvrFreq Prealarm Over frequency trip Pre-Alarm 81-3 ROCOF Alarm Rate of change of frequency trip Alarm DGC-2020HD Event List...
Page 128
AEM-2020 1 duplicate AEM Status Only AEM1 Global Warning AEM-2020 1 global warning Status Only AEM1 In1 Out Range AEM-2020 1 Input 1 Out of Range Alarm AEM1 In1 Out Range AEM-2020 1 Input 1 Out of Range Pre-Alarm Event List DGC-2020HD...
Page 129
AEM-2020 1 Input 5 Out of Range Alarm AEM1 In5 Out Range AEM-2020 1 Input 5 Out of Range Pre-Alarm AEM1 In5 T1 Alarm AEM-2020 1 Input 5 Threshold 1 Alarm AEM1 In5 T1 Prealarm AEM-2020 1 Input 5 Threshold 1 Pre-Alarm DGC-2020HD Event List...
Page 130
AEM1 Out2 Out Range A AEM-2020 1 Output 2 Out of Range Alarm AEM1 Out2 Out Range PA AEM-2020 1 Output 2 Out of Range Pre-Alarm AEM1 Out3 Out Range A AEM-2020 1 Output 3 Out of Range Alarm Event List DGC-2020HD...
Page 139
AEM3 Out3 Out Range A AEM-2020 3 Output 3 Out of Range Alarm AEM3 Out3 Out Range PA AEM-2020 3 Output 3 Out of Range Pre-Alarm AEM3 Out4 Out Range A AEM-2020 3 Output 4 Out of Range Alarm DGC-2020HD Event List...
Page 140
AEM-2020 3 RTD 4 Threshold 3 Pre-Alarm AEM3 RTD4 T4 Alarm AEM-2020 3 RTD 4 Threshold 4 Alarm AEM3 RTD4 T4 Prealarm AEM-2020 3 RTD 4 Threshold 4 Pre-Alarm AEM3 RTD5 Out Range AEM-2020 3 RTD 5 Out of Range Alarm Event List DGC-2020HD...
Page 144
AEM-2020 4 RTD 2 Threshold 3 Pre-Alarm AEM4 RTD2 T4 Alarm AEM-2020 4 RTD 2 Threshold 4 Alarm AEM4 RTD2 T4 Prealarm AEM-2020 4 RTD 2 Threshold 4 Pre-Alarm AEM4 RTD3 Out Range AEM-2020 4 RTD 3 Out of Range Alarm Event List DGC-2020HD...
Page 145
AEM-2020 4 RTD 6 Threshold 4 Pre-Alarm AEM4 RTD7 Out Range AEM-2020 4 RTD 7 Out of Range Alarm AEM4 RTD7 Out Range AEM-2020 4 RTD 7 Out of Range Pre-Alarm AEM4 RTD7 T1 Alarm AEM-2020 4 RTD 7 Threshold 1 Alarm DGC-2020HD Event List...
Page 146
Analog Input 1 Threshold 2 Alarm Analog In 1 T2 Prealarm Analog Input 1 Threshold 2 Pre-Alarm Analog In 1 T3 Alarm Analog Input 1 Threshold 3 Alarm Analog In 1 T3 Prealarm Analog Input 1 Threshold 3 Pre-Alarm Event List DGC-2020HD...
Page 147
Auto Restart In Prgrss Auto restart in progress Status Only AVR Output-Out Of Range AVR Output: out of range Alarm Alarm AVR Output-Out of Range AVR Output: out of range Pre-Alarm Prealarm Batt Chargr Fail-Alarm Battery charger failure Alarm DGC-2020HD Event List...
Page 149
CEM-2020 3 communication failure Pre-Alarm CEM3 Dup CEM-2020 CEM-2020 3 duplication CEM Status Only CEM3 Global Warning CEM-2020 3 global warning Status Only CEM3 HwMismatch PA CEM-2020 3 hardware mismatch Pre-Alarm CEM3 Input 1 Alarm CEM-2020 3 Input 1 Alarm DGC-2020HD Event List...
Page 158
DEF Warning Level 2 Diesel exhaust fluid warning level 2 Pre-Alarm Demand Start Stop Demand start/stop request: start Status Only RequestStart Demand Start Stop Demand start/stop request: stop Status Only RequestStop Diag Trbl Code A Diagnostic trouble code Alarm Event List DGC-2020HD...
Page 159
Gen Reverse Rotation Generator reverse rotation Pre-Alarm Gentest Generator test run session is in progress Status Only Gentest Loaded Generator test run session with load is in progress. Status Only Global Sender Fail Alrm Global sender fail Alarm DGC-2020HD Event List...
Page 161
Pre-Alarm Loss of ECU Comm A Loss of ECU communications Alarm Loss of ECU Comm PA Loss of ECU communications Pre-Alarm Loss Of Sensing Alarm Loss of sensing Alarm Loss Of Sensing Pre-Alarm Loss of sensing Pre-Alarm DGC-2020HD Event List...
