Troubleshoot the Module
Publication 1734-UM006B-EN-P - August 2005
Indication
Probable Cause
Network Status
Off
Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.
Flashing Green
Device is online, but has no connections in the established
state.
Green
Device online and has connections in the established state.
Flashing Red
One or more I/O connections are in timed-out state
Red
Critical link failure with failed communication device is
present. Device detected error that prevents it
communicating on the network.
Flashing
Communication faulted device - the device detected a
Red/Green
network access error and is in communication faulted state.
Device received and accepted an Identify Communication
Faulted Request with long protocol message.
Indication
Probable Cause
Input Status
Off
Input is inactive.
Yellow
Input is active and under control.