Protection And Error Conditions - Honeywell S4965V3250 Functional Description

Esys controller
Table of Contents

Advertisement

Title: Functional description S4965V3250

6.8 - Protection and error conditions

Several checks are included to protect the boiler and its environment. High Limit switch is constantly monitored, safety
times are constantly compared etc.
Any violation of (programmable) limits (and/or internal thermostat functions) will lead to an error/fault or warning condition.
Severe error will cause a lockout condition which can only be cleared by the reset key on the controller itself. Blocking error
will be resolved automatically if the cause of the error disappeared.
In case of lockout and blocking conditions, Fan will not operate.
Error codes can be divided in 2 groups:
Lock-out condition codes;
Blocking condition codes.
Complete list of errors of the controller is given as following table:
Error Code
Description
LOCK-OUT
1
Flame lockout after ignition trials
2
False Flame indication
3
High Limit error
4
APS related errors
5
Fan Tacho signal error
8
Flame circuit error
9
Gas valve drive circuit error
13
Remote reset lockout (volatile)
21
ADC error
25
CRC error
BLOCKING
26
Reset Knob error
34
Low supply voltage error
The meaning / explanation of the error numbers is as following:
First issue.
SW update and add parameter into list ModBus communication.
Description
Heating & Cooling Appliance Controls
Doc.: S4965V3250E20
Sign.
E.C.N.
I.Mariscak
0131527
I.Mariscak
Honeywell
Date
Rev.
27-Jun-2016
A
03-Aug-2016
B
Page 22/33

Advertisement

Table of Contents
loading

Table of Contents