Siemens 7SR105 Rho User Manual page 136

Motor protection relay
Table of Contents

Advertisement

OBJECT
Object
Variation
Number
50
0
1 (default -
50
see note 1)
50
3
51
1
51
2
52
1
52
2
60
0
60
1
60
2
60
3
60
4
80
1
Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or
3 scans. Default variations are configurable; however, default settings for the configuration parameters are indicated
in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with
qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7).
© 2018 Siemens Protection Devices
Function Codes
Description
(dec)
2 (write)
Time and Date
1 (read)
Time and Date
2 (write)
Time and Date Last
2 (write)
Recorded Time
Time and Date CTO
Unsynchronized
Time and Date CTO
Time Delay Coarse
Time Delay Fine
Not Defined
Class 0 Data
1 (read)
1 (read)
Class 1 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
1 (read)
Class 2 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
1 (read)
Class 3 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
1 (read)
Internal Indications
2 (write)(see note 3)
No Object
13 (cold restart)
(function code only)
No Object
14 (warm restart)
(function code only)
No Object
23 (delay meas.)
(function code only)
No Object
24 (record
(function code only)
current time)
Chapter 4 - 7SR105 Rho · Data Communications Definitions
REQUEST
(Library will parse)
Qualifier Codes
(hex)
17, 27, 28 (index)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
07, 08 (limited qty)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
07 (limited qty)
06 (no range, or all)
06 (no range, or all)
07, 08 (limited qty)
06 (no range, or all)
06 (no range, or all)
07, 08 (limited qty)
06 (no range, or all)
06 (no range, or all)
07, 08 (limited qty)
06 (no range, or all)
00, 01 (start-stop)
00 (start-
stop) index=7
RESPONSE
(Library will respond with)
Function
Qualifier Codes
Codes
(hex)
(dec)
129
07 (limited qty = 1)
(response)
129
(response)
(limited qty = 1)
130
(unsol. resp)
129
(response)
(limited qty = 1)
130
(unsol. resp)
129
(limited qty = 1)
(response)
129
(limited qty = 1)
(response)
129
00, 01 (start-stop)
(response)
Chapter 4 - Page 43 of 70