Scaling Upper/Lower Limit Value (Un\G54 To Un\G65); Ch Increase/Decrease Digital Limit Values (Un\G70 To Un\G81); Ch Warning Output Upper Limit Value/Lower Limit Value (Un\G86 To Un\G97) - Mitsubishi MELSEC-Q series User Manual

Gx configurator-da. channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

3
SPECIFICATIONS

3.4.14 Scaling upper/lower limit value (Un\G54 to Un\G65)

(1) When the scaling function is used, set a digital value input range. (Refer to Section
(2) The setting range is -32000 to 32000.
(3) To validate the settings, ON/OFF of the operating condition setting request (Y9) is
3.4.15 CH
(1) For rate control, set the range where the digital value can be incremented and decre-
(2) The setting range is 0 to 64000 (0 to FA00
(3) The operating condition setting request (Y9) must be turned ON/OFF to validate the
3.4.16 CH warning output upper limit value/lower limit value (Un\G86
(1) Set the upper and lower limit values of the digital input value for providing the warning
(2) The setting range is -32000 to 32000.
(3) The operating condition setting request (Y9) must be turned ON/OFF to validate the
3
- 36
3.4 Buffer Memory
3.4.14 Scaling upper/lower limit value (Un\G54 to Un\G65)
3.2.5.)
Set them so that the scaling upper limit value is greater than the scaling lower limit
value.
If any value outside the setting range is set, an error occurs and the corresponding
error code (Un\G19) is stored.
required. (Refer to Section 3.3.2.)
increase/decrease digital limit values (Un\G70 to Un\G81)
mented in a conversion cycle per channel (6ms). (Refer to Section 3.2.4.)
If any value outside the setting range is set, an error occurs and the corresponding
error code is stored in error code (Un\G19).
settings. (Refer to Section 3.3.2.)
When setting CH
from the sequence program, values from 0 to 32767 can be set as decimal num-
bers without change. Note that this is not applicable to 32768 to 65535. These
values must be converted to hexadecimal numbers before setting.
to Un\G97)
output. (Refer to Section 3.2.3.)
Make setting so that the upper limit value is greater than the lower limit value.
If any value outside the setting range is set, an error occurs and the corresponding
error code (Un\G19) is stored.
settings. (Refer to Section 3.3.2.)
).
H
increase/decrease digital limit values (Un\G70 to Un\G81)