Appendix A

LinkPower Supply Kit

One SmartLink LinkPower Supply (S-LPS) powers up to four wall stations over the
SmartLink™ network.
N o t e :
Due to the similar design for the SmartPack Wall Mount and the SmartSwitch Relay Panel
control terminations, the following instructions may be used for either product.
I n s t a l l a t i o n P r o c e d u r e
The LinkPower supply kit includes a LinkPower supply and four screws.
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 7:
24
You may have only one station power source on the SmartLink network. This
source may be either the LinkPower Supply (S-LPS) or a SmartLink Station Power
Module (S-SPM) which powers up to 16 SmartLink stations. As well, you may
have up to four SmartLink host products in a SmartLink system. One SmartLink
host product (SmartPack, SmartSwitch, Unison DRd with SmartLink or Sensor +
with SmartLink) in the system must have a LinkPower Supply or Station Power
Module installed for wall station power.
Remove power from the control electronics.
a: For a SmartPack Wall Mount, turn the Standby breaker off.
b: For a SmartSwitch relay panel, turn the circuit breaker off at the breaker
panel.
Remove the two screws securing the I/O panel to the chassis.
Fold the I/O panel down to reveal the control terminations.
Step 5
LinkPower
supply
Angle the LinkPower supply board approximately 10° and insert the four pins as
found on the LinkPower supply into the receptacle on the I/O board.
Align the LinkPower supply with the four screw mounts located on the I/O panel
and secure with the four screws provided. Do not over tighten the screws.
Close the I/O panel and secure with the two screws.
Re-apply power to the control electronics.
I/O board
Step 4
SmartPack User Manual