Page 162
OEL Alarm Overexcitation limiter Alarm OEL Pre-Alarm Overexcitation limiter Pre-Alarm Off Mode Status Off mode Status Only Oil Pressure SF-Alarm Oil pressure sender failure Alarm Oil Pressure SF-Prealarm Oil pressure sender failure Pre-Alarm Overcrank Alarm Overcrank Status Only Event List DGC-2020HD...
Page 163
Status Only Regen Inhbtd PA Regeneration inhibited Pre-Alarm Regen Reqd PA Regeneration required Pre-Alarm Run Mode Status Run mode Status Only Runup Spd Lo PA Run-up speed low Pre-Alarm SCR Forced Purge Isuzu SCR forced purge Pre-Alarm DGC-2020HD Event List...
Page 164
VRM RTD Input 3 Out Of Range Trip Pre-Alarm OutOfRange Pre-Alarm VRM RTD Input4 VRM RTD Input 4 Out Of Range Trip Alarm OutOfRange Alarm VRM RTD Input4 VRM RTD Input 4 Out Of Range Trip Pre-Alarm OutOfRange Pre-Alarm Event List DGC-2020HD...
Page 166
VRM RTD8 T4 Pre-Alarm VRM RTD Input 8 Threshold 4 Trip Pre-Alarm VRM uP Reset Alarm VRM-2020 microprocessor reset Alarm Weak Battery PreAlm Weak battery Pre-Alarm Zero Power Req Zero power transfer request to open circuit breaker Status Only Event List DGC-2020HD...
9469300996 Rev C Troubleshooting If you do not get the results that you expect from the DGC-2020HD, first check the programmable settings for the appropriate function. Use the following troubleshooting procedures when difficulties are encountered in the operation of your genset control system.
Page 168
Figure 82. Device Manager Step 3. In the Properties windows, select the Driver tab and click Update Driver. See Figure 83. Figure 83. DGC-2020HD Properties Step 4. Select Browse My Computer for Driver Software as shown in Figure 84. Troubleshooting...
Page 169
9469300996 Rev C Figure 84. Update Driver Software - DGC-2020HD Step 5. Click Browse and navigate to C:\Program Files\Basler Electric\USB Device Drivers\USBIO. Click Next. See Figure 85. Figure 85. Update Driver Software - DGC-2020HD Step 6. If a Windows Security window (Figure 86) appears, click Install.
Page 170
Check to determine if there are multiple ECUs on the engine. If so, consult the engine manufacturer’s documentation to determine the CAN Bus 2 address of the ECU that will respond to rpm requests. Set the Engine ECU Address setting under the CAN Bus 2 (ECU) Troubleshooting DGC-2020HD...
Use a voltmeter connected between the BATT– terminal (P4-49) and the sender negative terminals on the DGC-2020HD to verify that there is no voltage difference at any time. Any voltage differences may manifest themselves as erratic sender readings. Wiring should be corrected so that no differences exist.
Verify that all wiring is properly connected. Refer to the Typical Applications chapter in the Installation manual. Step 2. Ensure that the proper current is present at the DGC-2020HD current sensing inputs 1, 2, 3, 4, 5, and 6. Step 3.
• The DGC-2020HD itself when the automatic mains fail transfer (ATS) feature is enabled. • The DGC-2020HD itself when the Run with Load logic element receives a Start pulse in the programmable logic. • The DGC-2020HD itself when started from the Exercise Timer and the Run with Load box is checked in the Generator Exerciser settings.
Metering Explorer in BESTCOMSPlus and verify that the Mains Failed status LED is lit when the power on the DGC-2020HD bus voltage input is either out of voltage or frequency range. If necessary, modify the settings on the Settings, Breaker Management, Bus Condition screen to achieve correct detection.
Initiate a breaker close request by one of the methods listed in the Breaker Management chapter in the Configuration manual. Step 3: Check for raise and/or lower pulses coming from the DGC-2020HD if the governor or AVR bias control output type is contact. Step 4: Check the governor and/or AVR bias analog outputs on the DGC-2020HD with a volt meter if the governor or AVR bias control output type is analog.
Load Anticipation Large Frequency Overshoot on Recovery Kla Gain may be too high and GOV output may be saturated. See Figure 88. Navigate to Settings, Bias Control Settings, Governor Bias Control Settings and decrease Load Anticipation, Kla Gain. Troubleshooting DGC-2020HD...
Page 177
Settings, Governor Bias Control Settings and decrease Load Anticipation, Tla Washout Filter Constant. Figure 89. Tla Too High Causing Recovery Overshoot Poor Recovery Kla Gain may be too low. See Figure 90. Navigate to Settings, Bias Control Settings, Governor Bias Control Settings and increase Load Anticipation, Kla Gain. DGC-2020HD Troubleshooting...
