Electrical Data - High Ambient; Agz 026B Through 130B - McQuay AGZXXXBS Series Installation, Operation And Maintenance Manual

Air-cooled scroll compressor chiller
Table of Contents

Advertisement

Electrical Data - High Ambient

Table 29, AGZ 026BB/BH – 070BB/BH, Electrical Data, Single Point
AGZ Unit
026B
030B
035B
040B
045B
050B
055B
060B
065B
070B
NOTES:
1.
2.
3.
IOMM AGZ-5
Minimum
Circuit
Volts
Size
Ampacity
(MCA)
208
147
230
133
380
80
460
68
575
53
208
158
230
144
380
88
460
74
575
59
208
168
230
155
380
96
460
80
575
64
208
187
230
167
380
113
460
84
575
70
208
207
230
188
380
123
460
94
575
78
208
226
230
207
380
132
460
104
575
86
208
249
230
229
380
147
460
115
575
96
208
270
230
248
380
160
460
124
575
105
208
303
230
282
380
164
460
138
575
115
208
323
230
304
380
172
460
150
575
123
Units operating in ambient temperatures above 95°F (35°C) must use the Maximum Fuse or
HACR Breaker size.
All Electrical Data notes are on page 49.
Conduit hubs are not provided.

AGZ 026B through 130B

Power Supply
Recomm'd.
Fuse
Field Wire
Or HACR
Wire
Breaker
Quantity
Gauge
Size
75C
3
1/0
175
3
1/0
150
3
#4
90
3
#4
80
3
#6
60
3
2/0
175
3
1/0
175
3
#3
100
3
#4
90
3
#6
70
3
2/0
200
3
2/0
175
3
#3
110
3
#4
90
3
#6
70
3
3/0
200
3
2/0
200
3
#2
125
3
#4
90
3
#4
80
3
4/0
225
3
3/0
225
3
#1
125
3
#3
110
3
#4
90
3
4/0
225
3
3/0
225
3
1/0
150
3
#2
125
3
#3
100
3
250
250
3
4/0
250
3
1/0
175
3
#2
125
3
#3
110
3
300
300
3
250
250
3
2/0
175
3
#1
150
3
#2
125
3
350
350
3
300
350
3
2/0
200
3
1/0
175
3
#2
125
3
400
400
3
350
350
3
2/0
200
3
1/0
175
3
#1
150
Max. Fuse
Or HACR
Breaker
Size
175
150
90
80
60
175
175
100
90
70
200
175
110
90
70
200
200
125
90
80
225
225
125
110
90
225
225
150
125
100
250
250
175
125
110
300
250
175
150
125
350
350
200
175
125
400
350
200
175
150
43