System Sensor FAAST LT FL01 Series Quick Installation Manual page 3

Fire alarm aspiration sensing technology. stand-alone models.
Table of Contents

Advertisement

Figure 7: Sequence (1 to 9) to Mount the Detector on the Bracket
7a
7b
4
0.00
o
7c
6
7
7d
D200-101-00
1
99 mm
41
mm
2
90 mm
5
3
329 mm
8
9
Pipe Hole Configuration
Figure 8 below shows the pipe holes available on the unit. Each
unit has 2 pipe holes per channel connected together like a T-Piece.
If using a 1 channel unit, holes 3 and 4 do not function. Use Table
1 to locate the holes required for the installation:
1
CHANNEL 1
CHANNEL 1 (NOT
USED FOR COMMON
5
CHAMBER UNIT)
Table 1: Pipe Holes Used for Each FAAST LT Model
FAAST LT MODEL 
INLET PIPE HOLE 
FL0111E 
1 and / or 2 
FL0112E 
1 and / or 2 
FL0122E 
Channel 1 ‐ 1 and / or 2 
Channel 2 – 3 and / or 4 
 
Note 1: Pipe holes not used should be kept sealed.
Note 2: Do NOT glue pipes into the pipe holes.
Table 1a: Maximum Number of Pipe Holes Allowed Per Channel
All figures quoted using highest (level 1) sensitivity
CLASS 
PIPE LENGTH 
(m) 
100 
160 (2 x 80) 
Using T‐Piece 
100 
80 
 
Pipe Installation
1
3
2
3
4
CHANNEL 2 (ONLY FUNCTION
ON 2 CHANNEL UNITS)
Figure 8: Pipe Holes
CHANNEL 2 (ONLY
FUNCTIONS ON 2
CHANNEL AND COMMON
6
CHAMBER UNITS)
OUTLET PIPE HOLE 
MAX NUMBER OF HOLES PER 
CHANNEL 
18 (5 x 2mm, 6 x 2.5mm, 3 x 3mm, 
3 x 3.5mm and 1 x 4mm) + 4mm 
non sensing end hole 
9 holes per branch (3 x 2.5mm, 6 x 
3mm) + 3mm non sensing end hole 
6 (2 x 3.5mm, 2 x 4mm, 2 x 5mm 
inc end hole) 
3 (1 x 5mm, 2 x 6mm inc end hole) 
2
I56-3888-105