7
ONLINE MODULE CHANGE
7.3.2
(1) Conversion disable
.
(2) Dismounting of module
.
7
- 9
7.3 Online Module Change Procedure
7.3.2 When industrial shipment setting is used and initial setting was made with sequence program
When industrial shipment setting is used and initial setting was
made with sequence program
(a) Set D/A Conversion enable/disable setting (Un\G0) for all channel conversion
disable and turn Operating condition setting request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the actual analog output value,
turn OFF Operating condition setting request (Y9)
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" screen