Data record of the example
The following table shows the structure of the control data record for the above example.
Table 4- 9
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
Manual, 10/2018, A5E32840985-AB
Data record for example "Extending the configuration"
Element
Code
Block length
17
Block ID
196
Version
3
Version
0
Slot 0
00000000
Slot 2
00000010
Slot 3
00000011
Slot 4
00000100
Slot 5
00000101
Slot 6
00001011
Slot 7
00001100
Slot 8
00001101
Slot 9
00001001
Slot 10
00001010
Slot 11
00000110
Slot 12
00000111
Slot 13
00001000
4.3 Configuration control (option handling)
Explanation
Header
The configured slot 0 is the real slot 0.
B
The configured slot 2 is the real slot 2.
B
The configured slot 3 is the real slot 3.
B
The configured slot 4 is the real slot 4.
B
The configured slot 5 is the real slot 5.
B
The configured slot 6 is the real slot 11.
B
The configured slot 7 is the real slot 12.
B
The configured slot 8 is the real slot 13.
B
The configured slot 9 is the real slot 9.
B
The configured slot 10 is the real slot 10.
B
The configured slot 11 is the real slot 6.
B
The configured slot 12 is the real slot 7.
B
The configured slot 13 is the real slot 8.
B