System Sensor DH400ACDC Installation And Maintenance Instructions Manual
System Sensor DH400ACDC Installation And Maintenance Instructions Manual

System Sensor DH400ACDC Installation And Maintenance Instructions Manual

Air duct smoke detector

Advertisement

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH400ACDC Air Duct Smoke Detector
Before Installing
Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (I56-473),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor. NFPA
Standards 72 and 90A should also be referenced for de-
tailed information.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

Table of Contents

[1]
General Description
[2]
[3]
[4]
[5]
[6]
[7]
[8]
List of Tables and Figures
Fig. 1: Duct Detector Exploded View
Fig. 2: Installation of Sampling Tube Gaskets
Fig. 3: Mounting Location of Speed Nuts
Table 1: Inlet Sampling Tube Selection
Fig. 4: Inlet Sampling Tube
Fig. 5: Sampling Tube Mounting Configurations
Fig. 6: Wiring Diagram
Fig. 7: Wiring Diagram - No Control Panel
Fig. 8: Wiring Diagram - Accessories
Fig. 9: Sampling Tube Filter Installation
Fig. 10: Testing Detector Alarm
Fig. 11: Detector Head Removal
Fig. 12: RTS451/RTS451KEY Test Coil Installation
Fig. 13: Photo Head Exploded View
Fig. 14: Ion Head Exploded View
D400-13-00
[1] General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense
the presence of smoke in the duct.
Model DH400ACDC Air Duct Smoke Detectors are supplied
with model 1451DH ionization detector heads or model
2451 photoelectronic detector heads. These two smoke de-
tection methods are combined with an efficient housing de-
sign that samples air passing through a duct and allows
detection of a developing hazardous condition. When suffi-
cient smoke is sensed, an alarm signal is initiated at the fire
control panel monitoring the detector, and appropriate ac-
tion can be taken to shut off fans and blowers, change over
Page
air handling systems, etc. These actions can facilitate the
1
management of toxic smoke and fire gases throughout the
2
areas served by the duct system.
2
2
DH400ACDC detectors are designed to operate from 24
2
VDC, 24 VAC, 120 VAC, or 240 VAC. Alarm and supervisory
8
relay contacts are available for control panel interface
10
(alarm initiation), HVAC control, and other auxiliary func-
12
tions. These detectors are not designed for 2-wire applica-
13
tion.
16
For testing, the alarm can be enabled by a magnet activated
Page
test switch, by insertion of a calibrated test card into the
2
sensing chamber (photoelectronic version only), or by the
3
optional remote test station. The duct smoke detectors
3
latch into alarm state when alarm occurs. LEDs on each de-
3
tector illuminate to provide local alarm indication, and op-
4
tional
accessories
4
capabilities.
6
7
The detector can be reset by a momentary power interrup-
8
tion, by the magnet activated reset switch, or by the op-
8
tional remote test station.
9
9
10
11
11
1
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
offer
a
variety
of
annunciation
I56-555-08

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DH400ACDC and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor DH400ACDC

  • Page 1: Table Of Contents

    1-800-SENSOR2, FAX: 630-377-6495 Before Installing [1] General Description Please thoroughly read the System Sensor Guide for Proper An HVAC system supplies conditioned air to virtually every Use of Smoke Detectors in Duct Applications (I56-473), area of a building. Smoke introduced into this air duct sys- which provides detailed information on detector spacing, tem will be distributed to the entire building.
  • Page 2: Exploded View Of Duct Detector Components

