Interrupts and diagnostic, error, and system alarms
5.3 Alarms
5.3.5

STOP of the IO controller and recovery of the IO device

STOP of the SIMATIC IO controller
Diagnostics received from the IO device while the IO controller is in STOP state do not
initiate a call of the corresponding OBs when the IO controller starts up. You have to read
the data record E00C
all diagnostics for the slots assigned to an IO controller in an IO device.
Recovery of the SIMATIC IO device
If you want to read the diagnostics that occurred in the STOP state of the IO controller, you
have to read the E00C
diagnostics for the slots assigned to an IO controller in an IO device.
48
using the "RDREC" instruction in the startup OB. This record contains
H
data record using the "RDREC" instruction. This record contains all
H
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)