Invalid configuration states of the ET 200MP on PROFINET IO

Invalid configuration states
The following invalid configuration states of the ET 200MP lead to a short failure of the
ET 200MP IO device or prevent the exchange of user data with the I/O modules.
● More than two power supply modules (PS) inserted to the right of the interface module
● Number of modules exceeds maximum configuration
● Faulty backplane bus (e.g., additional IM present).
● I/O modules of a power segment consume more power than can be provided (overload).
In the case of an overload, the interface module provides diagnostic information,
cyclically checks the connection to the backplane bus and re-establishes it as soon as
possible.
Additional information
You can find additional information on maximum configuration, power budget and power
segments in the system manual S7-1500, ET 200MP Automation system
(https://support.industry.siemens.com/cs/ww/en/view/59191792).
See also:
Status and error displays (Page 36)
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
Manual, 10/2018, A5E32840985-AB
Contents
W#16#0007
B#16#00
B#16#01
Interrupts and diagnostic, error, and system alarms
Note
Manufacturer-specific diagnostics if
the configuration of the interface
module power supply is different from
the parameterized configuration
Power supply of the interface module
is not active.
Power supply of the interface module
is active.
5.3 Alarms
Bytes
2
1
1
1
1
47