7SR105 Rho Technical Manual
Address
Description
30241 CB Total Trip Count
30243 CB Delta Trip Count
30301 Ia Last Trip
30303 Ib Last Trip
30305 Ic Last Trip
30313 In Last Trip
30315 Ig Last Trip
30341 LED1-n
30342 LED1-n
30343 INP1-n
30344 INP1-n
30345 OUT1-n
30346 OUT1-n
30347 VRT1-n
30348 VRT1-n
30349 EQN1-n
30350 EQN1-n
30354 CB Wear A
30356 CB Wear B
30358 CB Wear C
30360 CB Wear A Remaining
30362 CB Wear B Remaining
30364 CB Wear C Remaining
30366 CB Wear Minimum
30380 StartCount
30382 Start Count Target
30392 Active Setting Group
30404 I1 Last Trip
30406 I2 Last Trip
30408 IEq Last Trip
30410 IUn Last Trip
30414 Thermal Capacity
30416 Thermal Capacity Available
30418 Last Motor Start Tim
30434 Thermal Capacity Last Start
30436 Last Start Max Current
30438 Last Start Min Voltage
30440 Time To Trip
30456 Thermal Time To Star
30472 CurrentMotorRunTimeM
30488 MotorTotalRunTimeMet
30504 AverageMotorRunTimeM
30520 Time Before Run Time
30536 MotorStopTimeMeter
30552 MotorNumStartsMeter Meter
30554 MotorEmStartsMeter Meter
30556 A66NumberOfStartsMet
Chapter 4 - Page 32 of 70
Format
UINT32
UINT32
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
BITSTRING
BITSTRING
BITSTRING
BITSTRING
BITSTRING
BITSTRING
BITSTRING
BITSTRING
BITSTRING
BITSTRING
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
UINT16
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
STR32
FP_32BITS_3DP
FP_32BITS_3DP
FP_32BITS_3DP
STR32
STR32
STR32
STR32
STR32
STR32
STR32
UINT32
UINT32
UINT32
Mult
Description
1.000000 CB Total Trip Count
1.000000 CB Delta Trip Count
1.000000 Ia Fault
1.000000 Ib Fault
1.000000 Ic Fault
1.000000 In Fault
1.000000 Ig Fault
0.000000 Led 1-16 status
0.000000 Led 17-32 status
0.000000 Input 1-16 status
0.000000 Input 17-32 status
0.000000 Output 1-16 status
0.000000 Output 17-32 status
0.000000 Virtual 1-16 status
0.000000 Virtual 17-32 status
0.000000 Equation 1-16 status
0.000000 Equation 17-32 status
0.000001 CB Wear A
0.000001 CB Wear B
0.000001 CB Wear C
1.000000 CB Wear A Remaining
1.000000 CB Wear B Remaining
1.000000 CB Wear C Remaining
1.000000 CB Wear Minimum
1.000000 Start Count
1.000000 Start Count Target
1.000000 Active Setting Group
1.000000 I1 Fault
1.000000 I2 Fault
1.000000 IEq Fault
1.000000 IUn Fault
1.000000 Thermal Capacity
1.000000 Thermal Capacity Available
1.000000 Last Motor Start Time
Thermal Capacity Last
1.000000
Start
1.000000 Last Start Max Current
1.000000 Last Start Min Voltage
1.000000 Time To Trip
1.000000 Thermal Time To Start
1.000000 Current Motor Run Time
1.000000 Total Motor Run Time
1.000000 Average Motor Run Time
Time Before Run Time
1.000000
Alarm
1.000000 Last Motor Stop Time
1.000000 Total Motor Starts
1.000000 Emergency Starts
1.000000 66 Starts Counter