    [5.1] Verify Duct Air Flow Direction And Velocity mends that the user read NFPA Standards 90A, 72, and 101. Model DH400ACDC detectors are designed to be used in air The DH400ACDC Air Duct Smoke Detectors are listed per handling systems having air velocities of 500 to 4000 feet UL 268A.
  • Page 3 per minute. Be sure to check engineering specifications to of air inlet holes on the tube. This tube must be purchased ensure that the air velocity in the duct falls within these pa- separately. Order the correct length, as specified in Table 1, rameters.
  • Page 4 Figure 4. Air duct detector inlet sampling tube: AIR HOLES INLET FLANGE TUBE PLUG ARROWS AIR FLOW DIRECTION MUST FACE INTO AIR FLOW A78-2047-00 Figure 5. Tube mounting configurations with varying air flow direction: DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW AIR FLOW DIRECTION...
  • Page 5 1 inch to 1-1/4-inch hole under the plate, and tightening the clamping plate screw. where the flange will be used. The DH400ACDC duct detector is designed to operate from 24 VDC, 24 VAC, 120 VAC, or 240 VAC. [5.4.3] Modifications Of Inlet Sampling Tubes There may be applications where duct widths are not what is specified for the installation.
  • Page 6 Figure 6. System wiring diagram for duct detectors using a UL listed control panel (see Figure 8 for wiring of optional accessories): CAUTION Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections. A78-2352-01 D400-13-00 I56-555-08...
  • Page 7 TROUBLE IS REMOVED, AND DURING RESET. OPEN CONTACTS CONTACTS EXTINGUISH OPTIONAL APA451 GREEN “POWER” LED POWER TO INDICATE TROUBLE CONDITION. DH400ACDC APA451 DUCT DETECTOR AUDIBLE PIEZO ALERT WITH ALARM AND POWER (TROUBLE) LEDS. FOR STAND ALONE APPLICATIONS ONLY. APA451 RECOMMENDED FOR COMPLIANCE TO NFPA 90A.
  • Page 8: Duct Detector Maintenance And Test Procedures

    Disable the zone or system under test to prevent more information. Replacement filters can be ordered from unwanted alarms. System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. (Ex- haust tube/intake tube filter P/N F36-05-00). After conducting these tests, record the appropriate infor- mation in the Detector Test Log at the end of this manual.
  • Page 9 Figure 10. Testing detector alarm: Figure 11. Detector head removal: DETECTOR HEAD DETECTOR HEAD TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TEST RESET TEST MAGNET LOCATOR LOCATOR PAINTED SIDE DUCT TOWARD HOUSING HOUSING TWIST CLOCKWISE TO INSTALL A78-2138-00 A78-2139-00 [6.1] Smoke Entry Tests Trouble- If the detector LEDs do not blink or if the [6.1.1] Air Flow...
  • Page 10: Detector Cleaning Procedures

    4. Carefully reinsert the detector head into the duct hous- the RTS451/RTS451KEY manual. The DH400ACDC duct de- ing and wait 50 seconds for power up. Do not hold the tector can be reset by the RTS451/RTS451KEY.
  • Page 11 Figure 13. Photo head exploded view: Figure 14. Ion head exploded view: REMOVABLE HEAD COVER REMOVABLE COVER CLEANING TEST SLOT REMOVABLE SCREEN (P/N RS14) CLEANABLE SCREEN P/N RS24 (W/O THERMAL) LOCK PRONG SENSING CHAMBER HEAD COVER REMOVAL SLOT VANED CHAMBER A78-1213-01 A78-2340-00 screens (RS24) are available.
  • Page 12: Specifications

    [8] Model DH400ACDC Air Duct Smoke Detector Specifications Description HVAC air duct mounted ionization or photoelectronic smoke detector for separately powered systems or stand alone sys- tems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.
  • Page 13: Warranty

    St. Charles, IL 60174. Please include a note describing the malfunction and for a period of three years from date of manufacture. System Sensor makes suspected cause of failure. The Company shall not be obligated to repair no other express warranty for this air duct smoke detector.
  • Page 14 NOTES D400-13-00 I56-555-08...
  • Page 15 NOTES D400-13-00 I56-555-08...
  • Page 16: Detector Test Log

    __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ D400-13-00 I56-555-08 © System Sensor 1997...

Table of Contents