Setting Mode; Instruments Mode; Instrument; Description - Siemens 7SR105 Rho User Manual

Motor protection relay
Table of Contents

Advertisement

1.3

Setting Mode

The Settings Mode is reached by pressing the READ DOWN ▼ button from the relay identifier screen.
Once the Settings Mode title screen has been located pressing the READ DOWN ▼ button takes the user into
the Settings mode sub-menus.
Each sub-menu contains the programmable settings of the relay in separate logical groups. The sub menus are
accessed by pressing the TEST/RESET► button. Pressing the ▼ button will scroll through the settings, after the
last setting in each sub menu is reached the next sub menu will be displayed. If a particular sub menu is not
required to be viewed then pressing ▼ will move directly to the next one in the list.
While a setting is being displayed on the screen the ENTER button can be pressed to edit the setting value. If the
relay is setting password protected the user will be asked to enter the password. If an incorrect password is
entered editing will not be permitted. All screens can be viewed if the password is not known.
While a setting is being edited flashing characters indicate the edit field. Pressing the ▲ or ▼ buttons will scroll
through the valid field values. If these buttons are held on, the rate of scrolling will increase.
Once editing is complete pressing the ENTER button stores the new setting into the non-volatile memory.
The actual setting ranges and default values for each relay model can be found in the appendix to this manual.

1.4 Instruments Mode

The Instrument Mode sub-menu displays key quantities and information to aid with commissioning. The following
meters are available and are navigated around by using the ▲,▼and TEST/REST buttons. The text description
shown here is the default information. Depending upon the relay model you have, you may not have all of the
meters shown.

INSTRUMENT

FAVOURITE METERS
→to view
CURRENT METERS
→to view
Primary Current
Ia
Ib
Ic
Secondary Current
Ia
Ib
Ic
Nom Current
Ia
©2018 Siemens Protection Devices Limited
This allows the user to view his previously constructed list of 'favourite
meters' by pressing TEST/RESET ► button and the READ DOWN
button to scroll though the meters added to this sub-group
To construct a sub-group of favourite meters, first go to the desired meter
then press ENTER this will cause a message to appear on the LCD 'Add
To Favourites YES pressing ENTER again will add this to the
FAVOURITE METERS Sub-menu. To remove a meter from the
FAVOURITE METERS sub-menu go to that meter each in the
FAVOURITE METERS sub-menu or at its Primary location press ENTER
and the message 'Remove From Favourites' will appear press ENTER
again and this meter will be removed from the FAVOURITE METERS
sub-group
This is the sub-group that includes all the meters that are associated with
Current
TEST/RESET ► allows access to this sub-group
Displays the 3 phase currents Primary RMS values
0.00A
0.00A
0.00A
Displays the 3 phase currents Secondary RMS values
0.000A
0.000A
0.000A
Displays the 3 Phase currents Nominal RMS values & phase angles with
respect to PPS voltage.
o
0.00xIn----
7SR105 Rho Settings and Instruments

DESCRIPTION

Chapter 2 Page 7 of 16