Technical specifications
The following specifications apply at 20 °C unless otherwise stated:
Electrical specifications
Insulation range
Nominal test voltages
Terminal voltage accuracy
Insulation accuracy
Short circuit current
Maximum load capacitance
Voltmeter accuracy (DC or AC) 3% ±3 V
Frequency measurement
Frequency accuracy
Voltage range (DC or AC)
Power supply
Battery life
0.1 MΩ to 1 TΩ
250 V , 500 V , 1000 V , 2500 V ,
5000 V
0 to +5% of nominal test voltage
Up to 1 GΩ: All ranges ±5%
±2 digits
Over 1 GΩ:
5000 V ±5% ±0.04% per GΩ
2500 V ±5% ±0.08% per GΩ
1000 V ±5% ±0.2% per GΩ
500 V ±5% ±0.4% per GΩ
250 V ±5% ±0.8% per GΩ
1.4 mA ± 0.5 mA
5 μF
45 Hz to 65 Hz
±2 Hz
25 to 600 V AC or DC
8 x LR6/AA batteries
5 hours @ 5 kV into 100 MΩ with
AA Alkaline LR6
Guard
Environmental specifications
Operating temperature range
Operating humidity
Storage temperature
Insulation protection
Maximum Altitude
Service error with stated environmental limits is twice intrinsic
error
Safety protection
Insulation CAT III 600 V - applicable standard IEC 61010-1:2001
Measurement Category III is applicable to test and measuring
circuits connected to the distribution part of the building's low-
voltage mains installation. This part of the installation is expected
to have a minimum of two levels of over-current protective devices
between the transformer and possible connecting points.
EMC
The product conforms to IEC 61326-1:2005
Dimensions (W x H x D)
Weight
2% error guarding 5 MΩ leakage
on 100 MΩ load
-20 ºC to +55 ºC
90% RH, 0 ºC - 40 ºC
70% RH, 40 ºC - 55 ºC
-30 ºC to +65 ºC
IP40
2000 m
220 mm x 115 mm x 163 mm
1.45 kg
10
Need help?
Do you have a question about the BM5200 and is the answer not in the manual?
Questions and answers