Allen-Bradley 1734-IJ User Manual page 60

Encoder/counter modules
Table of Contents

Advertisement

A-6
Configure Modules in RSLogix 5000 Software
If You Selected This for Type For This Value
Counter (default)
Encoder X1
Encoder X2
Encoder X4
Period/Rate
Rate Measurement
Publication 1734-UM006B-EN-P - August 2005
3. Refer to the table to make selections for the following entries.
• Store Count Mode
• Rollover
• Preset
• Counter Attenuator
• Frequency Precision
• Gate Multiplier
• Time Base
• Actual Gate Interval
Select
Store Count
Store Count Disabled
Mode
Store-Continue
Store-Wait-Resume
Store, Reset-Wait-Start
Store, Reset-Start
Rollover
1 to 16777216
Preset
0 to 16777215
Counter
0 to 255
Attenuator
Frequency
X 0.0001
Precision
X 0.001
X 0.01
X 0.1
X 1
X 10
X 100
Gate Multiplier
1 to 200
Time Base
10 to 3000 milliseconds
in multiples of 10
Actual Gate
You do not make a
Interval
selection, as this is a static
field you do not configure.
Comments
Default is Store Count Disabled.
Select an option to determine which mode you use
for operating the Z Gate/Reset Terminal,
Default is 16777215.
Select a value greater than the value for Preset.
Default is 0.
Select a value smaller than the value for Rollover.
Default is 1.
Select a value to attenuate the counter display.
Default is X1.
Select a value to multiply the frequency by the factor
selected.
Default is 1.
Select a value so that the product of Gate Multiplier
and Time Base does not exceed 3 seconds
(3000 milliseconds).
Default is 1000.
This is the product of Gate Multiplier and Time Base.
An acceptable value is less than 3 seconds
(3000 milliseconds).