Counter Configuration (Configuration Word 1); Filter Selection; Counter Configuration - Allen-Bradley 1734-IJ User Manual

Encoder/counter modules
Table of Contents

Advertisement

Counter Configuration (Configuration Word 1)

Use this byte to select the type of counter desired.
07
06
05
04
03
ZI
MD
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
0
1
Filter Selection (Configuration Word 2
This byte sets the A/B/Z input filters

Filter Selection

07
06
05
04
03
0
ZF
BF
AF
0
0
0
0
1
0
1
0
1
0
AB Drives
1
02
01
00
CF
Counter 0
0
0
0
Counter
0
0
1
Encoder X1
0
1
0
Encoder X2
0
1
1
Reserved
1
0
0
Encoder X4
1
0
1
Period/Rate
1
1
0
Reserved
1
1
1
Rate Measurement
Store Count Disabled
Mode 1 - store/continue
Mode 2 - store/wait/resume
Mode 3 - store, reset/wait/start
Mode 4 - store, reset/start
Reserved
Reserved
Reserved
Z input - 0 = not inverted
Z input - 1 = inverted
02
01
00
FS
0
0
0
No Filter
0
0
1
50kHz (10µs + 0µs/-1.6µs)
0
1
0
5kHz (100µs + 0µs/-13.2µs)
1
0
0
500Hz (1.0ms + 0µs/-125µs)
0
0
0
50Hz (10ms + 0ms/-1.25ms)
A input not filtered
A input filtered
B input not filtered
B input filtered
Z input not filtered
Z input filtered
Publication 1734-UM006B-EN-P - August 2005
Input and Output Data
3-5

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

1734-ik

Table of Contents