Generator Voltage Does Not Change When Voltage Bias Changes As a test, you can force a fixed voltage on the AVR bias output by setting the Min Output Voltage and Max Output Voltage to the same value by navigating to Settings, Programmable Outputs, Analog Output Troubleshooting DGC-2020HD...
If the input status is correct, but the Gen Breaker status under Metering, Status, Bus Condition, Gen is not, check the PLC logic, and verify that the Gen Breaker fed into the DGC-2020HD is tied in logic to the Status input on the Gen Breaker logic element.
Page 180
Step 2: Verify generator breaker status is being correctly received as described in Generator Breaker Status is not being received by the DGC-2020HD. If the status is correct, proceed to Step 3. Step 3: Check the Load Share Line operating voltage range by examining the Min. and Max. Voltage parameters found in BESTCOMSPlus®...
Step 10: If it appears that something is driving the load share line but it is not the DGC-2020HD on one of the non-running units, search for an external device that is driving or loading down the load share lines.
DGC-2020HD Front Panel Diagnostics Screens There are several diagnostic screens in the DGC-2020HD that can be useful for debugging load sharing issues and I/O module related issues. The following debug screens are available: Load Share Line, Control, AEM-2020, CEM-2020, VRM, Mains Power and VRM Control.
Page 183
To Mains logic element is true, the Watt Demand will be equal to the base load set point. When the generator breaker is open or the kW controller is disabled, the Watt Demand will always be equal to the value calculated from the voltage that the DGC-2020HD sees on its load share line. •...
Page 184
Ramp Status: This indicates the current kvar ramp direction as None, Up, or Down. • var Ramp Demand: This is the normalized var demand that is ramped from the initial var loading upon generator breaker closure to the desired var output. The rate at which the ramp occurs is Troubleshooting DGC-2020HD...
Page 185
Volt Error: This is the normalized difference between the measured generator voltage and the voltage to which the DGC-2020HD is trying to synchronize. It will be 0.00 at all times except when the DGC-2020HD is trying to synchronize its generator inputs to its bus input. When synchronizing, this will typically be 0.000 or some relatively small number and move a small...
Page 186
9469300996 Rev C • DGC To AEM BP: DGC-2020HD to AEM-2020 Binary Points. This is a 32-bit, bit packed number representing the binary points transmitted from the DGC-2020HD to the AEM-2020. Debug at this level is not necessary. • AEM To DGC BP: AEM-2020 to DGC-2020HD Binary Points. This is a 32-bit, bit packed number representing the binary points transmitted from the AEM-2020 to the DGC-2020HD.
Page 187
This screen is useful for debugging VRM-2020 control related issues. It gives visibility into the states of the VRM-2020 regulation modes and limiters in the DGC-2020HD. The VRM Control diagnostics screen is located on the front panel at Metering > Diagnostics > VRM Control.
Page 188
9469300996 Rev C Troubleshooting DGC-2020HD...
9469300996 Rev C Revision History Table 11 provides a historical summary of the changes made to the DGC-2020HD hardware. Application firmware changes are listed in Table 12 and BESTCOMSPlus® changes are listed in Table 13. The corresponding revisions made to this instruction manual are summarized in Table 14. Revisions are listed in chronological order.
Page 190
Added Engine ECU Address setting to specify which ECU to correspond with when multiple ECUs are detected on the network • Added support for Volvo EMS2.3 Tier 4 SCR Exhaust System parameter annunciation via proprietary J1939 PGN • Added configurable math functions Revision History DGC-2020HD...
Page 191
Display, and Pre-Alarm annunciation Display on the Overview Screen • Added a setting to allow user to modify the domain name used in emails from Basler products • Added more setpoint adjustment capability to volt trim, speed trim, kW, var, and PF controllers •...
Page 192
• 3.08.02, Mar-15 Minor regional settings improvement • 3.09.00, Apr-15 Added support for firmware version 1.01.00 (see firmware revision history above) • Analysis view updated with support for 6 plots • 3.10.00, Oct-15 Maintenance release (DECS-150 launch) Revision History DGC-2020HD...
Page 193
• C, Jul-18 Added description of rear power LED. • Added statement about DIN Rail and Rear Panel mount options not having an HMI. • Removed “LCD is Blank and all LEDs are Flashing…” from Troubleshooting chapter. DGC-2020HD Revision History...
Page 194
9469300996 Rev C Revision History DGC-2020HD...
Page 196
Highland IL 62249-1074 USA Suzhou Industrial Park 15-06 Peninsula Plaza Tel: +1 618.654.2341 215122 Suzhou Singapore 179098 Fax: +1 618.654.2351 P.R. CHINA Tel: +65 68.44.6445 email: info@basler.com Tel: +86 512.8227.2888 Fax: +65 68.44.8902 Fax: +86 512.8227.2887 email: singaporeinfo@basler.com email: chinainfo@basler.com...